Controllable Enumerated Status (Enc) - ABB COM600 series User Manual

Modbus serial slave (opc)
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS756913
3.4.5.18.
COM600 series, Version 5.1
Modbus Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Data Format
1 = WORD
(Phase A, B, C, Net,
2 = Integer
Res)
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
Phase Scale
Default: None
Neutral Scale
Default: None
Net Scale
Default: None
Res Scale
Default: None
Common
Update Rate
0...60000
Default: 0

Controllable Enumerated Status (ENC)

Table 3.4.5.18-1 Configurable ENC properties
Property/Parameter
Basic
Common Data Class
Addresses
Control Address
Indication Address
Description
Data format.
Scale used for phase measurement value.
Scale used for neutral.
Scale used for Net.
Scale used for Res.
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
Value or Value range/Default
ENC
0..65535
Default: 0
0...65535
Default: 0
Description
Common data class according
to IEC 61850.
Control address. Holding
register address for the control.
Holding register (4X reference)
address range 40001-49999.
Address 0 equals no informa-
tion available.
Indication address. Holding
register address for the control.
Holding register (4X reference)
address range 40001-49999.
Address 0 equals no informa-
tion available.
39