I/P signal converter Introduction Additional Information — TEIP11 TEIP11-PS I/P signal converter for controlling pneumatic Additional documentation on TEIP11, TEIP11-PS is actuators or conventional positioners for valve available for download free of charge at positioning. www.abb.com/positioners. Alternatively simply scan this code:...
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M Table of contents Change from one to two columns Commissioning ............15 Safety ................3 General information and instructions ........3 Maintenance ............. 15 ...
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M 1 Safety hange from one to two columns Warnings General information and instructions The warnings in these instructions are structured as follows: These instructions are an important part of the product and must be retained for future reference.
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M … 1 Safety Warranty provisions Intended use I/P signal converters for standard signals TEIP11 and TEIP11-PS Using the device in a manner that does not fall within the scope are used to control pneumatic actuators or pneumatic...
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M Change from one to two columns 2 Use in potentially explosive atmospheres Change from one to two columns DANGER Thermal data T4: –40 °C < Tamb < 85 °C Risk of explosion when used with combustible gases T5: –40 °C <...
25.5 V 3.825 W Special conditions The I/P signal converter TEIP11-PS Doc. 901068 or TEIP11-PS Doc. 901069 must be set up outdoors as a pneumatic power supply when used with combustible gases. The supplied gas must be kept sufficiently free of air and oxygen to prevent a potentially explosive atmosphere from forming.
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M Installation instructions The installation, commissioning, maintenance and repair of Requirements for operation with the ‘flameproof devices in potentially explosive atmospheres must only be (enclosure)’ (Ex d) type of protection carried out by appropriately trained personnel. Works may be...
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M 3 Design and function Force balancing takes place at the lever arm, which is mounted The I/P signal converter converts standard electrical signals, e.g. with a tension band. The coil and yoke generate a magnetic field 4 to 20 mA to 0.2 to 1 bar (3 to 15 psi).
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M Designs Control room housing unit for block mounting The control room housing unit for block mounting enables you to install a number of converters in a small space. This design features central air supply via connection block and stop valves in the air connectors of the integrated signal converter.
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M 4 Product identification 5 Transport and storage Name plate Inspection Check the devices immediately after unpacking for possible damage that may have occurred from improper transport. Details of any damage that has occurred in transit must be recorded on the transport documents.
Control room housing unit for block mounting Installation location requirements For this design, a special connection block is used to mount the Prior to installation, check to make sure that the TEIP11 and unit. TEIP11-PS I/P signal converters meet the measurement and safety requirements applicable at the installation location (see Additional documents on page 16).
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M … 6 Installation … Mounting Aluminum / stainless steel field mount housing Installation instructions Position the housing so that the cable gland is facing The sturdy housing unit can be installed outdoors without downwards or sideways, to prevent humidity from penetrating protection.
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M Electrical connections WARNING Cable glands The field mount housings feature a PG 11 cable entry. Risk of injury due to live parts! When the housing is open, contact protection is not provided Aluminum or stainless steel field mount housing and EMC protection is limited.
Pneumatic connections Note Pneumatic data TEIP11 • The TEIP11 and TEIP11-PS I/P signal converters may only be Instrument air operated with instrument air that is free of oil, water, and Free of oil, water, and dust acc. to DIN/ISO 8573-1 dust.
If the tolerance limits are exceeded, this can be corrected All devices delivered to ABB must be free from any hazardous through adjustment. materials (acids, alkalis, solvents, etc.). Two adjustment screws are used for the adjustment process.
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M 10 Recycling and disposal Note Products that are marked with the adjacent symbol may not be disposed of as unsorted municipal waste (domestic waste). They should be disposed of through separate collection of electric and electronic devices.
TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M Change from two to one column 12 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.