C50 1/16-DIN PROCESS CONTROLLER
CONCISE PRODUCT MANUAL – IM/C50
CAUTION:
Installation and configuration should be performed only by
personnel who are technically competent to do so. Local Regulations regarding
electrical installation & safety must be observed.
1. INSTALLATION
Panel-Mounting
The mounting panel must be rigid and may be up to 6.0mm
(0.25 inches) thick. The cut-out required for the instrument is
shown on the right. Instruments may be mounted side-by-side
in a multiple installation for which the cut-out width (for n
instruments) is (48n-4)mm or (1.89n-0.16)inches.
Mounting Panel
Instrument Housing
Ratchets
Gasket
CAUTION:
Do not remove the panel gasket; it is a seal against dust and
moisture.
Rear Terminal Wiring
USE COPPER CONDUCTORS
(EXCEPT FOR T/C INPUT)
Single Strand wire gauge:
Max 1.2mm (18SWG)
CAUTION:
Turn off all power. Remove instrument by gripping the sides of the
front panel and pulling the instrument out of its housing. Note its orientation.
Note: At first power-up the message 
 


 is displayed, as


described in section 8 of this manual. Access to other menus is denied
until configuration mode is completed
2. SELECT MODE
Select mode is used to access the configuration and operation menu functions.
It can be accessed at any time by holding down
Once in select mode, press
required to prevent unauthorised entry to Configuration, Setup & Automatic Tuning modes.
Press
or
to enter the correct code number, then press
Mode
Display
Operator
Set Up
Configuration
45 x 45mm
Product Info
+0.5 –0.0
Auto-Tuning
Note: The instrument will always return automatically to Operator mode if there is no
key activity for 2 minutes.
Slide mounting clamp over the
3. CONFIGURATION MODE
instrument housing towards rear face
of mounting panel until the tongues
First select Configuration mode from Select mode (refer to section 2).
engage in ratchets and instrument is
clamped in position.
Press
to scroll through the parameters, then press
To accept a change
To exit from Configuration mode, hold down
Note: Parameters displayed depends on how instrument has been configured.
Hold instrument firmly in position
(apply pressure to bezel only)
Parameters marked * are repeated in Setup Mode.
Parameter
Input Range/Type
Scale Range
Upper Limit
Scale Range
CAUTION: Check information label on
housing for correct operating voltage
Lower Limit
before connecting supply to Power Input
Decimal point
Fuse: 100 – 240V ac – 1amp anti-surge
position
Control Type
Primary Output
Control Action
Alarm 1Type
High Alm 1 value*
Low Alm 1 value*
Band Alm 1 value*
Dev. Alm 1 value*
NOTE: Option 2 is only available on
Alm 1 Hysteresis*
model C50K-2110-00.
Alarm 2 Type
High Alm 2 value*
Low Alm 2 value*
Band Alm 2 value*
Dev. Alm 2 Value*
Alm 2 Hysteresis*
Loop Alarm
Loop Alarm Time*
Alarm Inhibit
and pressing
.
or
to select the required mode. An unlock code is
to proceed.
Upper
Lower
Description
Default Unlock
Display


   

   



Normal instrument operation.
   






   
Tailor settings to the application.
   



   



Configures the instrument for use.
Check manufacturing information.
   



   



Invoke Pre-Tune or Self-Tune.

   


   



or
to set the required value.
must be pressed, otherwise parameter will revert to previous value.
and press
, to return to Select mode.
Lower
Upper
Adjustment range
Display
Display



   
See following table for possible codes
   



Scale Range Lower Limit +100 to Range Max
Range Min. to Scale Range Upper Limit -100



   
   

0=XXXX, 1=XXX.X, 2=XX.XX, 3=X.XXX


(non-temperature ranges only)
   







Primary (heat) only
   



Primary & Secondary (heat/cool)
   







Reverse Acting



   
Direct Acting
Process High Alarm

   





   
   

Process Low Alarm


   

Deviation Alarm


   



Band Alarm

   


No alarm


   

Range Min. to Range Max
in display units

   


   

1 LSD to span from setpoint in display units


   

+/- Span from setpoint in display units


   

1 LSD to full span in display units



   



   


Process High Alarm

   


Process Low Alarm
   



Deviation Alarm
Band Alarm
   




   
No alarm


   



Range Min. to Range Max
in display units
   






   
1 LSD to span from setpoint in display units
   



+/- Span from setpoint in display units

   


1 LSD to full span in display units

   

(disabled) or 
 (enabled)






1 sec to 99 mins. 59secs



   
(only applies if primary proportional band = 0)
No alarms Inhibited
   



   



   

Alarm 1 inhibited



   
Alarm 2 inhibited


   



Alarm 1 and alarm 2 inhibited
Parameter
Lower
Upper
Display
Display
Output 1 Usage
   


   







   


   




   



   
Codes



   
None

   


   




   


   





   

None
   



       


   



   

Output 2 Usage


   


   



   


   






   

   





   
   



   



Default
   





   

J T/C

   


Range max
(Lin=1000)



   
Range min
Display Strategy



   
(Linear=0)
Config Lock Code

   


1
   



Input Ranges and Types
(See Configuration Mode Parameter


   

Code
Input Type & Range
Code



   
B: 100 – 1824 ºC
bC
bC
L L L L .C C C C
bC
bC
B: 211 – 3315 ºF
L L L L .F F F F
bF
bF
bF
bF
C: 0 – 2320 ºC
CC
CC
CC
CC
NC
NC
NC
NC
C: 32 – 4208 ºF
CF
CF
CF
CF
NF
NF
NF
NF
J: -200 – 1200 ºC
JC
JC
JC
JC
rC
rC
rC
rC
J: -328 – 2192 ºF
JF
JF
JF
JF
rF
rF
rF
rF
Range Max.
J: -128.8 – 537.7 ºC
j j j j .C C C C
SC
SC
SC
SC
Range Min.
J: -199.9 – 999.9 ºF
j j j j .F F F F
SF
SF
SF
SF
       
K: -240 – 1373 ºC
KC
KC
KC
KC
tC
tC
tC
tC
       
K: -400 – 2503 ºF
KF
KF
tF
tF
KF
KF
tF
tF
       
K: -128.8 – 537.7 ºC
k k k k .C C C C
t.C
t.C
t.C
t.C

   


K: -199.9 – 999.9 ºF
K K K K .F F F F
t.F
t.F
t.F
t.F
L: 0 – 762 ºC
LC
LC
LC
LC
P24C
P24C
P24C
P24C
L: 32 – 1403 ºF
LF
LF
LF
LF
Range Max.
Range Min.
       
       
       

   




.


   


   


ABB Limited
Measurement & Analytics
Howard Road, St. Neots
Cambridgeshire, PE19 8EU
UK
Tel: +44 (0)1480 475 321
Fax: +44 (0)1480 217 948
Email: instrumentation@gb.abb.com
Adjustment range
Default
Primary (Heat) Power

   


Secondary (Cool) Power
Alarm 1, Direct
Alarm 1, Reverse
Alarm 2, Direct
Alarm 2, Reverse
Loop Alarm, Direct
Loop Alarm, Reverse
Logical Alarm 1 OR 2, Direct
Logical Alarm 1 OR 2, Reverse
Logical Alarm 1 AND 2, Direct
Logical Alarm 1 AND 2, Reverse
Primary (Heat) Power
   



Secondary (Cool) Power
Alarm 1, Direct
Alarm 1, Reverse
Alarm 2, Direct
Alarm 2, Reverse
Loop Alarm, Direct
Loop Alarm, Reverse
Logical Alarm 1 OR 2, Direct
Logical Alarm 1 OR 2, Reverse
Logical Alarm 1 AND 2, Direct
Logical Alarm 1 AND 2, Reverse
    ,     ,     ,     ,     or     (refer to section 7)
       
0 to 9999

   


 )


Input Type & Range
Code
Input Type & Range
L: 0.0 – 537.7 ºC
PtRh20% vs 40%:
P24F
P24F
P24F
P24F
32 – 3362 ºF
L: 32.0 – 999.9 ºF
N: 0 – 1399 ºC
Pt100: -199 – 800 ºC
PTC
PTC
PTC
PTC
N: 32 – 2551 ºF
Pt100: -328 – 1472 ºF
PtF
PtF
PtF
PtF
R: 0 – 1759 ºC
Pt100: -128.8 – 537.7 ºC
Pt.C C C C
Pt
Pt
Pt
R: 32 – 3198 ºF
Pt100: -199.9 – 999.9 ºF
Pt.F F F F
Pt
Pt
Pt
S: 0 – 1762 ºC




 
0 – 20 mA DC
S: 32 – 3204 ºF


4 – 20 mA DC


 
T: -240 – 400 ºC
0 – 50 mV DC




 
T: -400 – 752 ºF


10 – 50 mV DC


 
T: -128.8 – 400.0 ºC
    

0 – 5 V DC


 
T: -199.9 – 752.0 ºF
1 – 5 V DC




 
0 – 10 V DC




 
PtRh20% vs 40%:
0 – 1850 ºC
2 – 10 V DC




 

Advertisement

loading

Summary of Contents for ABB C50

  • Page 1 Output 1 Usage           Primary (Heat) Power      CONCISE PRODUCT MANUAL – IM/C50       It can be accessed at any time by holding down and pressing ...
  • Page 2 4. SETUP MODE 6. PRODUCT INFORMATION MODE 8. ERROR/FAULT INDICATIONS Parameter Upper Lower Description Display Display Note: Configuration must be completed before adjusting Setup parameters. First select Product information mode from Select mode (refer to section 2). Instrument Configuration & Setup required. Seen at first First select Setup mode from Select mode (refer to section 2).