Table of Contents

Advertisement

Instruction Manual September 2003
milltronics
SF 500

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Milltronics SF 500

  • Page 1 Instruction Manual September 2003 milltronics SF 500...
  • Page 2 Contact SMPI Technical Publications at the following address: Technical Publications Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: techpubs@siemens-milltronics.com For the library of SMPI instruction manuals, visit our Web site: www.siemens-milltronics.com © Siemens Milltronics Process Instruments Inc. 2003...
  • Page 3: Table Of Contents

    Table of Contents Milltronics SF 500 ....................... 1 Milltronics SF 500 features ......................1 The Manual ...............................2 Specifications ........................3 Installation ........................... 6 Dimensions ...............................6 Layout ................................7 Software Updates ...........................8 Interconnection ............................9 System Diagram ...........................9 Flowmeter ...............................10 One Load Cell ..........................10 Two Load Cell ..........................10...
  • Page 4 Material Tests ............................30 % Change ............................30 Material Test ..........................32 Design Changes .............................33 Recalibration ............................33 Routine Zero ..........................33 Initial Zero .............................34 Direct Zero ............................35 Auto Zero ............................35 Routine Span ..........................36 Initial Span ............................37 Direct Span ...........................37 Multispan ............................38 On-line Calibration ..........................41 Factoring ..............................45 Linearization ............................46 Operation ..........................49...
  • Page 5 Connection ..............................70 Wiring Guidelines ........................70 Configuring Communication Ports ....................71 P770 Serial protocols ........................71 P771 Protocol address ........................72 P772 Baud Rate ..........................72 P773 Parity .............................72 P774 Data bits ..........................73 P775 Stop bits ..........................73 P778 Modem attached .......................73 P779 Modem idle time .......................74 P780 RS-232 Transmission interval ..................74 P781 Data message ........................75 Dolphin Protocol ............................76...
  • Page 7: Milltronics Sf 500

    Milltronics SF 500 Note: The Milltronics SF 500 is to be used only in the manner outlined in this instruction manual. The Milltronics SF 500 is a full-feature integrator for use with solids flowmeters. The SF 500 processes the signal from the flowmeter and calculates values for the rate of material flow and totalization.
  • Page 8: The Manual

    If you have any questions, comments, or suggestions about the manual contents, please email us at techpubs@siemens-milltronics.com. For the complete library of Siemens Milltronics manuals, go to www.siemens-milltronics.com. Page 2 Milltronics SF 500 – INSTRUCTION MANUAL...
  • Page 9: Specifications

    • fuse, FU1 2AG, Slo Blo, 2 A, 250 V or equivalent Application • compatible with Siemens Milltronics solids flowmeters or equivalent 1 or 2 load cell flowmeters • compatible with LVDT equipped solids flowmeters, with use of optional interface board Accuracy •...
  • Page 10 • two load cells: non-sensing: Belden 9260, 6 wire shielded, 20 AWG or equivalent 150 m (500 ft.) max sensing: Belden 8418, 8 wire shielded, 20 AWG or equivalent, 300 m (1000 ft.) max Page 4 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 11 24 Vdc at 50 mA, short circuit protected • LVDT interface card: for interface with LVDT solids flowmeters (separately mounted) Weight • 2.6 kg (5.7 lbs.) Approvals • CE*, CSA NRTL/C *EMC performance available upon request. 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 5...
  • Page 12: Installation

    (4 places) customer glands to maintain ingress rating. mounting screw Note: Non-metallic enclosure does not provide grounding between connections. Use grounding type bushings and jumpers. Page 6 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 13: Layout

    The Security Switch is shown in its normal position (to the right). When it is P350 Calibration in the left position it locks out most keypad functions. See Security on page 103. 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 7...
  • Page 14: Software Updates

    • The maximum allowable working voltage between adjacent relay contact shall be 250 V. Software Updates Note: Contact a Siemens Milltronics representative and get the latest software revision before upgrading the software in the SF 500. To update the software you will need: •...
  • Page 15: Interconnection

    Do not run wiring in the same conduit as the high voltage contact or power wiring • Ground shield at one point only. Insulate at junctions to prevent inadvertent grounding. • Typical system capability. Not all components or their maximum quantity may be required. 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 9...
  • Page 16: Flowmeter

    SF 500 terminal 12 to scale RED SF 500 terminal 13 to scale BLK If the load cell wiring colours vary from those shown, or if extra wires are provided, consult Siemens Milltronics. Page 10 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 17: Lvdt

    SF 500 terminal 12 to integrator terminal block ‘+EXC’ SF 500 terminal 13 to integrator terminal block ‘-EXC’ For further connection information on specific LVDTs consult Siemens Milltronics. Note: A common error is missing the connection from SF 500 terminal 2 to SF 500 terminal 17.
  • Page 18: Auxiliary Inputs

    P270 Refer to on page 100 for programming details. Auto Zero Prefeed activated dry contact Auto Zero Refer to on page 35. RS-232 (Port 1) Printers receive common Page 12 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 19: Computers And Modems

    Computers and Modems Typical configurations for connection to a PC compatible computer or modem, using no flow control: DB-9 DB-25 RS-485 (Port 2) Daisy Chain customer device Terminal Device customer device 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 13...
  • Page 20: Remote Totalizer

    Jumper pins 4-6 and 7-8 when using hardware flow control. Otherwise, leave them open. mA Output 1 to customer instrumentation, isolated mA output, 750 Ω maximum load Remote Totalizer supply, 30V max remote totalizer 1 supply, 240V max remote totalizer 2 Page 14 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 21: Relay Output

    100 / 115 / 200 / 230V 50 / 60 Hz select voltage via switch 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 15...
  • Page 22: Ma I/O Board

    Disconnect power before installing or replacing the battery. Installation Steps Open the enclosure lid. Slide the battery into the holder. Be sure to align the + and – terminals correctly. Close and secure enclosure lid. Page 16 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 23: Installing Optional Plug-In Boards

    Installing Optional Plug-in Boards You can order the following optional plug-ins from Siemens Milltronics: SmartLinx module Enhances the existing SF 500 Communications System by providing an interface in one of several popular industrial communications standards. Analog Input / Output board The mA I/O board provides 2 programmable 0/4-20 mA outputs, 2 programmable 0/4-20 mA inputs and a nominal 24V dc supply for loop-powered devices.
  • Page 24: Modes Of Operation

    RUN is the normal or reference mode of operation. It continuously processes the rate signals from the flowmeter to produce internal rate signals. These are used as the basis for totalization (on page 51), mA output, relay control, and communication data. The RUN Page 18 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 25 Enter RUN Mode Enter PROGRAM Mode Press either the ZERO key or the Press either the ZERO key or the ZERO SPAN key to initiate Calibration SPAN key to initiate Calibration 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 19...
  • Page 26: Run Mode

    When in PROGRAM Mode the unit identifies the name of the parameter, the description, and the options or instructions for making a valid entry PROGRAM Mode Display VIEW P001 Language 1-Eng EDIT P001 Language 1-Eng Page 20 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 27: Entering Program Mode

    For direct access to index parameters Enter Rate 100.00 kg/h Or press e.g. access P940-2, load cell B mV signal P940-2 Load Cell mV Signal Test mV reading for B 6.78 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 21...
  • Page 28 P011 Design Rate: from the EDIT mode Enter Rate 200.00 kg/h Enter the CLEAR function Press Value is reset to factory value. P011 Design Rate: e.g. 0.00 kg/h Enter Rate 0.00 kg/h Page 22 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 29: Start Up

    Accept ’1’ as the number of load P003 Number of Load Cells cells. Enter (1 or 2) Press e.g. Accept ’2’ for measurements in P004 Rate Measurement System metric. Select 1-Imperial, 2-Metric 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 23...
  • Page 30 Enter test rate 0.00 t/h Press P017 Test rate: Weight MS 1 e.g. test rate of 75 t/h Enter test rate 0 t/h Press This value is obtained from the design data sheet Page 24 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 31: Load Cell Balancing

    The test rate value should be less than the design rate. If not, contact Siemens Milltronics. P017 Test rate: Weight MS 1 Enter test rate 75 t/h The initial programming requirements are now satisfied. To ensure proper entry of all critical parameter values, return to P002 and review parameters through to P017.
  • Page 32 Access P295 P295 Load Cell Balancing: Select: 1-A&B Press Load Cell Balancing A & B Place weight at cell B and press ENTER test weight Page 26 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 33 Place weight at cell A and press ENTER test weight Press Balancing the load cell Load Cell Balancing A & B requires a subsequent zero Load cells are now balanced. and span calibration 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 27...
  • Page 34: Zero Calibration

    Stop the material flow and apply the test weight to the flowmeter as instructed in the flowmeter manuals. Press Span Calibration. Current Span the current span count Setup test. Press ENTER to Start Page 28 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 35: Run Mode

    Where any inaccuracies exist, correct the system with a manual span adjustment (P019). Perform recalibration of the zero and span routinely to maintain accurate reporting of rate and total. Recalibration Refer now to on page 30. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 29...
  • Page 36: Recalibration

    Test weights are NOT used during material tests. If the span adjust value is not acceptable, repeat the material test to verify repeatability. If the result of the second material test differs considerably, consult Siemens Milltronics or any of its agents.
  • Page 37 3. stop material feed 4. weigh material Access P019 and enter EDIT mode P019 Manual Span Adjust Select 1-% Change 2-Material Test Press P598 Span Adjust Percentage Enter Calculated +/- error 0.00 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 31...
  • Page 38: Material Test

    975.633 kg is the actual weight of Press the material test e.g. the calculated deviation is Material Test Deviation -1.19 displayed as a % of the actual weight Accept 0-No, 1-Yes: Page 32 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 39: Design Changes

    % of Calibration complete. Deviation 0.02 full span Press ENTER to accept value 551418 e.g. the new zero count, if accepted if unacceptable, press to restart 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 33...
  • Page 40: Initial Zero

    Zero Calibration. Current Zero 551413 e.g. the current zero count Clear flowmeter. Press ENTER to start Note: This is the end of zero calibration. Proceed with zero or span recalibration or return to RUN. Page 34 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 41: Direct Zero

    Auto Zero conditions are being met. If material feed resumes during an auto zero function, the zero is aborted and the totalizing function restarts where it left off. 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 35...
  • Page 42: Routine Span

    Setup test. Press ENTER to start This is the end of span calibration. Remove the test weight and return to RUN. Page 36 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 43: Initial Span

    A record of the last valid span count is required. Access P368 and enter EDIT mode P368 Direct Span Entry Enter Span Count 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 37...
  • Page 44: Multispan

    Multispan Selection of Spans 1 and 2 Multispan Selection of Spans 1 to 8 SHLD AUX 1 AUX 2 AUX 3 AUX 4 AUX 5 *Remote contact can be from relay or open collector switch. Page 38 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 45 Select Function [0-13] Enter . This programs auxiliary input 3 (terminal 26), in conjunction with auxiliary input 1 and auxiliary input 2 to read the contact state for span selections 5 to 8. 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 39...
  • Page 46 Selection Aux 2 Aux 3 If required, reset or note the totalizer value, as the process materials being conveyed may Totalization (P619-P648) change. Refer to on page 111. Linearization applies concurrently to spans. Page 40 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 47: On-Line Calibration

    Connect the weigh bin to one of the mA High (e.g. 70%) inputs on the optional mA I/O board of the Milltronics SF 500: either mA input 1, reference weight: terminals 5 and 6; or mA input 2, terminals 10 t...
  • Page 48 Calibrate the mA inputs on the SF 500 to the 4 and 20 mA levels of the weigh bin. 4 mA is calibrated with the weigh bin empty, using P261-01 or –02. 20 mA is calibrated with the weigh bin full, using P262-01 and P262-02. Page 42 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 49 Calibration in progress RLY 1 When the Low limit (30%) is reached, the totalizer is deactivated and the assigned relay is de-energized, which reopens the material feed to the weigh bin. 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 43...
  • Page 50 If you want to reject the results and perform another on-line calibration, press return to P358. Access P358 On-line Calibration Features 0-OFF, 1-ACTIVE Press If the deviation is greater than ± 12%: Calibration is out of range Deviation Error: Page 44 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 51: Factoring

    Press ENTER to accept value 45.25 Press P359 Factoring: Enter 1 to start factoring Note: If multispan function is used, the test rate value is stored for the current multispan only. 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 45...
  • Page 52: Linearization

    After programming the compensation into the SF 500, run a material test to verify the effect of linearization. • If additional compensation is required, it must be based on new material tests performed with the linearization turned off (P390 = 0). Page 46 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 53 SF 500 flowmeter response linearized SF 500 response -5.1 internal response 100% - 150% of span % compensation -11.1 span (100%) -10.7 rate t/h 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 47...
  • Page 54 2, compensation actual weight per material test totalized weight by SF 500 flowmeter response linearized SF 500 response internal response 100% - 150% of span % compensation -10.7 span (100%) rate t/h Page 48 Milltronics SF 500 – INSTRUCTION MANUAL 7ML19985CN01...
  • Page 55: Operation

    116. The optional mA I/O board provides two additional mA outputs, programmable as outputs 2 and 3, using the same parameters as the standard output (1). If programmed for PID 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 49...
  • Page 56: Input

    Example: P011 = 360 t/h P100 = 1-rate P101 = 100% (360 t/h) P102 = 20% (72 t/h) P117 = 2% (7.2 t/h) Alarm is ON with relay de-energized. Page 50 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 57: Totalization

    10 for each 10 metric tonnes registered External totalizer 1 Given: P005 = 1 (t/h) P638 = 5 Then: contact closure occurs once for every 10 metric tonnes registered 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 51...
  • Page 58 RUN mode resets internal totalizer 1 Placing the internal totalizers on to the display scroll of the RUN mode is controlled by the totalizer display parameter (P647). This displays either one or both totalizers. Page 52 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 59: Pid Control

    – external process variable with or without rate control terminals terminal PID loop mA output mA input (mA I/O) (mA I/O) 1 & 2 5 & 6 3 & 4 7 & 8 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 53...
  • Page 60: Setpoint Controller - Rate Control

    *Set to 1 for Remote Setpoint operation Default Value = Comments: Connect signal to controlled device to mA O/P 2 For Remote Setpoint (optional). Connect remote 4-20 mA setpoint to I/P mA 1 Page 54 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 61: Setpoint Controller - Rate And Additive Control

    Connect additive rate controlled device to mA O/P 3 Connect additive process variable to mA I/P Hardwire mA O/P 1 to mA O/P 2 Ratio of Additive to Primary product may be adjusted by changing P418-02 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 55...
  • Page 62: Setpoint Controller - Master/Slave Control

    (rate) A L T R E S E T D I S P T O T A L C L E A R E N T E R optional remote setpoint Page 56 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 63: Sf 500 - Master

    Remote Ratio (optional) P418- ---- Setpoint=% of input Default Value = Comments: Connect primary rate controlled device to mA 2 O/P Ratio of Additive to Primary product may be adjusted by changing P418-01 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 57...
  • Page 64: Setup And Tuning

    P and I terms. Unfortunately, larger terms can make the system unstable. A derivative term is needed to influence the control output as the process variable approaches the set point. Page 58 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 65: Derivative Control (Pre-Act Or Rate), D

    P , I, and D terms alone. This is done on a one-time basis. • allowable input range: 0.000 to 1.000 • typical operating range: 0.250 to 0.550 • default value: 0.300 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 59...
  • Page 66: Pid Setup And Tuning

    P term value if there is too much oscillation and error. Likewise, increase the value if the error is not consistent and oscillating around the setpoint. Refer to fig 1, 2, and 3 below. Page 60 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 67 Restart the pre-feeder (test weights or chains still applied) and feed rate setpoint entered. Again observe the oscillation of the control output. Compare results to the figures 4,5 and 6 below. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 61...
  • Page 68 The D term becomes very useful in applications where the material control point is far away from the measuring point, e.g. a long screw feeder more than a few seconds process time from the flowmeter. Page 62 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 69: Programming

    5 and 6 on the mA I/O board. • mA input 2 is an external signal normally reserved for controller 2. The signal is input at terminals 7 and 8 on the mA I/O board. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 63...
  • Page 70 Input 2: the setpoint is the mA value on input 2, terminals 7 and 8 on the mA I/O board. P415-01 Local Setpoint Value Enter the setpoint value in engineering Enter Setpoint units. Not applicable if P414 = 1 or 2 Page 64 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 71 Select 1- 0 to 20, 2-4 to 20 Assign either: P255-01 mA Input Function 1. PID setpoint, or 2. process variable as the Select 0, 1-PID SP, 2-PID PV function of the mA input 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 65...
  • Page 72: Batching

    ♦ alarm function. RU N ZERO SPAN Typical auxiliary input assignment. RESE T CLEA R ENT ER ♦ DI SP TOT AL Inputs 1- 5 are available for batch reset. Page 66 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 73: Programming

    Set to OFF (0) or AUTO (1) or manual (2) Relays Select relay (1 – 5) Access P100, Relay Function Select function 5, Pre-Warn Select relay (1-5, other than the pre-warn relay) Access P100 Relay Function Select function 6, Setpoint 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 67...
  • Page 74: Operation

    Or, in manual mode, enter a set value to cause the batch setpoint to pre-act at a designed accumulation. Page 68 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 75: Communications

    The SF 500 supports two protocols: Dolphin and Modbus. Dolphin is a proprietary Siemens Milltronics protocol designed to be used with Dolphin Plus. Modbus is an industry standard protocol used by popular SCADA and HMI systems. 7ML19985CN01...
  • Page 76: Sf 500 And Smartlinx

    ® SF 500 and SmartLinx In addition to three onboard communication ports, the SF 500 is compatible with Siemens Milltronics SmartLinx ® communication modules which provide an interface to popular industrial communication systems. This section only describes the onboard communications. For more information on SmartLinx ®...
  • Page 77: Configuring Communication Ports

    The Siemens Milltronics protocol is compatible with the Dolphin Plus configuration program. See the Siemens Milltronics web site for information on this PC product (http://www.siemens-milltronics.com/). The Modbus protocol is an open standard developed by AEG Schneider Automation Inc.
  • Page 78: P771 Protocol Address

    The unique identifier of the SF 500 on the network for the selected port, ports 1 to 3 (P771- 01 to -03). For devices connected with the Siemens Milltronics protocol this parameter is ignored. For devices connected with a serial Modbus protocol this parameter is a number from 1- 247.
  • Page 79: P774 Data Bits

    P772 value. For troubleshooting purposes the baud rate on the modem can be hard-coded to the rate set on the SF 500. See your modem documentation for information on fixing the baud rate. Values no modem connected modem connected 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 73...
  • Page 80: P779 Modem Idle Time

    Applicable only to ports programmed for printer communication (parameter 770). Sets the interval between transmissions to be applied to the selected port, ports 1 to 3 (P780-01 to –03). Enter the period in minutes. ( = 0) Page 74 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 81: P781 Data Message

    Therefore, if you connect a SmartLinx card to the SF 500, set P799 = 1 and not write anything to the ® SmarLinx card, your setpoints will be 0. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 75...
  • Page 82: Dolphin Protocol

    The protocol is available on all communications ports on all units. This protocol is not available for third party use. The primary use of this protocol is to connect the SF 500 to Siemens Milltronics’ Dolphin Plus configuration software. Dolphin Plus Screen Shot...
  • Page 83: Modbus Rtu/Ascii Protocol

    Modbus protocol, contact your local Schneider representative. Also you may try their website at http://www.modicon.com. Note: Siemens Milltronics does not own the Modbus RTU protocol. All information regarding that protocol is subject to change without notice. How Modbus Works As mentioned above, Modbus is a master-slave type protocol.
  • Page 84: Modbus Format

    Parameter Values Parameter Values Refer to , page 87. Read Identifies the read / write capability for the register being addressed. Reference Provides reference documentation for the register being addressed. Page 78 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 85 Relay Outputs 41,080 bit mapped see page 86 mA Inputs 41,090 0000 - 20,000 mA Outputs 41,110 0000 - 20,000 Diagnostic Diagnostic State 41,200 number code see page 95 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 79...
  • Page 86: Modbus Register Map (Cont' D )

    For more information on this data format see page 87 Device Identifier (R40,064) This value identifies the Siemens Milltronics device type and is “2” for the SF 500. Handshaking Area (Parameter Access) An advanced handshaking area is built into the SF 500. Use it to read and write 32 bit parameters.
  • Page 87 40,090, 40,091, and 40,092. Write the value to registers 40,096 and 40,097 Write the desired format word to register 40.093 to enable the SF 500 to interpret the value correctly. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 81...
  • Page 88 For example, if the decimal offset (value of bits 9 to 11) is ‘2’ and the shift (value of bit 12 is ‘0’), then the decimal point is shifted two places to the right. Page 82 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 89 Bits Values R41,000 1999 R41,001 R41,002 R41,003 R41,004 R41,005 R41,006 Note: The time zone register is used only as a reference and does not affect the operation of the SF 500. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 83...
  • Page 90 Auto PID 2 Freeze PID 2 Setpoint Source Local Remote Zero In progress Span In progress Write Privileges System Configured Not Configured Mode Calibration Mode RUN Mode Totalizing Not Totalizing Totalizing Page 84 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 91 Bits 0 and 1 are used to indicate the number of decimal places being read in Total 1, Words 7 and 8. Bit 15 is used to indicate if the decimal place is too large to read the total value correctly. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 85...
  • Page 92 For 0 to 20 mA I/O, the register value ranges from 0 to 20,000. For 4 to 20 mA I/O, the register value ranges from 4,000 to 20,000. If the 4 or 20 mA values have been trimmed, Page 86 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 93 The whole is read as a 32-bit integer. To accommodate some Modbus drivers, the most significant byte (MSB) and least significant byte (LSB) can be reversed. See Format Word for SF 500 on page 80 for details. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 87...
  • Page 94: Modems

    Text Messages If a Siemens Milltronics device parameter returns a text message, that message is converted to a number and provided in the register. The numbers are shown in the table below: Number Text Message as Displayed on LCD 22222...
  • Page 95 ATDT • Initialization command: ATE0Q0V1X05=0512=100 • Reset command: ATZ • Hang-up command: ATHO • Command response delay: 5 seconds • Answer Delay: 30 seconds • Inter-character delay: 55 ms 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 89...
  • Page 96: Error Handling

    Echo back the command with the correct response. This is the normal response. (see the Modbus specifications for more details). Return an Exception Code. This reflects an error in the message. Page 90 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 97 If the user attempts to write one or more registers that are out of range, an exception response code 2 will be generated. • If using an unsupported function code, undocumented results may occur. The user is encouraged not to do this. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 91...
  • Page 98: Parameters

    Selects the type of test reference used to represent a material rate: weight or electronic. weight: the weight that is supplied specific to the flowmeter electronic: calibration based on automatic calculation of the mV span from the load cells or LVDT Page 92 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 99 P003 Number of Load Cells Siemens Milltronics flowmeters are available in models of one or two load cell design. Select the number of load cells corresponding to the flowmeter connected. If using the optional remote LVDT conditioner card, for LVDT based scales, select the “1”...
  • Page 100 % change into P598, or as the weight of the material test. Entry: 1 = % change 2 = material test Recalibration Refer to on page 30. Page 94 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 101: Relay/Alarm Function (P100 - P117)

    7 = on-line calibration** * valid only if PID system (P400) is enabled. τ valid only if batch function (P560) is enabled. ** valid only if on-line calibration (P355) is enabled. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 95...
  • Page 102 Sets the alarm mode for the relay selected, relays 1 to 5 (P100 - 01 to - 05. Entry: 1 = high and low 2 = high only 3 = low only Note: Not applicable if P100 = 2, 3, 4, 5, 6 or 7. Page 96 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 103: Normal Operation

    This function allows the user to simulate an alarm condition: ON or OFF, which will override normal operation until P119 setting is returned to normal. Values P119 Condition Display (alarm field) normal normal alarm on ALM # alarm off blank 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 97...
  • Page 104: Ma I/O Parameters (P200 - P220)

    The instantaneous mA values are averaged for the set period, and then the average value is output during the next period while a new average is being calculated. Entry: 0 = OFF 1 – 999 = averaging period Page 98 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 105 Sets the mA range for the input selected, inputs 1 to 2 (P250 - 01 to - 02). Entry: 1 = 0 - 20 mA 2 = 4 - 20 mA 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 99...
  • Page 106 (P365)*. Page 100 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 107 0 = OFF 1 = alternate display 2 = reset totalizer 1 3 = zero 4 = span 5 = print 6 = multispan selection * 7 = reserved 8 = reset batch 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 101...
  • Page 108: Calibration Parameters (P295 - 360)

    The cumulative days that the application device has been in service. The time is recorded once daily in a non-resetable counter. Periods of less than 24 hours. are not recorded, nor accumulated. ( = 0) Page 102 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 109: On-Line Calibration Options (P355 To P358)

    P357. 1 MAX LIMIT, range 0.0 to 100.0 ( = 0%) P357.2 HIGH LIMIT, range 0.0 to 100.0 ( = 0%) P357.3 LOW LIMIT, range 0.0 to 100.0 ( = 0%) 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 103...
  • Page 110 7 = multispan 7 (MS7), for product or condition G 8 = multispan 8 (MS8), for product or condition H Multispan P270 Auxiliary Input Function Refer to on page 38 and (6) on page 100. Page 104 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 111 The initial span is the reference to which all subsequent span calibrations are compared in determining whether they have deviated beyond an accumulated ±12.5% of the initial span. ( = 1) Initial Span Note: Refer to on page 37 for execution. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 105...
  • Page 112: Linearization Parameters (P390 - P392)

    Change should be made in the manual mode and are effected upon return to the auto mode. • The PID function does not control during any of the calibration functions (e.g. zero, span, factor, material test). Page 106 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 113 100%. The proportional band is the range of deviation from the setpoint that corresponds to the full range or the control output. Enter the proportional term 0.000 to 2.000. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 107...
  • Page 114 * for PID-01, the setpoint source is mA input 1; for PID-02, the setpoint source is mA input ** Option 3 is only available if P402 has been set for an external process value source. The setpoint will be the current rate value displayed as a percentage. Page 108 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 115: Batch Control (P560 - P568)

    Sets the batch total. When the amount of material delivered reaches this point, the batch relay contact opens (P100) to signal the end of the batch. ( = 0.000) Enter the setpoint of the units of weight selected (P005). 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 109...
  • Page 116 Enter a value to make the setpoint relay change status before reaching the setpoint. This allows the feeding system to empty with each batch. The value of the manual pre-Act entry is generally reflective of the material that is left in the feeding system. Page 110 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 117: Totalization (P619 - P648)

    1 = 0.001 (one thousandth) 2 = 0.01 (one hundredth) 3 = 0.1 (one tenth) 4 = 1 (unit) 5 = 10 (x ten) 6 = 100 (x hundred) 7 = 1000 (x thousand) 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 111...
  • Page 118 1 = 0.001 (one thousandth) 2 = 0.01 (one hundredth) 3 = 0.1 (one tenth) 4 = 1 (unit) 5 = 10 (x ten) 6 = 100 (x hundred) 7 = 1000 (x thousand) Page 112 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 119 This parameter becomes available when Ecal is selected in P002. Enter the mV span corresponding to 0 to 100% full scale rate. The display changes to P017 to show the design rate value as the test rate. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 113...
  • Page 120: Communication (P750 - P799)

    PASS requirements are met. Communication then resumes. P791 Bus Error Indicates if an error condition is occurring on the bus. Values Description no error refer to the SmartLinx module documentation for explanation of the Error Code code. Page 114 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 121: Test And Diagnostic (P900 - P951)

    Displays the EPROM (Flash ROM) software revision level. P901 Memory Test Tests the memory. Test is initiated by scrolling to the parameter or repeated by 'pressing enter' Display: PASS = normal FAIL = consult Siemens Milltronics. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 115...
  • Page 122 Displays a log of the last 25 error or alarm events (P948 – 01 to – 25) that have occurred. Event 01 is the current error. Display: 0 = no error Troubleshooting # = error code; refer to on page 118 Page 116 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 123 08), that have been done since the last master reset. ( = 0) P999 Master Reset Resets parameters and totalizers to their factory setting. ( = 0) Enter 9 to execute the reset. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 117...
  • Page 124: Troubleshooting

    Contact Siemens Milltronics. Error that occurred Error message flashing on some time ago, may Verify if error is still active. Cycle SF 500 from display remain on display, PROGRAM to RUN modes. flashing Page 118 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 125: General-Communications

    Finally, if you should check that the port you are using on the computer. Sometimes trying a different Modbus driver will solve the problem. An easy stand-alone driver called ModScan32, is available from Win-Tech at www.win-tech.com. This driver is very useful to test communications. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 119...
  • Page 126: Error Codes

    Load Cell AD’s are not func- Consult Siemens Milltronics. tioning Err: 227 No process data available. Consult Siemens Milltronics. Batch pre-act adjustment Pre-act adjustment is ignored. Tune process to limit batch > 10% error. Integrator not configured...
  • Page 127: Glossary

    Zero Limit (P370). Linearization Compensates for non-linear output of the flowmeter caused by varying load rates. Load Cell Strain Gauge type transducer that produces an electrical output proportional to force (load) applied. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 121...
  • Page 128 Span Register This is the number of span calibrations that have been performed since the last master reset. Test Weight A calibrated weight which will represent a certain load on the scale. Page 122 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 129 Totalizer An incremental counter that records the total of material that has been monitored. Zero Register Shows the number of zero calibrations that have been performed since the last master reset. 7ML19985CN01 Milltronics SF 500 - INSTRUCTION MANUAL Page 123...
  • Page 130 98 value 95 output test 116 data output trim 99 advanced access 80 resolution 5 bits 73 setpoint 54 types 87 source 100 date and time 83 maximum separation 70 Page 124 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 131 P119 relay override 97 P418 remote setpoint ratio 106 P200 mA output Range 98 P560 batch mode control 19 P200 mA output range 49 P201 mA output function 49 P564 batch setpoint 66 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 125...
  • Page 132 P949 diagnostic error testing 117 setpoint 102 P951 span register 117 span 8 P999 master reset 8 adjust 30 read and write 80 calibration 30 reading 81 correction 38 values 87 direct 37 writing 81 Page 126 Milltronics SF 500 - INSTRUCTION MANUAL 7ML19985CN01...
  • Page 133 87 web site 71 wiring 9-pin to RJ-11 14 guidelines 70 wiring guidelines 70 zero 4 auto 35 calibration 29 direct 35 initial 34 recalibration 29 routine 45 7ML19985CN01 Milltronics SF 500 – INSTRUCTION MANUAL Page 127...
  • Page 134 Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. 2003 1954Technology Drive, P .O. Box 4225 Subject to change without prior notice Peterborough, ON, Canada K9J 7B1 Rev. 1.1 Tel: (705) 745-2431 Fax: (705) 741-0466 *7ml19985CN01* Email: techpubs@siemens-milltronics.com...

Table of Contents