Mitsubishi Electric MELSEC iQ-R Series User Manual page 48

Controller module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CW Configurator is not connected to the actual system configuration
Create the module configuration manually to set parameters.
Parameter settings from the navigation window
Set the following parameters from the navigation window.
■System parameter
To change the number of slots of a base unit or the number of occupied points for a module as well as to configure the multiple
CPU setting or synchronization setting, the system parameter is set from the navigation window.
[Navigation window]  [Parameter]  [System Parameter]
■Module parameter of CPU module
To use a built-in Ethernet function for CPU module, setting the module parameter for CPU module is required.
[Navigation window]  [Parameter]  [(CPU module)]  [Module Parameter]
■Memory card parameter
To use any of the functions with SD memory card, setting the memory card parameter is required.
[Navigation window]  [Parameter]  [(CPU module)]  [Memory Card Parameter]
■Multiple module parameters and module extended parameter
Some intelligent function modules may require parameter settings for multiple modules or module extended parameter
setting.
[Navigation window]  [Parameter]  [Module Information]  [(each of Intelligent function module)]  [Module
Extended Parameter] or [Module Parameter]
Settings with the module configuration diagram and settings by system parameter are used properly as
follows depending on their usage.
• Module configuration diagram: Module-specific information such as the number of occupied points is used
without changing.
• System parameter: The number of slots of a base unit or the number of occupied points for a module is
changed.
6 PROCEDURE BEFORE OPERATION
46
6.8 Setting Parameters
1.
Select a base unit to be used from the Element
Selection window, and drag and drop it onto the Module
Configuration Diagram.
2.
Drag respective modules to be used and drop it on the
base unit placed in the diagram.
3.
Select [Edit]  [Parameter]  [Fix] from the menu.
4.
Double click the module to display the parameter editor
for the respective modules.
5.
After setting the parameters, click the [Apply] button.

Advertisement

Table of Contents
loading

This manual is also suitable for:

R12ccpu-v

Table of Contents