30

ACS800-37 and sine filters

Enclosure and cooling

ACS800-37 sine filter drives have the filter fitted in a separate cubicle, protected to
IP21, IP22, IP42, IP54 or IP54R.
The filters have a dedicated cooling fan that rotates whenever the drive is powered.
As standard, fan and filter overtemperature switches are wired to stop the drive by
breaking the DIIL (start interlock) circuit on the RMIO control board.

Motor cabling

The motor cabling is done from the sine filter cubicle of the drive cabinet. The
connection points are visible in the drawings in the chapter Illustrations.
The cable length between the filter and the motor is not restricted. All other cabling
requirements for the ACS800 also apply to the filters. See the Hardware Manual of
the drive.

Rating table for ACS800-37 sine filter drives

Drive type
Frame
Filter type
ACS800-17-
Three-phase supply voltage 380 V, 400 V or 415 V
0140-3
R7i
NSIN0315-6
0170-3
R7i
NSIN0315-6
0210-3
R8i
NSIN0485-6
0260-3
R8i
NSIN0485-6
0320-3
R8i
NSIN0900-6
0390-3
R8i
NSIN0900-6
0510-3
R8i
NSIN0900-6
0640-3
2x R8i
NSIN1380-6
0770-3
2x R8i
NSIN1380-6
0960-3
2x R8i
2xNSIN0900-6
1070-3
3x R8i
2xNSIN1380-6
1370-3
3x R8i
2xNSIN1380-6
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V, or 690 V
0170-7
R7i
NSIN0210-6
0210-7
R7i
NSIN0210-6
0260-7
R8i
NSIN0315-6
0320-7
R8i
NSIN0315-6
0400-7
R8i
NSIN0485-6
0440-7
R8i
NSIN0485-6
0540-7
R8i
NSIN0485-6
0790-7
2x R8i
NSIN0900-6
0870-7
2x R8i
NSIN0900-6
1160-7
2x R8i
NSIN1380-6
1330-7
3x R8i
NSIN1380-6
1510-7
3x R8i
2xNSIN0900-6
2320-7
4x R8i
2xNSIN1380-6
2780-7
5x R8i
3xNSIN1380-6
3170-7
6x R8i
3xNSIN1380-6
Note:
*Applies to drives protected to IP21 with bottom cable entry/exit.
** 776 mm If 1st. enviroment and common motor terminal not used
Sine filters with ACS800 drives
Heat dis-
Air
I
P
cont.max
cont.max
sipation
flow
3
A
kW
kW
m
202
110
7,0
2000
250
132
8,1
2000
292
160
9,3
3860
370
200
12
3860
469
250
15
5160
565
315
19
5160
730
400
26
5160
919
500
29
8400
1111
630
37
8400
1379
800
50
10400
1535
900
53
14240
2056
1200
73
14240
139
132
8,2
2000
162
160
9,5
2000
201
200
13
3860
279
250
17
3860
335
315
20
3860
382
355
20
3860
447
450
24
3860
659
630
39
8400
729
710
39
8400
953
900
46
8400
1112
1120
59
12240
1256
1250
68
14240
1866
1800
90
16800
2321
2300
117
23920
2665
2700
133
25200
*Height
Noise
*Height
IP21/22/
level
IP54
42
/h
dBA
mm
mm
80
2130
2315
80
2130
2315
81
2130
2315
81
2130
2315
81
2130
2315
81
2130
2315
81
2130
2315
82
2130
2315
82
2130
2315
82
2130
2315
83
2130
2315
83
2130
2315
79
2130
2315
79
2130
2315
80
2130
2315
80
2130
2315
81
2130
2315
81
2130
2315
81
2130
2315
81
2130
2315
81
2130
2315
82
2130
2315
82
2130
2315
82
2130
2315
83
2130
2315
83
2130
2315
83
2130
2315
*Height
*Depth
*Width *Depth
IP54R
top exit
mm
mm
mm
mm
2051
1030
646
646
2051
1030
646
646
2051
1630
646
646 **
2051
1630
646
646 **
2051
2230
646
646 **
2051
2230
646
646 **
2051
2230
646
646 **
2051
3430
646
776
2051
3430
646
776
2051
4730
646
776
2051
5530
646
776
2051
5530
646
776
2051
1030
646
646
2051
1030
646
646
2051
1630
646
646 **
2051
1630
646
646 **
2051
1630
646
646 **
2051
1630
646
646 **
2051
1630
646
646 **
2051
3430
646
776
2051
3430
646
776
2051
3430
646
776
2051
4230
646
776
2051
5530
646
776
2051
6130
646
776
2051
8430
646
776
2051
8630
646
776
Weight
kg
650
650
1200
1200
1650
1650
1650
2750
2750
3400
4550
4550
650
650
1200
1200
1200
1200
1200
1900
1900
2750
3800
4450
5100
7050
7200