LG V-NET PQCPC22N0 Installation & User Manual page 121

Acs acp
Hide thumbs Also See for V-NET PQCPC22N0:
Table of Contents

Advertisement

It is installed by interfacing 16 room central controller and the ACP, but some indoor units are not rec-
ognized, or not properly performing the central control commands
- It is the case of incorrect setting of the simple central controller (16 room central controller) DIP
switch.
Set all simple central controllers to Slave mode, and reset the power.
- If the indoor unit to control with simple central controller is in another physical line as in the fol-
lowing figure, the simple central controller cannot recognize the corresponding indoor unit.
Therefore, the connections need to be modified to have the simple central controller to be in
the same RS-485 communication line with the indoor unit to control.
NOTES
121