<Return>
Measured
Prod
PV
SV
Dynm
Variables
TV
(HART
QV
only)
<Return>
LRV
URV
Damping
NAMUR
Output
4-20 mA
Loop Curr
Output
Mode
(HART
only)
Latching
Mode
BDH/BDL
Loop
<Return>
Set LRV
Set LRV
(HART
only)
Set URV
Revision 8
Single Liquid
2 Liq Flooded
2 Liq NonFlood
Saturated Steam
SingleLiqLowDC
Product Level
% Prod Level
Dist To Prod
Prod Lvl Rate
Product Volume
Vapor Thick
% Vapor Thick
Vapor Volume
Intf Level
% Intf Level
Dist To Intf
Intf Lvl Rate
Upr Prod Thick
Lower Prod Vol
Upper Prod Vol
#####.###
##.#
Disabled
Enabled
Latching
Non-Latching
Hi Saturation
Low Saturation
Last Good Val
Default
ATTENTION: Executing this service will set the Lower
Range Value (LRV) equal to the input GWR Level.
ATTENTION: Executing this service will set the Upper
Range Value (URV) equal to the input Guided Wave
Radar Level.
SLG 700 SmartLine Level Transmitter User's Manual
Read-Only
PV = Primary Variable
SV = Secondary Variable
TV = Tertiary Variable
QV = Quaternary Variable
Configure the dynamic variables
for monitoring on a host such as
DTM or handheld device.
Disabled: Sets loop output and
burnout levels to Honeywell
levels.
Enabled: Sets loop output and
burnout levels to the NAMUR
levels
Disabled: Required for multi-drop
HART communications.
Latching Mode: This parameter
allows selection of transmitter
critical error behavior.
Latching: The transmitter will
remain in a critical error state until
a user performs a hardware /
software reset.
Non-Latching: The transmitter
exits critical error state
automatically when causes of the
critical error have been resolved.
Loop output when level is in a
high or low blocking distance
zone.
Press to
enter
menu
selection,
and to
select from
list, to
enter
Press to
enter
menu
selection,
and to
select from
list, to
enter and
shift to
next digit
Press to
enter menu
selection,
to execute
Page 107