4. Settings for FP7

For connecting GT series and FP7, the communication parameters of FP7 should be set with FPWIN
GR7. Execute "Option" - "FP7 Configuration" menu in FPWIN GR7, and set the parameters in the "Built-
in SCU" page.
Settings
COM0
COM1 settings
COM2 settings
Communication
mode
Unit number
Baud rate
Data length
Parity
Stop bit
RS/CS
Send waiting time
Header STX
Modem initialization
Set when connecting the COM0 port of FP7 and GT.
Set when connecting the 1CH of 1-ch or 2-ch type communication cassette
and GT.
Set when connecting the 2CH of 2-ch type communication cassette and GT.
Select "MEWTOCOL-7".
Set a desired unit number. When using the PLC multiple connection, the unit
number specified by GTWIN corresponds to this unit number.
Set the same "Baud Rate" as that specified in GTWIN "GT Configuration" -
"Communication Parameters" - "Baud Rate".
Set the same "Data Length" as that specified in GTWIN "GT Configuration" -
"Communication Parameters" - "Data Length".
Set the same "Parity" as that specified in GTWIN "GT Configuration" -
"Communication Parameters" - "Parity".
Select "1".
Select "Disable".
For connecting with RS232C or RS422, specify "0".
For connecting with RS485, adjust the setting with the GT and FP7 actually
connected.
Select "Disable".
Select "Not initialize".