Installation instructions:
BEKOMAT® 33U / 33U CO
Only the displayed installation position of the
BEKOMAT (3) is permissible. Never install in a hor-
izontal or any other tilted position.
Feed pipe (1) and ball valve (2) at least G½.
No filter or screen in the inlet line.
Slope in the inlet line >1%.
Use ball valves (2) only.
Operating pressure: min. 0,8/1,2 bar (12/17 psig),
max. 16 bar (230 psig). See type plate.
Short pressure hose (4) fixed on a pressure-re-
sistant pipe.
The required minimum pressure increases by
0,1 bar (1,4 psi) per metre gradient in the dis-
charge pipe (5).
Discharge pipe (5) rising by max. 5 m (16,4ft).
Install manifold (6) ¾" with a slope of 1%.
Introduce the discharge pipe (5) from the top into
the manifold (6).
Prior to the start-up, always carry out a leak test
and verify the correct engagement of the control
unit.