Siemens SINAMICS DCP Manual

Siemens SINAMICS DCP Manual

Dc/dc power converter
Hide thumbs Also See for SINAMICS DCP:

Advertisement

Quick Links

s
SINAMICS drives
SINAMICS DCP
DC/DC Power Converter
List Manual
Edition
05/2016
Siemens Parts

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SINAMICS DCP

  • Page 1 SINAMICS drives SINAMICS DCP DC/DC Power Converter List Manual Edition 05/2016 Siemens Parts...
  • Page 3 Foreword Fundamental safety instructions SINAMICS drives Parameters SINAMICS DCP Function diagrams DC/DC Power Converter Faults and alarms List Manual Appendix Index Valid for Firmware version SINAMICS DCP Siemens Parts 05/2016...
  • Page 4 Note the following: WARNING Siemens products are only permitted to be used for the applications listed in the catalog and in the associated technical documentation. If third-party products and components are used, then they must be recommended or approved by Siemens. These products can only function correctly and safely if they are transported, stored, set up, mounted, installed, commissioned, operated and maintained correctly.
  • Page 5 The contents of this documentation are not part of an earlier or existing agreement, a promise or a legal agreement, nor do they change this. All obligations on the part of Siemens can be found in the respective sales contract, which also contains the complete and sole warranty provisions.
  • Page 6 Preface SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 7 Index ................Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 8 Table of contents SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 9 Fundamental safety instructions Content General safety instructions Industrial security Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 10 Machines can malfunction as a result of incorrect or changed parameter assignment, which in turn can lead to injuries or death. • Protect the parameterization (parameter assignments) against unauthorized access. • Respond to possible malfunctions by applying suitable measures (e.g. EMERGENCY-STOP or EMERGENCY-OFF). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 11 Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, devices, and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates.
  • Page 12 1 Fundamental safety instructions 1.2 Industrial security SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 13 Parameters Content Overview of parameters List of parameters Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 14 - - - - - - - - - - - - End of example - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - The individual pieces of information are described in detail below. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 15 The parameter list can contain parameters that are not visible in the expert lists of the particular commissioning software (e.g. parameters for trace functions). The value for the factory setting can deviate from the value shown in the list as a result of specific customer requirements. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 16 All objects This parameter is used by all drive objects. CU_DCP Advanced Control Unit SINAMICS DCM (CUD) CU_DCP (PROFINET) Advanced Control Unit SINAMICS DCP (CUD) with "PROFINET" function module (p0108.31). DCP_CTRL Closed-loop control for SINAMICS DCP. DCP_CTRL (PROFINET) Closed-loop control for SINAMICS DCP with "PROFINET" function module (r0108.31).
  • Page 17 The pulses are not enabled and the state "C1(x)" or "C2(x)" is not active. Note Parameter p0009 is CU-specific (belongs to the Control Unit). Parameter p0010 is drive-specific (belongs to each drive object). The operating state of individual drive objects is displayed in r0002. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 18 • FloatingPoint32 Float 32-bit floating point number Depending on the data type of the BICO input parameter (signal sink) and BICO output parameter (signal source), the following combinations are possible when creating BICO interconnections: SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 19 In the case of a binector/connector input, the signal source of the default BICO interconnection is specified. A non-indexed connector output is assigned the index [0]. Description Explanation of the function of a parameter. Values Lists the possible values of a parameter. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 20 The signal is shown on this function diagram. Dependency Conditions that must be fulfilled in conjunction with this parameter. Also includes special effects that can occur between this parameter and others. See also: List of other parameters to be additionally considered. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 21 "Legal information" (Page 4). Notice The description of this safety notice can be found at the beginning of this manual, see "Legal information" (Page 4). Note Information that the user may find useful. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 22 2 Parameters 2.2 List of parameters List of parameters Product: SINAMICS DCP, Version: 4703500, Language: eng Objects: CU_DCP, DCP_CTRL, TM150, TM15DI_DO, TM31 Product: SINAMICS DCDC_V, Version: 1200700, Language: eng Objects: DCP_CTRL r0002 Control Unit operating display / CU op_display CU_DCP...
  • Page 23 Can be changed: C1, U, T Access level: 1 Data type: Integer16 Func. diagram: - Factory setting Description: Sets the access level for reading and writing parameters via the Basic Operator Panel (BOP). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 24 [1] 0 Description: Sets the parameter number and parameter index for display for p0006 = 4 for the Basic Operator Panel (BOP). Index: [0] = Parameter number [1] = Parameter index Dependency: Refer to: p0006 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 25 The index that belongs to the parameter set in index 0 should be set in index 1. The permissible changes in index 1 always depend on the parameter number set in index 0. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 26 Sets the device and basic drive commissioning. By appropriately setting this parameter, those parameters are filtered that can be written into in the various commissioning steps. Value: Ready Device configuration Defining the drive type/function module Drive base configuration SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 27 Value: Ready Quick commissioning Encoder commissioning Data sets Only Siemens int Reserved Note: The drive can only be powered up outside the drive commissioning (drive enable). To realize this, this parameter must be set to 0. By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically reset to 0.
  • Page 28 Setting this parameter filters out the parameters that can be written into in the various commissioning steps. For the BOP, this setting also causes the read access operations to be filtered. Value: Ready Only Siemens int Parameter reset Dependency: Refer to: p0970...
  • Page 29 The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning software. Macros available as standard are described in the technical documentation of the particular product. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 30 No coast-down / coast-down (OFF2) No coast down Coast down (OFF2) No Quick Stop / Quick Stop (OFF3) No Quick Stop Quick Stop (OFF3) Acknowledge fault (0 -> 1) Motorized potentiometer raise Motorized potentiometer lower SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 31 = 0 b = 0 c = 0 d = no. of motor encoders e = no. of additional encoders f = number of Terminal Modules g = number of Terminal Boards Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 32 Displays the number of drive objects that have already been set up. Index 1: Displays the number of drive objects that have already been set up and, in addition, the drive objects that still have to be set up. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 33 If components are inserted for the first time and the appropriate drive object is activated, then the drive system is automatically booted. To do this, the pulses of all of the drive objects must be suppressed. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 34 If components are inserted for the first time and the appropriate drive object is activated, then the drive system is automatically booted. To do this, the pulses of all of the drive objects must be suppressed. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 35 BASIC INFEED CONTROLMV ACTIVE INFEED CONTROLM2C SINAMICS G120 230 (SingleDO-Drive which combines Device+Vector) SINAMICSG120 240_2 (SingleDO-Drive which combines Device+Vector) SINAMICS_G120_CU250S_V (SingleDO Drive combines Device+Vector) SINAMICSG120 G120D(SingleDO-Drive which combines Device+Vector) SINAMICS_G120_CU250S_S (SingleDO Drive combines Device+Servo) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 36 SINAMICS G120 230 (SingleDO-Drive which combines Device+Vector) SINAMICSG120 240_2 (SingleDO-Drive which combines Device+Vector) SINAMICS_G120_CU250S_V (SingleDO Drive combines Device+Vector) SINAMICSG120 G120D(SingleDO-Drive which combines Device+Vector) SINAMICS_G120_CU250S_S (SingleDO Drive combines Device+Servo) SINAMICSG110M (SingleDO-Drive which combines Device+Vector) SINAMICS ET200 Link variant for Sinamics Microbasissystem SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 37 Bit 16 Bit 17 Bit 18 Bit 19 Bit 20 Bit 21 Bit 22 Bit 23 Bit 24 Bit 25 Bit 26 Bit 27 Bit 28 Bit 29 Bit 30 Bit 31 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 38 The clock cycles for the current controller / speed controller / - / setpoint channel / - / - / technology controller are defined as follows: p0112 = 3: 1000 / 2000 / - / 4000 / - / - / 4000 µs Value: Expert Standard SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 39 Only setting values that are an integer multiple of 125 µs are permissible. Index: [0] = Basic sampl time Note: This parameter only applies to set the sampling times of possible supplementary functions. The sampling times for inputs/outputs must be set in p4099. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 40 TM31 Data type: Unsigned32 Func. diagram: - Factory setting Description: Displays the firmware version of the Terminal Module. Dependency: Refer to: r0018, r0197, r0198 Note: Example: The value 1010100 should be interpreted as V01.01.01.00. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 41 Re bits 12 ... 11: These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes only on certain automation systems with integrated SINAMICS functionality. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 42 Name character 1 r0203[15]: Name character 16 For the commissioning software, the ASCII characters are displayed uncoded. Notice: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 43 If the data between the volatile and non-volatile device memories differ, then it may be necessary to save the data on the memory card in a non-volatile fashion prior to the transfer (e.g. p0971 = 1). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 44 (e.g. by means of "Copy RAM to ROM"). Once the data has been successfully transferred, this parameter is automatically reset to 0. If an error occurs, the parameter is set to a value > 1000. Possible fault causes: SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 45 2. In Index 1, enter the command data set that is to be copied into. 3. Start copying: Set index 2 from 0 to 1. p0809[2] is automatically set to 0 when copying is completed. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 46 Access level: 2 Data type: Unsigned16 Func. diagram: 8575 Factory setting Description: Displays the status word for the drive data set changeover. Bit field: Signal name 1 signal 0 signal Internal parameter calculation active SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 47 For drives with closed-loop torque control (p50084 = 2), the following applies: - BI: p0840 = 0 signal: immediate pulse suppression For drives with closed-loop speed/torque control, the following applies: - BI: p0840 = 0/1 signal: ON (pulses can be enabled) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 48 - No OFF3 (enable is possible) Caution: When "master control from PC" is activated, this binector input is ineffective. Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 49 If a control is available, then STW1.10 must be set to 1 (PZD1) so that the received data is updated. This applies regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 50 PROFIBUS address / PB address CU_DCP Can be changed: T Access level: 2 Data type: Unsigned16 Func. diagram: 1520, 2410 Factory setting Description: Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 51 Fault code / Fault code CU_DCP, DCP_CTRL Can be changed: - Access level: 2 Data type: Unsigned16 Func. diagram: 8060 Factory setting Description: Displays the numbers of faults that have occurred. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 52 Lists the fault codes stored in the drive unit. The indices can only be accessed with a valid fault code. Dependency: The parameter assigned to the fault code is entered in r0951 under the same index. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 53 Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139). The structure of the fault buffer and the assignment of the indices is shown in r0945. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 54 12 Mbit/s 31.25 kbit/s 45.45 kbit/s 255: Unknown r0964[0...6] Device identification / Device ident CU_DCP Can be changed: - Access level: 2 Data type: Unsigned16 Func. diagram: - Factory setting Description: Displays the device identification. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 55 2 Parameters 2.2 List of parameters Index: [0] = Company (Siemens = 42) [1] = Device type [2] = Firmware version [3] = Firmware date (year) [4] = Firmware date (day/month) [5] = Number of drive objects [6] = Firmware patch/hot fix...
  • Page 56 The Control Unit power supply may only be powered down after data has been saved (i.e. after data save has been started, wait until the parameter again has the value 0). Writing to parameters is inhibited while saving. The progress while saving is displayed in r3996. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 57 If cyclic communication is not active, then the reset is immediately executed. If the cyclic communication is active for both PROFIdrive interfaces, then the reset is executed after completing both cycle communications. After communications have been established, check the reset operation (refer below). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 58 Func. diagram: - Factory setting Description: Displays the identification of the drive object. Index: [0] = Company (Siemens = 42) [1] = Drive object type [2] = Firmware version [3] = Firmware date (year) [4] = Firmware date (day/month) [5] = PROFIdrive drive object type class...
  • Page 59 Start dnload of param. saved in non-volatile mem w/ p0977=10 Start dnload of param. saved in non-volatile mem w/ p0977=11 Start dnload of param. saved in non-volatile mem w/ p0977=12 Start download Siemens internal setting 20 100: Start resetting of all BICO interconnections...
  • Page 60 List of existing parameters 2 / List avail par 2 All objects Can be changed: - Access level: 4 Data type: Unsigned16 Func. diagram: - Factory setting Description: Displays the parameters that exist for this drive. Dependency: Refer to: r0980, r0989 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 61 Can be changed: - Access level: 3 Data type: Unsigned16 Func. diagram: - Factory setting Description: Displays those parameters with a value other than the factory setting for this drive. Dependency: Refer to: r0990, r0991 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 62 Sets the reference quantity for temperature. All temperatures specified as relative value are referred to this reference quantity. The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 63 Field bus interface address / Field bus address CU_DCP Can be changed: T Access level: 2 Data type: Unsigned16 Func. diagram: - Factory setting Description: Sets the address for the fieldbus interface USS. Dependency: Refer to: p2030 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 64 Factory setting Description: Sets the communication protocol for the field bus interface. Value: No protocol PROFIBUS Note: Changes only become effective after POWER ON. The parameter is not influenced by setting the factory setting. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 65 Do not change the setting p2037 = 0. Note: If the STW1 is not transferred according to the PROFIdrive with PZD1 (with bit 10 "master control by PLC"), then p2037 should be set to 2. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 66 Sets the delay time to initiate fault F01910 after a setpoint failure. The time until the fault is initiated can be used by the application. This means that is is possible to respond to the failure while the drive is still operational (e.g. emergency retraction). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 67 [13] = PZD 14 [14] = PZD 15 [15] = PZD 16 [16] = PZD 17 [17] = PZD 18 [18] = PZD 19 [19] = PZD 20 Note: IF1: Interface 1 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 68 [48] = PZD 49 [49] = PZD 50 [50] = PZD 51 [51] = PZD 52 [52] = PZD 53 [53] = PZD 54 [54] = PZD 55 [55] = PZD 56 [56] = PZD 57 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 69 [22] = PZD 23 [23] = PZD 24 [24] = PZD 25 Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed. Note: IF1: Interface 1 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 70 [47] = PZD 48 [48] = PZD 49 [49] = PZD 50 [50] = PZD 51 [51] = PZD 52 [52] = PZD 53 [53] = PZD 54 [54] = PZD 55 [55] = PZD 56 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 71 [20] = PZD 21 [21] = PZD 22 [22] = PZD 23 [23] = PZD 24 [24] = PZD 25 Bit field: Signal name 1 signal 0 signal Bit 0 Bit 1 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 72 [32] = PZD 33 [33] = PZD 34 [34] = PZD 35 [35] = PZD 36 [36] = PZD 37 [37] = PZD 38 [38] = PZD 39 [39] = PZD 40 [40] = PZD 41 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 73 [2] = PZD 3 [3] = PZD 4 [4] = PZD 5 Bit field: Signal name 1 signal 0 signal Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 74 [2] = PZD 3 + 4 [3] = PZD 4 + 5 [4] = PZD 5 + 6 [5] = PZD 6 + 7 [6] = PZD 7 + 8 [7] = PZD 8 + 9 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 75 A BICO interconnection for a single PZD can only take place either on r2050 or r2060. A maximum of 4 indices of the "trace" function can be used. Note: IF1: Interface 1 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 76 [51] = PZD 52 + 53 [52] = PZD 53 + 54 [53] = PZD 54 + 55 [54] = PZD 55 + 56 [55] = PZD 56 + 57 [56] = PZD 57 + 58 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 77 [40] = PZD 41 + 42 [41] = PZD 42 + 43 [42] = PZD 43 + 44 [43] = PZD 44 + 45 [44] = PZD 45 + 46 [45] = PZD 46 + 47 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 78 Displays the last parameter received from the PROFIBUS/PROFINET controller for clock synchronism. The parameters for clock synchronism are created when configuring the bus and are transferred at the start of cyclic operation from the controller to the device. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 79 [10] = PZD 11 [11] = PZD 12 [12] = PZD 13 [13] = PZD 14 [14] = PZD 15 [15] = PZD 16 [16] = PZD 17 [17] = PZD 18 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 80 [41] = PZD 42 [42] = PZD 43 [43] = PZD 44 [44] = PZD 45 [45] = PZD 46 [46] = PZD 47 [47] = PZD 48 [48] = PZD 49 [49] = PZD 50 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 81 [10] = PZD 11 [11] = PZD 12 [12] = PZD 13 [13] = PZD 14 [14] = PZD 15 [15] = PZD 16 [16] = PZD 17 [17] = PZD 18 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 82 [41] = PZD 42 [42] = PZD 43 [43] = PZD 44 [44] = PZD 45 [45] = PZD 46 [46] = PZD 47 [47] = PZD 48 [48] = PZD 49 [49] = PZD 50 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 83 [11] = PZD 12 [12] = PZD 13 [13] = PZD 14 [14] = PZD 15 [15] = PZD 16 [16] = PZD 17 [17] = PZD 18 [18] = PZD 19 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 84 [37] = PZD 38 [38] = PZD 39 [39] = PZD 40 [40] = PZD 41 [41] = PZD 42 [42] = PZD 43 [43] = PZD 44 [44] = PZD 45 [45] = PZD 46 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 85 Factory setting Description: Sets the send and receive telegram. Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded. Value: 390: SIEMENS telegram 390, PZD-2/2 391: SIEMENS telegram 391, PZD-3/7 392: SIEMENS telegram 392, PZD-3/15 393: SIEMENS telegram 393, PZD-4/21...
  • Page 86 2 Parameters 2.2 List of parameters 395: SIEMENS telegram 395, PZD-4/25 396: SIEMENS telegram 396, PZD-20/21 999: Free telegram configuration with BICO Note: For p0922 < 999 the following applies: p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are inhibited.
  • Page 87 [13] = Bit 13 [14] = Bit 14 [15] = Bit 15 Dependency: Refer to: p2088, r2089 Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 88 Can be changed: U, T Access level: 3 Data type: Unsigned16 Func. diagram: 2472 Factory setting 0000 0000 0000 0000 bin Description: Setting to invert the individual binector inputs of the binector connector converter. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 89 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: p2051, p2080, p2081, p2082, p2083 Note: r2089 together with p2080 to p2084 forms five binector-connector converters. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 90 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Note: IF1: Interface 1 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 91 BO: IF1 PROFIdrive PZD3 receive bit-serial / IF1 PZD3 recv bitw CU_DCP Can be changed: - Access level: 3 Data type: Unsigned16 Func. diagram: 2468 Factory setting Description: Binector output for bit-serial interconnection of PZD3 received from the PROFIdrive controller. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 92 Binector output for bit-serial interconnection of PZD4 (normally control word 2) received from the PROFIdrive controller. Bit field: Signal name 1 signal 0 signal Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 93 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: p2099 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 94 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: p2099 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 95 Not inverted Bit 11 Inverted Not inverted Bit 12 Inverted Not inverted Bit 13 Inverted Not inverted Bit 14 Inverted Not inverted Bit 15 Inverted Not inverted Dependency: Refer to: r2094, r2095, p2099 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 96 From the signal source set via the connector input, the corresponding lower 16 bits are converted. p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters: Connector input p2099[0] to binector output in r2094.0...15 Connector input p2099[1] to binector output in r2095.0...15 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 97 Sets the fault response for the selected fault. Value: NONE OFF1 OFF2 OFF3 Reserved Reserved Reserved Dependency: The fault is selected and the required response is set under the same index. Refer to: p2100 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 98 Sets the first signal source to acknowledge faults. Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed. Note: A fault acknowledgement is triggered with a 0/1 signal. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 99 Dependency: Refer to: F07860 Note: An external fault is triggered with a 1/0 signal. If this fault is output at the Control Unit, then it is transferred to all existing drive objects. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 100 BI: External fault 3 / External fault 3 DCP_CTRL Can be changed: U, T Access level: 3 Data type: Unsigned32 / Binary Func. diagram: 2546 Factory setting Description: Sets the signal source for external fault 3. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 101 - all of the alarms of the alarm buffer that have gone [0...7] are transferred into the alarm history [8...63]. - the alarm buffer [0...7] is deleted. Refer to: r2110, r2122, r2123, r2124, r2125 Note: The parameter is reset to 0 at POWER ON. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 102 CU_DCP, TM150, Can be changed: U, T Access level: 3 TM15DI_DO, TM31 Data type: Unsigned32 / Binary Func. diagram: - Factory setting Description: Sets the signal source for external alarm 2. Dependency: Refer to: A07851 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 103 Selects the fault or alarm selection and sets the required type of message realized under the same index. Refer to: p2119 Note: Re-parameterization is also possible if a message is present. The change only becomes effective after the message has gone. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 104 Can be changed: - Access level: 3 Data type: Unsigned16 Func. diagram: 8065 Factory setting Description: This counter is incremented every time the alarm buffer changes. Dependency: Refer to: r2110, r2122, r2123, r2124, r2125 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 105 Can be changed: - Access level: 3 TM31 Data type: Unsigned32 Func. diagram: 8050, 8065 Factory setting - [ms] - [ms] - [ms] Description: Displays the system runtime in milliseconds when the alarm occurred. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 106 Change acknowledge mode fault number / Chng ackn F_no CU_DCP, DCP_CTRL Can be changed: U, T Access level: 3 Data type: Unsigned16 Func. diagram: 8075 Factory setting 65535 Description: Selects the faults for which the acknowledge mode is to be changed SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 107 It is not possible to re-parameterize the acknowledge mode for a fault in the following cases: - Fault number does not exist (exception value = 0). - Message type is not "fault" (F). - Acknowledge mode is not permissible for the set fault number. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 108 If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set. Refer to: p2128 Note: CO: r2129 = 0 --> None of the selected messages has occurred. CO: r2129 > 0 --> At least one of the selected messages has occurred. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 109 CO/BO: Status word faults/alarms 2 / ZSW fault/alarm 2 CU_DCP Can be changed: - Access level: 2 Data type: Unsigned16 Func. diagram: 2548 Factory setting Description: Display and BICO output for the second status word of faults and alarms. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 110 CO/BO: Control word faults/alarms / STW fault/alarm TM150, TM15DI_DO, Can be changed: - Access level: 2 TM31 Data type: Unsigned16 Func. diagram: 2546 Factory setting Description: Display and BICO output for the control word of faults and alarms. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 111 Safety message present Internal message 1 present Alarm present 8065 Internal message 2 present Alarm class bit 0 High Alarm class bit 1 High Maintenance required Maintenance urgently required Fault gone/can be acknowledged Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 112 Display and BICO output for the first status word of the monitoring functions. Bit field: Signal name 1 signal 0 signal n_act >= 0 8011 Speed setp - act val deviation in tolerance 8011 t_off SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 113 Display and connector output for frequently used percentage values. Index: [0] = Fixed value +0 % [1] = Fixed value +5 % [2] = Fixed value +10 % [3] = Fixed value +20 % Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 114 This means that the drive system is synchronized to the time specified by the time master. To start p3101[1] must be written to followed by p3101[0]. After writing to p3101[0], the UTC time is accepted. p3101[0]: Milliseconds p3101[1]: Days SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 115 Can be changed: - Access level: 3 Data type: Unsigned32 Func. diagram: - Factory setting Description: Displays the absolute value of the last synchronization deviation that was determined. r3108[0]: Milliseconds r3108[1]: Days Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 116 Can be changed: U, T Access level: 3 TM15DI_DO, TM31 Data type: Unsigned32 / Binary Func. diagram: 2546 Factory setting Description: Sets the signal source for the negated enable signal of external fault 3. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 117 Check the infeed settings. Re bit 03: An inadmissible operating state of the power electronics was identified (overcurrent, overtemperature, IGBT failure, ...). Check that the permissible load cycles are maintained. Check the ambient temperatures (fan). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 118 Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122 Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139). The structure of the fault buffer and the assignment of the indices is shown in r0945. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 119 Value = 0: Assignment to a component not possible. The buffer parameters are cyclically updated in the background (refer to status signal in r2139). The structure of the alarm buffer and the assignment of the indices is shown in r2122. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 120 Description: Displays the diagnostic attribute of the alarm which has occurred. Bit field: Signal name 1 signal 0 signal Hardware replacement recommended Alarm class bit 0 High Alarm class bit 1 High Maintenance required SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 121 Can be changed: - Access level: 3 Data type: Integer32 Func. diagram: 8060 Factory setting Description: Displays the component number of the oldest fault that is still active. Dependency: Refer to: r2131, r3131 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 122 Access level: 4 Data type: Unsigned32 Func. diagram: - Factory setting Description: Displays the counter reading for modified BICO interconnections on this device. The counter is incremented by one for each modified BICO interconnection. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 123 Factory setting 10800 Description: Index 0: Displays the boot state. Index 1: Displays the partial boot state Value: Not active Fatal fault Fault Reset all parameters Drive object modified Download using commissioning software Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 124 Parameter write not inhibited. 0 < r3996[0] < 100: Parameter write inhibited. The value shows how the calculations are progressing. Index: [0] = Progress calculations [1] = Cause Note: Re index 1: Only for internal Siemens troubleshooting. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 125 DI 4 (X530.1) High DI 5 (X530.2) High DI 6 (X530.3) High DI 7 (X530.4) High DI/DO 8 (X541.2) High DI/DO 9 (X541.3) High DI/DO 10 (X541.4) High DI/DO 11 (X541.5) High Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 126 DI 3 (X520.4) High DI 4 (X530.1) High DI 5 (X530.2) High DI 6 (X530.3) High DI 7 (X530.4) High DI/DO 8 (X541.2) High DI/DO 9 (X541.3) High DI/DO 10 (X541.4) High DI/DO 11 (X541.5) High SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 127 DI 4 (X530.1) High DI 5 (X530.2) High DI 6 (X530.3) High DI 7 (X530.4) High DI/DO 8 (X541.2) High DI/DO 9 (X541.3) High DI/DO 10 (X541.4) High DI/DO 11 (X541.5) High Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 128 DI/DO 2 (X520.4) Output Input DI/DO 3 (X520.5) Output Input DI/DO 4 (X520.6) Output Input DI/DO 5 (X520.7) Output Input DI/DO 6 (X520.8) Output Input DI/DO 7 (X520.9) Output Input DI/DO 8 (X521.2) Output Input SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 129 If the signal at the binector input p4030 is high, then terminal COM 0 (X542.2) is connected to NO 0 (X542.3). Note: DO: Digital Output NC: Normally Closed contact NO: Normally Open contact Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 130 Factory setting Description: Sets the signal source for terminal DI/DO 4 (X520.6) of Terminal Module 15 (TM15). Note: Prerequisite: The DI/DO must be set as an output (p4028.4 = 1). DI/DO: Bidirectional Digital Input/Output SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 131 Can be changed: U, T Access level: 1 Data type: Unsigned32 / Binary Func. diagram: 9401 Factory setting Description: Sets the signal source for terminal DI/DO 9 (X521.3) of Terminal Module 15 (TM15). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 132 Factory setting Description: Sets the signal source for terminal DI/DO 11 (X541.5) of Terminal Module 31 (TM31). Note: Prerequisite: The DI/DO must be set as an output (p4028.11 = 1). DI/DO: Bidirectional Digital Input/Output SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 133 Since the sum of the output currents at terminals X541.1, X541.2, X541.3 and X541.4 is limited, an overcurrent or short circuit at one output terminal can cause a dip in the signal at the other terminals. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 134 DI/DO 11 (X541.5) High Note: Inversion using p4048 has been taken into account. The setting of the DI/DO as either input or output is of no significance (p4028). DO: Digital Output DI/DO: Bidirectional Digital Input/Output SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 135 CO: TM31 analog inputs current input voltage/current / TM31 AI U/I_inp TM31 Can be changed: - Access level: 1 Data type: FloatingPoint32 Func. diagram: 9566, 9568 Factory setting Description: Displays the actual input voltage in V when set as voltage input. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 136 15 V or the impressed current of 60 mA; if this is not carefully observed, the input will be damaged. Notice: For operation as a voltage input/current input, switch S5.0 or S5.1 must be appropriately set. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 137 The unit of this parameter (V or mA) depends on the analog input type. Refer to: p4056 Notice: This parameter is automatically overwritten when the analog input type (p4056) is modified. Note: The parameters for the characteristic do not have a limiting effect. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 138 Data type: Integer16 Func. diagram: 9566, 9568 Factory setting Description: Activates the absolute value generation for the analog input signals of Terminal Module 31 (TM31). Value: No absolute value generation Absolute value generation switched in SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 139 - [%] Description: Displays the actual referred output value of the analog outputs of Terminal Module 31 (TM31). Index: [0] = AO 0 (X522.1, X522.2, X522.3) [1] = AO 1 (X522.4, X522.5, X522.6) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 140 For p4076 = 1, 4, p4077 is set to 0.0 %, p4078 to 0.0 V, p4079 to 100.0 % and p4080 to 10.0 V. For p4076 = 2, p4077 is set to 0.0 %, p4078 to 4.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 141 The scaling characteristic for the analog outputs is defined using 2 points. This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the characteristic. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 142 TM15DI_DO Can be changed: U, T Access level: 1 Data type: Unsigned32 / Binary Func. diagram: 9402 Factory setting Description: Sets the signal source for terminal DI/DO 18 (X522.4) of Terminal Module 15 (TM15). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 143 Description: Sets the signal source for terminal DI/DO 23 (X522.9) of Terminal Module 15 (TM15). Note: Prerequisite: The DI/DO must be set as an output (p4028.23 = 1). DI/DO: Bidirectional Digital Input/Output Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 144 High Notice: The raw data of the digital inputs is directly displayed (e.g. without any debounce). Note: Should only used for internal Siemens purposes (alternative r4022, r4023). p4095 TM15DI/DO digital inputs simulation mode / TM15D DI sim_mode TM15DI_DO Can be changed: U, T...
  • Page 145 Bit field: Signal name 1 signal 0 signal DI/DO 0 (X520.2) High DI/DO 1 (X520.3) High DI/DO 2 (X520.4) High DI/DO 3 (X520.5) High DI/DO 4 (X520.6) High DI/DO 5 (X520.7) High Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 146 Sets the simulation mode for the analog inputs of Terminal Module 31 (TM31). Value: Terminal evaluation for analog input x Simulation for analog input x Index: [0] = AI 0 (X521.1/X521.2, S5.0) [1] = AI 1 (X521.3/X521.4, S5.1) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 147 Refer to: p0009, r0110, r0111 Notice: The sampling times entered in index 0 (digital inputs/outputs) and index 2 (analog outputs) must always be greater than or equal to the sampling time in index 1 (analog inputs). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 148 For sensor type "PTC thermistor" (p4100 = 1), the following applies: To activate the corresponding alarm or fault, p4102[0...1] must be set <= 250 °C. Note: The temperature sensor is connected at terminals X522.7(+) and X522.8(-). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 149 (r4105[x] > p4102[2x+1] or the associated timer (p4103[x] has expired. - The fault remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x+1]) - hysteresis (p4118[x]) and the fault has been acknowledged. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 150 For p4102[0...1] = 251 °C, evaluation of the corresponding threshold is deactivated. For sensor type "PTC thermistor" (p4100 = 1), the following applies: To activate the alarm or fault, p4102[0...1] must be set <= 250 °C. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 151 Fault F35207 only causes the drive to be shut down if there is at least one BICO interconnection between the drive and TM31. Note: With p4103 = 0 ms, the timer is de-activated and only the fault threshold is effective. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 152 [1] = Temperature channel 1 [2] = Temperature channel 2 [3] = Temperature channel 3 [4] = Temperature channel 4 [5] = Temperature channel 5 [6] = Temperature channel 6 [7] = Temperature channel 7 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 153 - the temperature sensor is connected at terminals 3(+) and 4(-). - the measuring conductor is connected at terminals 1(+) and 2(-). Value: 1x2 wire evaluation 2x2 wire evaluation 3 wire evaluation 4 wire evaluation Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 154 Wire resistance measurement is only possible for 1x2 or 2x2 wire evaluation (p4108[0...5] = 0, 1). Note: The wire resistance value can be also directly entered into p4110[0...11]. The automatic conductor calibration for 1x2 and 2x2 wire evaluation is always performed with the value in p4110[0...11]. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 155 Temperature channel 3 Temperature channel 4 Temperature channel 5 Temperature channel 6 Temperature channel 7 Temperature channel 8 Temperature channel 9 Temperature channel 10 Temperature channel 11 Dependency: Refer to: r4105, r4112, r4113, r4114 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 156 - [°C] - [°C] Description: Display and connector output for the average value of each group for the Terminal Module 150 (TM150). This value is calculated from the actual temperature values (r4105[0...11]) of each group. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 157 The following applies for a corresponding fault: - Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x+1]) - hysteresis (p4118[x]) and the fault has been acknowledged. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 158 Can be changed: U, T Access level: 3 Data type: Unsigned16 Func. diagram: - Factory setting 65535 Description: Trace functionality for OEM encoder manufacturers. Index: [0] = Encoder 1 [1] = Encoder 2 [2] = Encoder 3 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 159 Displays the actual status of the trace. Value: Trace inactive Trace is recording presamples Trace is waiting for trigger event Trace is recording Recording (trace) ended Index: [0] = Trace 0 [1] = Trace 1 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 160 Displays the required memory in bytes for the actual parameterization. This applies, if the trace for the measurement functions is used. Index: [0] = Trace 0 [1] = Trace 1 Dependency: Refer to: r4799 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 161 Func. diagram: - Factory setting -340.28235E36 340.28235E36 0.00 Description: Sets the trigger threshold for the trace. Index: [0] = Trace 0 [1] = Trace 1 Dependency: Only effective when p4710 = 2, 3. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 162 Factory setting Description: Displays the trigger index in the trace buffer. The trigger event occurred at this point. Index: [0] = Trace 0 [1] = Trace 1 Dependency: Only valid when p4705 = 4. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 163 Data type: Unsigned8 Func. diagram: - Factory setting 0000 bin 0001 bin 0000 bin Description: Sets the averaging in the time range for the trace. Index: [0] = Trace 0 [1] = Trace 1 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 164 Trace record signal 0 / Trace record sig 0 CU_DCP Can be changed: U, T Access level: 3 Data type: Unsigned32 Func. diagram: - Factory setting Description: Selects the first signal to be traced. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 165 [3] = Trace 0 PINx with block Id and PIN Id [4] = Trace 1 PINy with DO Id and chart Id [5] = Trace 1 PINy with block Id and PIN Id Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 166 The values 16385 to 32768 from signal 0, trace 0 are to be read out. In this case, memory bank 1 is set with p4795 = 1. The values can now be read out in r4740[0] to r4740[16383]. Dependency: Refer to: p4795 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 167 Can be changed: - Access level: 3 Data type: FloatingPoint32 Func. diagram: - Factory setting Description: Displays the trace buffer (record buffer) for trace 0 and signal 6. Dependency: Refer to: r4740, p4795 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 168 CU_DCP Can be changed: - Access level: 3 Data type: FloatingPoint32 Func. diagram: - Factory setting Description: Displays the trace buffer (record buffer) for trace 1 and signal 4. Dependency: Refer to: r4740, p4795 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 169 Trace 0 trace buffer signal 1 / Trace 0 tr sig 1 CU_DCP Can be changed: - Access level: 3 Data type: Unsigned32 Func. diagram: - Factory setting Description: Displays the trace buffer (record buffer) for trace 0 and signal 1. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 170 Trace 0 trace buffer signal 7 / Trace 0 tr sig 7 CU_DCP Can be changed: - Access level: 3 Data type: Unsigned32 Func. diagram: - Factory setting Description: Displays the trace buffer (record buffer) for trace 0 and signal 7. Dependency: Refer to: r4760 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 171 Can be changed: - Access level: 3 Data type: Unsigned32 Func. diagram: - Factory setting Description: Displays the trace buffer (record buffer) for trace 1 and signal 5. Dependency: Refer to: r4760 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 172 1111 1111 1111 1111 1111 1111 0000 bin 1111 1111 bin Description: Sets the physical address for the third signal to be traced. The data type is defined using p4732. Index: [0] = Trace 0 [1] = Trace 1 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 173 0000 bin 1111 1111 bin Description: Sets the physical address for the eighth signal to be traced. The data type is defined using p4737. Index: [0] = Trace 0 [1] = Trace 1 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 174 Data type: Unsigned32 Func. diagram: - Factory setting Description: Changes over the memory bank to read out the contents of the trace buffer. Dependency: Refer to: r4740, r4741, r4742, r4743, r4750, r4751, r4752, r4753 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 175 Access level: 3 Data type: Integer16 Func. diagram: - Factory setting Description: The function generator is started with p4800 = 1. The signal is only generated for a 1 signal of binector input p4819. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 176 Can be changed: U, T Access level: 3 Data type: Unsigned32 Func. diagram: - Factory setting 4294967295 Description: Sets the physical address where the function generator is to be connected. Dependency: Only effective when p4810 = 99. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 177 Function generator signal shape / FG signal shape CU_DCP Can be changed: U, T Access level: 3 Data type: Integer16 Func. diagram: - Factory setting Description: Sets the signal to be generated for the function generator. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 178 Only effective for p4820 = 2 (staircase). Units are dependent on p4810. If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current). If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 179 0.00000 [%] 200.00000 [%] 100.00000 [%] Description: Sets the scaling for the amplitude of the signal waveforms for all output channels. The value can be changed while the function generator is running. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 180 MTrace cycle number setting / Cycle number CU_DCP Can be changed: U, T Access level: 3 Data type: Unsigned32 Func. diagram: - Factory setting 4294967295 Description: Sets the number of cycles of a multiple trace. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 181 Can be changed: - Access level: 4 TM15DI_DO, TM31 Data type: Unsigned16 Func. diagram: - Factory setting Description: Displays the total length of the GUIDs of the OA applications installed on this drive object. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 182 Refer to: r4950, r4951, r4952, r4955, p4956, r4957, r4959, r4960 Notice: If there is no OA application, then it is not possible to access an index. Note: Example: The value 1010100 should be interpreted as V01.01.01.00. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 183 Can be changed: - Access level: 4 Data type: Unsigned16 Func. diagram: - Factory setting Description: Displays the total length of the IDs of all the OA applications installed on the memory card/device memory. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 184 Refer to: r4985, r4986, r4987, r4988, r4989, r4991, r4992, r4993, r4994 Notice: If there is no OA application, then it is not possible to access an index. Note: Example: The value 1010100 should be interpreted as V01.01.01.00. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 185 Func. diagram: - Factory setting Description: Displays the properties of all the OA applications installed on the memory card/device memory. r4994[0]: Version of OA application 1 r4994[1]: Version of OA application 2, ... Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 186 Refer to: r4985, r4986, r4987, r4988, r4989, r4990, r4991, r4992, r4993 Notice: If there is no OA application, then it is not possible to access an index. Note: The parameter is only for internal Siemens diagnostics. r7760 Write protection/know-how protection status / Wr_prot/KHP stat CU_DCP, TM150,...
  • Page 187 = 51 dec --> ASCII characters = "3" --> serial number, character 6 r7843[6] = 69 dec --> ASCII characters = "E" --> serial number, character 7 r7843[7] = 0 dec --> ASCII characters = " " --> serial number, character 8 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 188 Displays the configuration changes on the drive object. Index: [0] = Sum of the following indices [1] = p0010, p0107, p0108 [2] = Drive object name (p0199) [3] = Structure-relevant parameters (e.g. p0180) [4] = BICO interconnections SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 189 Re index 1: Drive object faults. When changing r0944, the value in this index is incremented. Re index 2: Drive object alarms. When changing r2121, the value in this index is incremented. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 190 Factory setting Description: Displays the ACX file saved in the appropriate directory in the non-volatile memory. Dependency: Refer to: p1000 Note: For a value = 9999999, the following applies: The read operation is still running. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 191 Only characters belonging to the standard ASCII character set may be used (32 dec to 126 dec). Note: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual. Re p8806[0...31]: System identifier. Re p8806[32...53]: Location identifier. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 192 Parameter p8809 contains the information described below. Re p8809[0...3]: Contains the value from r9781[0] "SI change tracking checksum functional". Re p8809[4...7]: Contains the value from r9782[0] "SI change tracking time stamp checksum functional". Re p8809[8...53]: Reserved. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 193 Refer to: F08501 Note: This monitoring function only monitors the connection between the Control Unit and COMM BOARD and not the data traffic on the fieldbus. Value = 0: Monitoring is de-activated. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 194 IF2 PZD sampling time / IF2 PZD t_sample CU_DCP Can be changed: C1(3) Access level: 3 Data type: FloatingPoint32 Func. diagram: - Factory setting 1.00 [ms] 16.00 [ms] 4.00 [ms] Description: Sets the sampling time for the cyclic interface 2 (IF2). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 195 [20] = PZD 21 [21] = PZD 22 [22] = PZD 23 [23] = PZD 24 [24] = PZD 25 [25] = PZD 26 [26] = PZD 27 [27] = PZD 28 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 196 IF2 diagnostics PZD send / IF2 diag PZD send DCP_CTRL Can be changed: - Access level: 3 Data type: Unsigned16 Func. diagram: 2487, 9208, 9210 Factory setting Description: Displays the sent PZD (actual values) sent via interface 2. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 197 [56] = PZD 57 [57] = PZD 58 [58] = PZD 59 [59] = PZD 60 [60] = PZD 61 [61] = PZD 62 [62] = PZD 63 [63] = PZD 64 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 198 CU_DCP (PROFINET Can be changed: - Access level: 3 CBE20) Data type: Integer16 Func. diagram: - Factory setting Description: Status display for COMM BOARD. Value: No initialization Fatal fault Initialization Send configuration Receive configuration SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 199 = x --> state of cyclic communication r8858[3] = y --> state of the IP configuration r8858[4] = 1281 --> device ID 0501 hex = SINAMICS S120/S150 r8858[5 ... 39] --> only for internal Siemens diagnostics. r8859[0...7] COMM BOARD identification data / CB ident data...
  • Page 200 FloatingPoint data types. A BICO interconnection for a single PZD can only take place either on r8850 or r8860. A maximum of 4 indices of the "trace" function can be used. Note: IF2: Interface 2 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 201 [50] = PZD 51 + 52 [51] = PZD 52 + 53 [52] = PZD 53 + 54 [53] = PZD 54 + 55 [54] = PZD 55 + 56 [55] = PZD 56 + 57 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 202 [40] = PZD 41 + 42 [41] = PZD 42 + 43 [42] = PZD 43 + 44 [43] = PZD 44 + 45 [44] = PZD 45 + 46 [45] = PZD 46 + 47 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 203 Access level: 3 TM15DI_DO, TM31 Data type: Unsigned16 Func. diagram: - Factory setting Description: Display for the maximum interconnected PZD in the receive/send direction Index 0: receive (r8850, r8860) Index 1: send (p8851, p8861) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 204 [4] = PZD 5 [5] = PZD 6 [6] = PZD 7 [7] = PZD 8 [8] = PZD 9 [9] = PZD 10 [10] = PZD 11 [11] = PZD 12 [12] = PZD 13 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 205 [6] = PZD 7 [7] = PZD 8 [8] = PZD 9 [9] = PZD 10 [10] = PZD 11 [11] = PZD 12 [12] = PZD 13 [13] = PZD 14 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 206 IF2 diagnostics bus address PZD receive / IF2 diag addr recv TM150, TM15DI_DO, Can be changed: - Access level: 3 TM31 Data type: Unsigned16 Func. diagram: - Factory setting Description: Displays the bus address of sender from which the PZD is received. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 207 [44] = PZD 45 [45] = PZD 46 [46] = PZD 47 [47] = PZD 48 [48] = PZD 49 [49] = PZD 50 [50] = PZD 51 [51] = PZD 52 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 208 [17] = PZD 18 [18] = PZD 19 [19] = PZD 20 [20] = PZD 21 [21] = PZD 22 [22] = PZD 23 [23] = PZD 24 [24] = PZD 25 [25] = PZD 26 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 209 BI: IF2 binector-connector converter status word 1 / Bin/con ZSW1 DCP_CTRL Can be changed: U, T Access level: 3 Data type: Unsigned32 / Binary Func. diagram: 2489 Factory setting Description: Selects bits to be sent via interface 2. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 210 [1] = Bit 1 [2] = Bit 2 [3] = Bit 3 [4] = Bit 4 [5] = Bit 5 [6] = Bit 6 [7] = Bit 7 [8] = Bit 8 [9] = Bit 9 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 211 [9] = Bit 9 [10] = Bit 10 [11] = Bit 11 [12] = Bit 12 [13] = Bit 13 [14] = Bit 14 [15] = Bit 15 Dependency: Refer to: p8888, r8889 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 212 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: p8851, p8880, p8881, p8882, p8883, p8884, p8888 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 213 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: r8850 Note: IF2: Interface 2 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 214 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: r8850 Note: IF2: Interface 2 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 215 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: p8898, p8899 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 216 Every SINAMICS device type has its own PROFINET Device ID and its own PROFINET GSD. Note: List of the SINAMICS Device IDs: 0501 hex: S120/S150 0504 hex: G130/G150 050A hex: DC MASTER 050C hex: MV 050F hex: G120P 0510 hex: G120C 0511 hex: G120 CU240E-2 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 217 Access level: 3 CBE20) Data type: Unsigned8 Func. diagram: - Factory setting Description: Sets the DHCP mode for the Communication Board Ethernet 20/25 (CBE20/CBE25). Dependency: Refer to: p8940, p8941, p8942, p8943, p8945 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 218 CBE2x IP Address of Station active / CBE2x IP act CU_DCP (PROFINET Can be changed: - Access level: 3 CBE20) Data type: Unsigned8 Func. diagram: - Factory setting Description: Displays the active IP address for the Communication Board Ethernet 20/25 (CBE20/CBE25). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 219 DAP ID = 20007 hex: SINAMICS CBE20 V4.5 DAP ID = 20008 hex: SINAMICS CBE20 V4.6 DAP ID = 20009 hex: SINAMICS CBE20 V4.7 DAP ID = 20209 hex: SINAMICS CBE25 V4.7 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 220 Data setting to read topology properties. The result is displayed depending on the property in r9207 or r9208. Re index 0: 0: actual topology, 1: target topology Re index 1: Sets the component number of the component involved. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 221 Can be changed: U, T Access level: 3 Data type: Unsigned16 Func. diagram: - Factory setting Description: Sets the component number for a component to get its status LED to flash. Dependency: Refer to: p9211 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 222 Index 3: Maximum time of all acyclic requests referred to the parameter Id (index 0). Index 4: Average of all acyclic requests referred to the parameter Id (index 0). The time unit is 10us. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 223 Displays the status of the memory card. Bit field: Signal name 1 signal 0 signal Memory card inserted Memory card activated SIEMENS memory card Memory card as USB data storage medium from the PC used Dependency: Refer to: p9400 Note: Re bit 01, 00: Bit 1/0 = 0/0: No memory card inserted (corresponds to p9400 = 0).
  • Page 224 Re bit 02, 00: Bit 2/0 = 0/0: No memory card inserted. Bit 2/0 = 0/1: Memory card inserted, but not a SIEMENS memory card. Bit 2/0 = 1/0: Status not possible. Bit 2/0 = 1/1: SIEMENS memory card inserted.
  • Page 225 The list is sorted according to signal sources and is structured as follows: r9842[0]: Interconnection 1 (signal sink, BICO coded), r9843[0]: Interconnection 1 (signal source, BICO coded) r9842[1]: Interconnection 2 (signal sink, BICO coded), r9843[1]: Interconnection 2 (signal source, BICO coded) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 226 Otherwise, another drive would continue to attempt to read a signal from a drive that no longer existed. Note: All indices of r9491 to p9493 designate the same interconnection. r9491[x] contains the signal receiver and r9492[x] the matching signal source; p9493[x] can be set to modify the interconnection. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 227 - the number of interconnections is zero (p9497 = 0). For p9495 not equal to 0, the following applies: - the BI/CI parameters involved are listed in p9498[0...29] (signal sink). - the associated BO/CO parameters are listed in p9499[0...29] (signal source). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 228 Dependency: Refer to: p9495, p9496, p9497, p9498 Refer to: A01318, A01507 Note: A BICO interconnection (signal sink, signal source) is displayed in the same index of p9498 and p9499. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 229 Access level: 3 Data type: FloatingPoint32 Func. diagram: - Factory setting - [%] - [%] - [%] Description: Displays the system utilization. If the utilization is greater than 100%, fault F01054 is output. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 230 [16] = Net utilization 8 [17] = Total utilization 8 [18] = Net utilization 9 [19] = Total utilization 9 [20] = Net utilization 10 [21] = Total utilization 10 [22] = Net utilization 11 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 231 [82] = Net utilization 41 [83] = Total utilization 41 [84] = Net utilization 42 [85] = Total utilization 42 [86] = Net utilization 43 [87] = Total utilization 43 [88] = Net utilization 44 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 232 [148] = Net utilization 74 [149] = Total utilization 74 [150] = Net utilization 75 [151] = Total utilization 75 [152] = Net utilization 76 [153] = Total utilization 76 [154] = Net utilization 77 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 233 [30] = Net utilization 15 [31] = Total utilization 15 [32] = Net utilization 16 [33] = Total utilization 16 [34] = Net utilization 17 [35] = Total utilization 17 [36] = Net utilization 18 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 234 [96] = Net utilization 48 [97] = Total utilization 48 [98] = Net utilization 49 [99] = Total utilization 49 [100] = Net utilization 50 [101] = Total utilization 50 [102] = Net utilization 51 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 235 [161] = Total utilization 80 [162] = Net utilization 81 [163] = Total utilization 81 [164] = Net utilization 82 [165] = Total utilization 82 Dependency: Refer to: r9975, r9980 Refer to: F01054 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 236 Displays the calculated DRIVE-CLiQ system load based on the existing target topology. The values are not made available until the RUNUP READY (800) state is adopted (see p3988). Index 0 ... 7 corresponds to DRIVE-CLiQ socket X100 ... X107. Dependency: Refer to: F01340 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 237 Memory usage drive object reference value / Mem_use DO ref val CU_DCP Can be changed: - Access level: 4 Data type: Unsigned32 Func. diagram: - Factory setting Description: Displays the memory usage for each drive object as reference value. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 238 Data type: Unsigned32 Func. diagram: - Factory setting Description: Diagnostics parameter to display additional information for internal software errors. Note: Only for internal Siemens troubleshooting. r50000 Operating display / Op_display DCP_CTRL Can be changed: - Access level: 1 Data type: FloatingPoint32 Func.
  • Page 239 Data type: Integer32 Func. diagram: 2650, 6830 Factory setting Description: Display and connector output for the sequence control operating state. SINAMICS DCP is presently being operated in these quadrants. Note: Value: significance (quadrant) 0: pulse inhibit 1: step-down, positive current...
  • Page 240 DCP_CTRL Can be changed: - Access level: 1 Data type: FloatingPoint32 Func. diagram: 6860 Factory setting - [A] - [A] - [A] Description: Displays the rated DC current as stamped on the rating plate. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 241 Data type: Integer16 Func. diagram: 3100 Factory setting Description: Sets the signal level for fixed bit 0. This value is available at binector output r53230.0 for interconnection. Value: High Dependency: Refer to: r53230 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 242 Can be changed: U, T Access level: 3 Data type: Integer16 Func. diagram: 3100 Factory setting Description: Sets the signal level for fixed bit 5. This value is available at binector output r53230.5 for interconnection. Value: High SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 243 Can be changed: U, T Access level: 2 Data type: FloatingPoint32 Func. diagram: 8030 Factory setting 0 [°C] 200 [°C] 0 [°C] Description: Sets the alarm threshold for monitoring the external temperature (terminal X177.53-55). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 244 Access level: 3 Data type: FloatingPoint32 Func. diagram: 2075 Factory setting -200.00 [%] 200.00 [%] 0.00 [%] Description: Sets the offset for analog input 0 (AI 0, X177.25/26) on the CUD. Note: AI: Analog Input SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 245 Sets the type for analog input 1 (AI 1, X177.27/28) on the CUD. Value: Bipolar voltage input (-10 V ... +10 V) Bipolar current input (-20 mA ... +20 mA) Unipolar current input monitored (+4 mA ... +20 mA) Note: AI: Analog Input Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 246 Func. diagram: 2080 Factory setting 0 [ms] 10000 [ms] 0 [ms] Description: Sets the time constant for smoothing the signal from analog input 1 (AI 1, X177.27/28) on the CUD. Note: AI: Analog Input SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 247 Factory setting Description: Sets the signal source for inverting the signal from analog input 2 (AI 2, X177.29/30) on the CUD. 1 signal: inversion 0 signal: no inversion Note: AI: Analog Input Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 248 Fast analog inputs signal processing / Fast AI sig DCP_CTRL Can be changed: T Access level: 3 Data type: Integer16 Func. diagram: 2085, 2090 Factory setting Description: Sets the signal processing for fast analog inputs "Select input 3 ... 6". SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 249 60.00 [V] Description: Sets the input voltage (8 - 270 V) for scaling to 100%. Notice: This analog input cannot be externally accessed. It is reserved for subsequent use. Note: AI: Analog Input Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 250 Description: Sets the signal source for enabling the analog input for the "main actual value (XT1.103/104). Notice: This analog input cannot be externally accessed. It is reserved for subsequent use. Note: AI: Analog Input SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 251 Access level: 3 Data type: Unsigned32 / FloatingPoint32 Func. diagram: 2095 Factory setting Description: Sets the signal source for the output value at analog output 1 (AO 1, X177.51/52). Note: AO: Analog Output Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 252 Can be changed: U, T Access level: 3 Data type: FloatingPoint32 Func. diagram: 2050 Factory setting 0 [ms] 10000 [ms] 0 [ms] Description: Sets the delay time for digital input 1 (DI 1, X177.12) on the CUD. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 253 Access level: 3 Data type: Unsigned32 / Binary Func. diagram: 2055 Factory setting Description: Sets the signal source for digital output 1 (DO 1, X177.20) on the CUD. Note: DO: Digital Output Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 254 Access level: 3 Data type: FloatingPoint32 Func. diagram: 2055 Factory setting 0 [ms] 10000 [ms] 0 [ms] Description: Sets the delay time for digital output 3 (DO 3, X177.22) on the CUD. Note: DO: Digital Output SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 255 Can be changed: U, T Access level: 3 Data type: Unsigned32 / Binary Func. diagram: 2065 Factory setting Description: Sets the signal source for digital input/output 7 (DI/DO 7, X177.18) on the CUD. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 256 Can be changed: T Access level: 3 Data type: Integer16 Func. diagram: 2060, 2065 Factory setting Description: Sets the type for digital input/output 4 ... 7 (DI/DO 4 ... DI/DO 7) of the CUD. Value: Input Output SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 257 Displays the mainboard serial number. Index 0: serial number character 1 Index 31: serial number character 32 Note: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 258 Index 26: current power unit 3 - setpoint current 2 [0.01 A] Index 27: current power unit 3 - actual current 2 [0.01 A] - - - - - - - - - - SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 259 Can be changed: - Access level: 4 Data type: Unsigned16 Func. diagram: 8054 Factory setting Description: This parameter is only for internal Siemens troubleshooting. r50829[0...55] CUD calibration values / CUD calib. val DCP_CTRL Can be changed: - Access level: 4 Data type: Unsigned16 Func.
  • Page 260 Display and connector output for the status of the trace. In the least significant byte, the parameter value contains the status of trace 0 – and in the most significant byte, the status of trace 1. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 261 - from the first telegram received error-free after switching on the electronics power supply. The telegram can be received from any device. - from the first telegram received error-free after the telegram monitoring responds (as the failure time has expired). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 262 Parallel interface CAN diagnostics information / Par_IF CAN diag DCP_CTRL Can be changed: - Access level: 2 Data type: Unsigned16 Func. diagram: 9350 Factory setting Description: Displays the CAN diagnostic information for the parallel interface. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 263 DCP_CTRL Can be changed: - Access level: 3 Data type: FloatingPoint32 Func. diagram: 3100 Factory setting - [%] - [%] - [%] Description: Connector output with constant fixed value value -200 %. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 264 Data type: FloatingPoint32 Func. diagram: 2075 Factory setting - [%] - [%] - [%] Description: Display and connector output for the raw value at the "Main actual value" analog input (XT1.103/104). Note: AI: Analog Input SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 265 Factory setting - [%] - [%] - [%] Description: Display and connector output for the raw value at analog input 3 (X177.1/2) on the CUD. Dependency: Refer to: r52019 Note: AI: Analog Input Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 266 Func. diagram: 2090 Factory setting - [%] - [%] - [%] Description: Display and connector output for the raw value at analog input 6 (X177.7/8) on the CUD. Dependency: Refer to: r52025 Note: AI: Analog Input SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 267 Description: Display and connector output for the power unit temperatures of the device. Index: [0] = Temperature power unit 1 [1] = Temperature power unit 2 [2] = Temperature power unit 3 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 268 0 signal DI 0 (X177.11) High 2050 DI 0 inverted (X177.11) High 2050 DI 1 (X177.12) High 2050 DI 1 inverted (X177.12) High 2050 DI 2 (X177.13) High 2050 DI 2 inverted (X177.13) High 2050 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 269 DI/DO 7 (X177.18) overload present 2065 Dependency: For bits 04 ... 07: The terminal must be set as an output (p50789[0...3] = 1). Note: DO: Digital Output DI/DO: bidirectional digital input/digital output Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 270 Display and BICO output for the state of the telegram monitoring for the parallel interface. Bit field: Signal name 1 signal 0 signal Telegram monitoring timeout - continuous 9350 signal Telegram monitoring timeout - pulse 9350 OFF1 from master 9350 Pulse enable from the master 9350 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 271 In this time interval, the MPP tracker changes the current setpoint in order to identify the point with the maximum power. Note: MPP: maximum power point (point along the characteristic with the maximum power) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 272 0.00 [s] 100.00 [s] 0.05 [s] Description: Sets the time constant for smoothing the actual power value. Dependency: Refer to: p54010, r54015 Note: MPP: maximum power point (point along the characteristic with the maximum power) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 273 - [%] - [%] Description: Display and connector output for the output of the MPP tracker after manual/automatic switchover. Note: MPP: maximum power point (point along the characteristic with the maximum power) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 274 Can be changed: - Access level: 2 Data type: FloatingPoint32 Func. diagram: 6700 Factory setting - [A] - [A] - [A] Description: Displays the current values of the last PV array characteristic that was plotted. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 275 Selects the signal source for the voltage actual value. Value: Actual value voltage side 1 Actual value voltage side 2 Actual value voltage inner side 1 Actual value voltage inner side 2 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 276 Sets the width of the dead range in the setpoint-actual value difference channel for the "DC link buffering" function. Dependency: Refer to: p54146 Note: The set value refers to the rated voltage of the SINAMICS DCP. p54125 Voltage controller proportional gain / U_ctrl Kp DCP_CTRL...
  • Page 277 Can be changed: T Access level: 2 Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6818 Factory setting 52002[0] Description: Sets the signal source for the positive current limit of the voltage controller. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 278 DCP_CTRL Can be changed: T Access level: 2 Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6720 Factory setting 55506[0] Description: Sets the signal source for the voltage actual value of the battery charging characteristic. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 279 2 r54211[2]: current value characteristic point 2 r54210[3]: voltage value characteristic point 3 r54211[3]: current value characteristic point 3 Note: Linear interpolation is realized between the individual points. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 280 Mainboard LED test / Mainb LED test DCP_CTRL Can be changed: U, T Access level: 3 Data type: Unsigned16 Func. diagram: 8055 Factory setting 0000 bin Description: Setting to test LEDs H1000 and H1010 on the mainboard. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 281 Mainboard diagnostics EEPROM write protection / EEPROM write_prot DCP_CTRL Can be changed: U, T Access level: 4 Data type: Integer16 Func. diagram: 8055 Factory setting Description: Sets the write protection for the EEPROM on the mainboard. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 282 Current side 2 Power Note: The current actual value sensing in SINAMICS DCP measures the reactor current. The specified setpoint is converted into a reactor current setpoint and this is used for the closed-loop current control. For value = 10:...
  • Page 283 Can be changed: - Access level: 2 Data type: FloatingPoint32 Func. diagram: 6806 Factory setting - [%] - [%] - [%] Description: Display and connector output for the current setpoint after the correction current controller. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 284 [5] = Barrier layer temperature at free-wheeling diode D1B [6] = Barrier layer temperature at free-wheeling diode D2A [7] = Barrier layer temperature at free-wheeling diode D2B [8] = Maximum permissible barrier layer temperature SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 285 Sets the permissible overload time for the dynamic overload. Dependency: Refer to: F60530 Note: Fault F60530 is initiated if the duration of the maximum permissible overload current exceeds the time set here. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 286 Func. diagram: 6810 Factory setting 0.00 [V] 600.00 [V] 30.00 [V] Description: Sets the minimum voltage. Operation is only possible if the voltages on side 1 and side 2 continuously exceed the value set here. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 287 CO/BO: Limitation status / Lim status DCP_CTRL Can be changed: - Access level: 2 Data type: Unsigned16 Func. diagram: 6810 Factory setting Description: Display and connector output for the status of the setpoint limiting. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 288 Data type: FloatingPoint32 Func. diagram: 6812 Factory setting 0 [V] 1500 [V] 1000 [V] Description: Sets the upper threshold value for the overvoltage on side 1. The reactor current is reduced to zero from this value. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 289 Can be changed: - Access level: 2 Data type: FloatingPoint32 Func. diagram: 6812 Factory setting - [%] - [%] - [%] Description: Display and connector output for the reactor current setpoint after the voltage limiting. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 290 Can be changed: - Access level: 2 Data type: FloatingPoint32 Func. diagram: 6820 Factory setting - [%] - [%] - [%] Description: Display and connector output for the reactor current setpoint of the main current controller. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 291 Can be changed: - Access level: 2 Data type: FloatingPoint32 Func. diagram: 6820 Factory setting - [%] - [%] - [%] Description: Display and connector output for the PI output of the main current controller. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 292 Access level: 2 Data type: FloatingPoint32 Func. diagram: 6820 Factory setting 1.0 [%] 50.0 [%] 10.0 [%] Description: Sets the lower limit of the voltage actual values for precontrol and adaptation of the main current controller. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 293 Display and connector output for the outputs of the differential current controller. Index 0: Correction value to symmetrize power units 1 and 2. Index 1: Correction value to symmetrize power units 1 and 3. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 294 0.00 [%] 200.00 [%] 200.00 [%] Description: Sets the positive limiting for the control angle. In conjunction with p55306, it is possible to restrict the operating range of the SINAMICS DCP. Dependency: Refer to: p55306 Note: Examples: Control angle limited to: 0 ...
  • Page 295 Can be changed: - Access level: 3 Data type: FloatingPoint32 Func. diagram: 6830 Factory setting - [Hz] - [Hz] - [Hz] Description: Display and connector output for the actual switching frequency of the modulator. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 296 Func. diagram: 6835 Factory setting 0.0 [%] 20.0 [%] 3.0 [%] Description: Sets the tolerance for reaching the setpoint voltage for resistor or pulsing up precharging. Index: [0] = Side 1 [1] = Side 2 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 297 The signals to be traced are fixed and cannot be changed. The recorded trace is output periodically at this parameter. Between the individual repeats, there is a pause (all signals = 0) of approximately 5 ms. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 298 Sets the maximum speed for the device fan. This parameter is used for the following applications: - reducing fan noise in the final test area. - consciously allowing the device temperature to rise faster to stress the device for testing purposes. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 299 Procedure to reset the operating hours: Set p55472 = 1 --> the operating hours counter (r55470) is set to zero. --> the parameter is automatically set to zero after this is done. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 300 Can be changed: - Access level: 2 Data type: FloatingPoint32 Func. diagram: 6818, 6850 Factory setting - [%] - [%] - [%] Description: Display and connector output for the inner voltage on side 1. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 301 Access level: 2 Data type: FloatingPoint32 Func. diagram: 6850 Factory setting - [%] - [%] - [%] Description: Display and connector output for the reactor current of power unit 2. Dependency: Refer to: r55510 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 302 - [%] - [%] - [%] Description: Display and connector output for the sum of the averaged reactor currents. The value is the sum of r55521, r55522 and r55523. Dependency: Refer to: r55521, r55522 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 303 Factory setting - [A] - [A] - [A] Description: Displays the sum of the averaged reactor currents. The value is the sum of r55531, r55532 and r55533. Dependency: Refer to: r55531, r55532 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 304 [3] = Power at side 1 (with external current measurement) [4] = Power at side 2 (with external current measurement) Note: SINAMICS DCP cannot measure the power. For index 0: P = U_out * I_out The power is calculated from the voltage measured at the output and the calculated output current.
  • Page 305 Display and connector output for the actual value of the current at side 1. Note: The current actual value sensing in SINAMICS DCP measures the reactor current. The current at side 1 is calculated from the reactor current actual value.
  • Page 306 Overcurrent has occurred in power unit 2 6855 Overvoltage has occurred at side 1. 6855 Overvoltage has occurred at side 2. 6855 Overtemperature has occurred at the AC 6855 Overtemperature has occurred at the BD 6855 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 307 Power unit properties frequency / PU property f DCP_CTRL Can be changed: - Access level: 3 Data type: FloatingPoint32 Func. diagram: 6860 Factory setting - [kHz] - [kHz] - [kHz] Description: Displays the clock frequency of the power unit. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 308 PROFINET IP of Station / PN IP of Station CU_DCP (PROFINET Can be changed: - Access level: 3 CBE20) Data type: Unsigned8 Func. diagram: 2410 Factory setting Description: Displays PROFINET IP of Station. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 309 Internal control/status words Sequence control Auxiliary functions Superimposed closed-loop control Closed-loop control 3.10 Signals and monitoring functions 3.11 Faults and alarms 3.12 Data sets 3.13 Communication between devices 3.14 Basic Operator Panel 20 (BOP20) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 310: Table Of Contents

    3102 – Function generator ............SINAMICS DCP...
  • Page 311 8560 – Command Data Sets (CDS) ........... . . Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 312 9912 – Control word interconnection ........... . SINAMICS DCP...
  • Page 313: Explanations On The Function Diagrams

    Explanations on the function diagrams Function diagrams 1020 – Explanation of the symbols (part 1) 1021 – Explanation of the symbols (part 2) 1022 – Explanation of the symbols (part 3) 1030 – Handling BICO technology Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 314 Parameter belongs to Power Unit A static state is represented here. The (Def.w) Not relevant Data Set (PDS) sampling time data is not relevant. [1020.7] [aaaa.b] DO: All Objects Function diagram fp_1020_89.vsd - Explanation of the symbols (part 1) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 315 S & H Sample and hold element. y = x if SET = 1 (no retentive memory during POWER OFF) DO: All Objects Function diagram fp_1021_89.vsd Siemens Parts - Explanation of the symbols (part 2) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 316 1 for pulse duration T. The pulse generator signal state. cannot be retriggered. At T=0, a pulse duration of one cycle applies. DO: All Objects Function diagram fp_1022_89.vsd - Explanation of the symbols (part 3) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 317 Terminal X122.1 acts as "Jog bit 0". p840[0] = 2090.0 The motorized potentiometer output acts as the main setpoint for the speed controller. p55050] = 2050[1] DO: All Objects Function diagram fp_1030_89.vsd Siemens Parts - Handling BICO technology SINAMICS DCP 03.06.2014 v 1.2...
  • Page 318: Cud Input/Output Terminals

    2080 – Analog inputs (AI 1 ... AI 2) 2085 – Analog inputs (AI 3 ... AI 4) 2090 – Analog inputs (AI 5 ... AI 6) 2095 – Analog outputs (AO 0 ... AO 1) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 319 24 V X177.13 DI 2 r53010.04 r53010.05 p50768 (50 ms) 24 V X177.14 DI 3 r53010.06 r53010.07 DO: DCP_CTRL Function diagram fp_2050_89.vsd Siemens Parts - 2050 - - Digital inputs (DI 0 ... DI 3) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 320 <1> DO 3 X177.22 Short-circuit A60018 monitoring X177.24 DO overload r53021.03 <1> For log. "1": Output transistor is conductive DO: DCP_CTRL Function diagram fp_2055_89.vsd - 2055 - - Digital outputs (DO 0 ... DO 3) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 321 <1> The wiring represented as a dashed line applies during use as a digital output (p50789[x] = 1) DO: DCP_CTRL Function diagram fp_2060_89.vsd Siemens Parts - 2060 - - Digital inputs/outputs bidirectional (DI/DO 4 ... DI/DO 5) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 322 <1> The wiring represented as a dashed line applies during use as a digital output (p50789[x] = 1) DO: DCP_CTRL Function diagram fp_2065_89.vsd - 2065 - - Digital inputs/outputs bidirectional (DI/DO 6 ... DI/DO 7) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 323 (0.00) 0...10000 [ms] -270.00...270.00 [V] p50745 (0) p50741[D] (60.00) <1> r52013 r52012 <1> This analog input is not accessible. DO: DCP_CTRL Function diagram fp_2075_89.vsd Siemens Parts - 2075 - - Analog inputs (AI 0) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 324 -1000.0...1000.0 [%] 0...10000 [ms] 10V=100% p50721[D] (100.0) p50725 (0) X177.29 p50721 r52017 AI 2 100% [5884.1] ± 10V X177.30 r52016 DO: DCP_CTRL Function diagram fp_2080_89.vsd - 2080 - - Analog inputs (AI 1 ... AI 2) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 325 0...10000 [ms] p50731[1] (100.0) p50735[1] (0) 100μs X177.3 p50731 r52021 AI 4 100% ± 10V X177.4 r52020 DO: DCP_CTRL Function diagram fp_2085_89.vsd Siemens Parts - 2085 - - Analog inputs (AI 3 ... AI 4) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 326 -1000.0...1000.0 [%] 0...10000 [ms] p50731[3] (100.0) p50735[3] (0) 100μs X177.7 p50731 r52025 AI 6 100% ± 10V X177.8 r52024 DO: DCP_CTRL Function diagram fp_2090_89.vsd - 2090 - - Analog inputs (AI 5 ... AI 6) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 327 CUD AO 1 s_src 100% p50755 X177.51 y [V] = * p50758 100% AO 1 r52027 X177.52 DO: DCP_CTRL Function diagram fp_2095_89.vsd Siemens Parts - 2095 - - Analog outputs (AO 0 … AO 1) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 328: Profidrive

    2410 – PROFIBUS (PB)/PROFINET (PN)/USS, addresses and diagnostics 2460 – IF1 receive telegram, free interconnection via BICO (p0922 = 999) 2470 – IF1 send telegram, free interconnection via BICO (p0922 = 999) 2472 – IF1 status words, free interconnection SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 329 <5> Bus termination can be switched on/off with p50820 <6> Not with CPU stop DO: CU_DCP;DCP_CTRL Function diagram fp_2410_89.vsd Siemens Parts - 2410 - - PROFIBUS (PB) / PROFINET (PN) / USS, addresses and diagnostics SINAMICS DCP 03.06.2014 v 1.2...
  • Page 330 <4> The connector-binector converter only ever converts the lower 16 bits, regardless of the input variable. DO: DCP_CTRL Function diagram fp_2460_89.vsd - 2460 - - IF1 receive telegram, free interconnection via BICO (p0922 = 999) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 331 (Telegram content = 4000 hex or 4000 0000 hex for double words if the input variable has the value 100%.) DO: DCP_CTRL Function diagram fp_2470_89.vsd Siemens Parts - 2470 - - IF1 send telegram, free interconnection via BICO (p0922 = 999) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 332 Bin/con ZSW inv Bin/con ZSW inv p02088[4].0 p02088[1].15 Bin/con ZSW send p02084 [0...15] [15] r02089[4] Bin/con ZSW inv p02088[4].15 [15] DO: DCP_CTRL;CU_DCP Function diagram fp_2472_89.vsd - 2472 - - IF1 status words, free interconnection SINAMICS DCP 03.06.2014 v 1.2...
  • Page 333: Internal Control/Status Words

    3.5 Internal control/status words Internal control/status words Function diagrams 2546 – Control word, faults/alarms 2548 – Status word, faults/alarms 1 2580 – Control word, sequence control 2585 – Status word, sequence control Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 334 Ext fault 1 eff <2> & p02107 [C] <2> [8060.1] r02138.14 Ext fault 2 eff p03112 [C] <2> [8060.1] r02138.15 Ext fault 3 eff DO: All Objects Function diagram fp_2546_89.vsd - 2546 - - Control word faults/alarms SINAMICS DCP 03.06.2014 v 1.2...
  • Page 335 Bit no. r02139 r02139.00 From fault buffer [8060.6] r02139.03 r02139.05 r02139.06 From alarm buffer [8065.4] r02139.07 r02139.08 r02139.11 r02139.12 DO: All Objects Function diagram fp_2548_89.vsd Siemens Parts - 2548 - - Status word, faults/alarms 1 SINAMICS DCP 03.06.2014 v 1.2...
  • Page 336 Therefore it is not drive can accept the process data. included in the List Manual. DO: DCP_CTRL Function diagram fp_2580_89.vsd - 2580 - - Control word sequence control SINAMICS DCP 08.05.2014 v 1.2...
  • Page 337 Sequence control [2650] r00899.07 r00899.08 <1> r00899.09 r00899.11 <1> Process data from control system is requested. DO: DCP_CTRL Function diagram fp_2585_89.vsd Siemens Parts - 2585 - - Status word sequence control SINAMICS DCP 03.06.2014 v 1.2...
  • Page 338: Sequence Control

    3 Function diagrams 3.6 Sequence control Sequence control Function diagrams 2650 – Sequencer SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 339 Ia controller operating state Op_display OFF 3 = 0 r50000 Fault add info Fault handling r50047 OFF 2 = 0 DO: DCP_CTRL Function diagram fp_2650_89.vsd Siemens Parts - 2650 - - Sequencer SINAMICS DCP 25.04.2016 v 1.2...
  • Page 340: Auxiliary Functions

    3 Function diagrams 3.7 Auxiliary functions Auxiliary functions Function diagrams 3100 – Fixed values 3102 – Function generator SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 341 Fix bit 7 p50428 - 150 % r02902[13] r53230.07 r52008 -150,00 % - 200 % r02902[14] 0,00 % r00000.00 r00000 100,00 % r00001.00 r00001 DO: DCP_CTRL Function diagram fp_3100_89.vsd Siemens Parts - 3100 - - Fixed values SINAMICS DCP 11.11.2015 v 1.2...
  • Page 342 0.00...10000.00 [%] Only value "0" meaningful for FG amplitude FG 2nd amplitude FG offset FG ramp-up offset FG lower limit FG upper limit p4810 DO: CU_DC Function diagram fp_3102_89.vsd - 3102 - - Function generator SINAMICS DCP 03.06.2014 v 1.2...
  • Page 343 3 Function diagrams 3.8 Superimposed closed-loop control Superimposed closed-loop control Function diagrams 6700 – MPP Tracker 6720 – Battery charging characteristic Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 344 MPP tracker [6812.7] (55125.11) MPPT enable s_src p54014 [0...3] [2585.7] (899.11) & [6810.5] (55125.7) MPPT I_s man s_src p54000 [2460.5] (2050[1]) MPPT man/aut s_src p54001 DO: DCP_CTRL Function diagram fp_6700_89.vsd - 6700 - - MPP tracker SINAMICS DCP 25.04.2016 v 1.2...
  • Page 345 Batt enab s_src p54204 charging characteristic (899.11) p54214 (50.00 V) Batt man I_s s_src Batt Hyst p54200 (2050[1]) Batt man/aut s_src p54201 DO: DCP_CTRL Function diagram fp_6720_89.vsd Siemens Parts - 6720 - - Battery charging characteristic SINAMICS DCP 25.04.2016 v 1.2...
  • Page 346 6820 – Main current controller 6825 – Residual current controller 6830 – Pulse width modulation 6835 – Contactor control/precharging 6845 – Fan control 6850 –Actual value acquisition 6855 – Power unit monitoring 6860 – Power unit, properties SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 347 PWM 3 controller Correction current [6830] [6825] controller [6850] [6806] externally measured actual current Current Set- Voltage actual controller value point measurem [6818] DO: DCP_CTRL Function diagram fp_6800_89.vsd Siemens Parts - 6800 - - Overview SINAMICS DCP 25.04.2016 v 1.2...
  • Page 348 OC / OFF3 r00898.02 [2580.8] Setp negative r55075.02 Operation enable r00898.03 [2580.8] stop a limit has been reached [6810.7] [6812.8] [6812.5] [6817.7] [6820.6] [6825.8] DO: DCP_CTRL Function diagram fp_6805_89.vsd - 6805 - - Setpoint processing SINAMICS DCP 25.04.2016 v 1.2...
  • Page 349 Act val I_S1 [%] r55541 [6850.4] Act val I_S2 [%] r55542 [6850.4] Act P [%] [6850.4] r55540 F60058 Par not consistent DO: DCP_CTRL Function diagram fp_6806_89.vsd Siemens Parts - 6806 - - Correction current controller SINAMICS DCP 25.04.2016 v 1.2...
  • Page 350 Dyn overld I_incr power stack p55081 ActVal I_re SumAvg [%] Dyn overload t_sig [%] load cycle r55520 r55091 monitoring [6850.2] F60530 Dyn overload temp too high DO: DCP_CTRL Function diagram fp_6808_89.vsd - 6808 - - Dynamic Overload SINAMICS DCP 25.04.2016 v 1.2...
  • Page 351 PV FlyConn op_mode Allow overvoltage [6850.2] Pos I_lim active r55125.00 I/P_lim I_reac_set [%] I_set reactor [%] r55120 r55071 [6812.1] [6806.7] Neg I_lim active r55125.01 DO: DCP_CTRL Function diagram fp_6810_89.vsd Siemens Parts - 6810 - - Current/power limitation SINAMICS DCP 27.04.2016 v 1.2...
  • Page 352 Upp U_lim S1 rch Low U_lim S2 rch r55125.09 r55125.11 U_lim I_react_set [%] r55150 p55145 (0.500 s) p55145 (0.500 s) U_lim t_recovery U_lim t_recovery DO: DCP_CTRL Function diagram fp_6812_89.vsd - 6812 - - Voltage limiting SINAMICS DCP 25.04.2016 v 1.2...
  • Page 353 U_rated -100% Overvolt detected r50071 Fault value = 3 Lim S1 U dyn s_src p55180 (52002) Lim S1 U_over dyn p55182 DO: DCP_CTRL Function diagram fp_6817_89.vsd Siemens Parts - 6817 - - Voltage limitation, dynamic SINAMICS DCP 25.04.2016 v 1.2...
  • Page 354 [6850.2] Block dc link Act val U inner S2 [%] [6818.7] buffering r55506 [6850.2] U_act dead range p54102 U_ctrl act val sel r54135.01 DO: DCP_CTRL Function diagram fp_6818_89.vsd - 6818 - - Voltage controller SINAMICS DCP 25.04.2016 v 1.2...
  • Page 355 [9350.6] p51800 PU topo pos ActVal I_react PU1 [%] [6850.2] r55511 ActVal I_re SumAvg [%] [6850.2] r55520 Pulses enab [2585.8] r00899.11 DO: DCP_CTRL Function diagram fp_6820_89.vsd Siemens Parts - 6820 - - Main current controller SINAMICS DCP 27.04.2016 v 1.2...
  • Page 356 [6850.2] r55522 I_diff_ctrl_outp [%] r55252[1] ActVal I_re PU1avg [%] r55521 [6850.2] ActVal I_re PU2avg [%] [6850.2] r55522 ActVal I_re PU3avg [%] r55523 [6850.2] DO: DCP_CTRL Function diagram fp_6825_89.vsd - 6825 - - Differential current controller SINAMICS DCP 25.04.2016 v 1.2...
  • Page 357 PWM 3 Control signal jumper 3 Setp negative [6850.5] & [6805.5] r55075.02 Enable direction DC1 --> DC2 Pulses enab Enable [2585.8] r00899.11 DO: DCP_CTRL Function diagram fp_6830_89.vsd Siemens Parts - 6830 - - Pulse width modulation SINAMICS DCP 25.04.2016 v 1.2...
  • Page 358 Boost side 2 [6817.2] Act val U S1 [%] [6850.2] r55501 Boost current [6817.2] Act val U S2 [%] Target voltage [6850.2] r55502 [6817.2] DO: DCP_CTRL Function diagram fp_6835_89.vsd - 6835 - - Contactor control/pre-charging SINAMICS DCP 25.04.2016 v 1.2...
  • Page 359 Fault value = 10 Dev_fan serv life Dev_fan reset h p55471 (30000 h) p55472 Dev_fan h disp r55470 Operating hours counter A60510 Fan end serv life reach DO: DCP_CTRL Function diagram fp_6845_89.vsd Siemens Parts - Fan control SINAMICS DCP 25.04.2016 v 1.2...
  • Page 360 ActVal I_re SumAvg [%] Act val I_S2 [%] Act val I_S2 100 ms r55530 r55520 r55542 r55544 I_act abs val smth [A] r00027 DO: DCP_CTRL Function diagram fp_6850_89.vsd - 6850 - - Actual value acquisition SINAMICS DCP 02.05.2016 v 1.2...
  • Page 361 2 signals "Overtemperature has occurred" r55550 r55550.12 r55550.13 PU F ackn s_src Being ackn p55551 Reset [2548.6] r02139.00 (2139.0) >1 Op_display r50000 o12.0 DO: DCP_CTRL Function diagram fp_6855_89.vsd Siemens Parts - 6855 - - Power unit monitoring SINAMICS DCP 25.04.2016 v 1.2...
  • Page 362 PU property I Serial no. r55601[0...n] r50069[0] PU property P Options r55602 r50068[0] PU property f r55603 U_rated r50071 I_rated r50072 Power unit DO: DCP_CTRL Function diagram fp_6860_89.vsd - 6860 - - Power unit, properties SINAMICS DCP 25.04.2016 v 1.2...
  • Page 363 3.10 Signals and monitoring functions 3.10 Signals and monitoring functions Function diagrams 8030 – Temperature sensor 8048 – Monitoring functions in the device 8054 – Internal diagnostics 8055 – General diagnostics 8056 – Diagnostic memory Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 364 Ext temp high A <5> Ext temp_alarm <3> r53130.0 X177.55 Operating temperature (dependent on type of PTC thermistor) Monitoring (short-circuit/ F60096 wire break) Temp_sensor faulty DO: DCP_CTRL Function diagram fp_8030_89.vsd - 8030 - - Temperature sensor SINAMICS DCP 25.04.2016 v 1.2...
  • Page 365 Alarm mod_temp exceed r52050[3] Mainboard temp Note: The temperature sensors are monitored for wire breaks and F60096 is triggered if necessary. DO: DCP_CTRL Function diagram fp_8048_89.vsd Siemens Parts - 8048 - - Monitoring functions in the device SINAMICS DCP 25.04.2016 v 1.2...
  • Page 366 TMS bootloader im r50060[11] Mainb version r50060[12] Mainb bootloader Trace PU [%] r50060[13] DCC version power stack trace r55399[0...9] r50060[14] FBLOCKS version DO: DCP_CTRL Function diagram fp_8054_89.vsd - 8054 - - Diagnostics, internal SINAMICS DCP 25.04.2016 v 1.2...
  • Page 367 EEPROM write_cmd EEPROM write_protect act orange 2.0 Hz Step down p54992 (0 ) red 2.0 Hz Overvoltage range p54993 (1 ) EEPROM write_prot DO: DCP_CTRL Function diagram fp_8055_89.vsd Siemens Parts - 8055 - - General diagnostics SINAMICS DCP 25.04.2016 v 1.2...
  • Page 368 - Information about change important parameter, software-updates etc. Each time an internal error occurs: Information -> diagnostics file - Detailed information on internal errors DO: DCP_CTRL Function diagram fp_8056_89.vsd - 8056 - - Diagnostic memory SINAMICS DCP 25.04.2016 v 1.2...
  • Page 369 3 Function diagrams 3.11 Faults and alarms 3.11 Faults and alarms Function diagrams 8060 – Fault buffer 8065 – Alarm buffer 8070 – Fault/alarm trigger word (r2129) 8075 – Fault/alarm configuration Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 370 Refer to "Fault buffer - Saving on switching off" in the List Manual. Fault pres The buffer parameters are cyclically updated in the background (refer to status signal in r2139). [5811.1, 5838.1] <3> r02139.03 DO: All Objects Function diagram fp_8060_89.vsd - 8060 - - Fault buffer SINAMICS DCP 03.06.2014 v 1.2...
  • Page 371 <1> The buffer parameters are cyclically updated in the background (refer to status signal in r2139). POWER ON DO: All Objects Function diagram fp_8065_89.vsd Siemens Parts - 8065 - - Alarm buffer SINAMICS DCP 03.06.2014 v 1.2...
  • Page 372 0. Fault/alarm code r02129.00 1. Message present 1. Fault/alarm code r02129.01 15. Message present [15] 15. Fault/alarm code r02129.15 Fault/alarm trigger setting DO: All Objects Function diagram fp_8070_89.vsd - 8070 - - Fault/alarm trigger word (r2129) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 373 With the factory settings, the fault reaction, acknowledge mode, and message type are preassigned in a meaningful way for all faults and alarms. Any changes can only be made in one individual value range, specified by SIEMENS, in each case.
  • Page 374 3 Function diagrams 3.12 Data sets 3.12 Data sets Function diagrams 8560 – Command Data Sets (CDS) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 375 (0) p00809[2] (0) CDS selected r00836 CDS count r00836.0 p00170 (2) CDS select., bit 0 p00810 CDS1 CDS0 CDS effective r00050 r00050.0 DO: DCP_CTRL Function diagram fp_8560_89.VSD Siemens Parts - Command Data Sets (CDS) SINAMICS DCP 03.06.2014 v 1.2...
  • Page 376 3 Function diagrams 3.13 Communication between devices 3.13 Communication between devices Function diagrams 9350 – Paralleling interface SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 377 Par_IF t_monit expired Telegr mon pul r53310.1 Monitoring r51809 Par_IF diag info Telegr mon t_fail p51807 r51810 Par_IF act disp r51811 Par_IF CAN diag DO: DCP_CTRL Function diagram fp_9350_89.VSD Siemens Parts - Parallel connection interface SINAMICS DCP 25.04.2016 v 1.2...
  • Page 378 3 Function diagrams 3.14 Basic Operator Panel 20 (BOP20) 3.14 Basic Operator Panel 20 (BOP20) Function diagrams 9912 – Control word interconnection SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 379 STW BOP.11 STW BOP.12 STW BOP.13 STW BOP.14 STW BOP.15 <1> The BICO interconnection is just an example and may be changed by the user. DO: CU_DCP Function diagram fp_9912_89.vsd Siemens Parts - Control word interconnection SINAMICS DCP 03.06.2014 v 1.2...
  • Page 381 Faults and alarms Content Overview of faults and alarms List of faults and alarms Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 382 • Status signal ZSW1.7 is set. • The alarm is entered in the alarm buffer. How are alarms eliminated? • Alarms acknowledge themselves. If the cause of the alarm is no longer present, they automatically reset themselves. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 383 • Restore factory setting (p0009 = 30 and p0976 = 1). • Download with modified structure (e.g. number of drive objects changed). • Power-up after other parameter values have been loaded (e.g. p0976 = 10). • Upgrade firmware to later version. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 384 You can change the default properties of a fault or alarm by setting parameters. References: SINAMICS DCP operating instructions The "List of faults and alarms" (Page 386) supplies information referred to the properties of a message set as default. If the properties of a specific message are changed, the corresponding information may have to be modified in this list.
  • Page 385 Provides a general description of the methods available for eliminating the cause of the active fault/alarm. WARNING Service and maintenance personnel are responsible for choosing a suitable method for eliminating the cause of faults on a case-for-case basis. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 386 4 Faults and alarms 4.2 List of faults and alarms List of faults and alarms Product: SINAMICS DCP, Version: 4703500, Language: eng Objects: CU_DCP, DCP_CTRL, TM150, TM15DI_DO, TM31 Product: SINAMICS DCDC_V, Version: 1200700, Language: eng Objects: DCP_CTRL F01000 Internal software error...
  • Page 387 - check the selected component number (p7828). - check the DRIVE-CLiQ wiring. - save suitable firmware file for download in the directory "/siemens/sinamics/code/sac/". - use a component with a suitable hardware version - after POWER ON has been carried out again for the DRIVE-CLiQ component, download firmware again.
  • Page 388 All objects Cause: An internal software error has occurred. Fault value (r0949, interpret decimal): Only for internal Siemens troubleshooting. Remedy: - carry out a POWER ON (power off/on) for all components. - upgrade firmware to later version. - contact the Hotline.
  • Page 389 Drive object: All objects Cause: On the memory card, one file in the directory /SIEMENS/SINAMICS/DATA or /ADDON/SINAMICS/DATA has been illegally changed with respect to that supplied from the factory. No changes are permitted in this directory. Alarm value (r2124, interpret decimal): zyx dec: x = Problem, y = Directory, z = File name x = 1: File does not exist.
  • Page 390 All objects Cause: An internal software timeout has occurred. Fault value (r0949, interpret decimal): Only for internal Siemens troubleshooting. Remedy: - carry out a POWER ON (power off/on) for all components. - upgrade firmware to later version. - contact the Hotline.
  • Page 391 The last available backup data record was loaded. The parameterization must be checked. It is recommended that the parameterization is downloaded again. dd, cc, bb: Only for internal Siemens troubleshooting. See also: p0971 (Save drive object parameters), p0977 (Save all parameters) Remedy: - Download the project again with the commissioning software.
  • Page 392 = 011 --> data save started with p0977 = 11 b = 012 --> data save started with p0977 = 12 d, c: Only for internal Siemens troubleshooting. Remedy: - check the file attribute of the files (PSxxxyyy.***, CAxxxyyy.***, CCxxxyyy.***) and, if required, change from "read only"...
  • Page 393 123: Write access only in the commissioning state, device configuration (device: p0009 = 1). 124: Write access only in the commissioning state, device download (device: p0009 = 29). 125: Write access only in the commissioning state, device parameter reset (device: p0009 = 30). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 394 SERVO or VECTOR ). 21: Error when accepting the download parameters. 22: Software-internal download error. Additional values: only for internal Siemens troubleshooting. Remedy: - use the current version of the commissioning software. - modify the offline project and carry out a new download (e.g. compare the number of drive objects, motor, encoder, power unit in the offline project and at the drive).
  • Page 395 Also see r9406 up to r9408. Alarm value (r2124, interpret hexadecimal): Only for internal Siemens troubleshooting. Remedy: - Check the parameters displayed in r9406 up to r9408, and correct these if required.
  • Page 396 4 Faults and alarms 4.2 List of faults and alarms Fault value (r0949, interpret hexadecimal): Method ID. Note: Only for internal Siemens troubleshooting. Remedy: Contact the Hotline. F01056 CU: Internal error (clock cycle of parameter group already assigned differently) Drive object:...
  • Page 397 4 Faults and alarms 4.2 List of faults and alarms Fault value (r0949, interpret hexadecimal): Method ID. Note: Only for internal Siemens troubleshooting. Remedy: Contact the Hotline. F01063 CU: Internal error (PDM) Drive object: DCP_CTRL, TM150 Cause: An internal software error has occurred.
  • Page 398 Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets, OA applications, blocks, etc). Fault value (r0949, interpret decimal): Only for internal Siemens troubleshooting. Remedy: - change the configuration on this Control Unit (e.g. fewer drives, function modules, data sets, OA applications, blocks, etc).
  • Page 399 A data save in the non-volatile memory was not able to be successfully carried out. - non-volatile memory is defective. - insufficient space in the non-volatile memory. Fault value (r0949, interpret decimal): Only for internal Siemens troubleshooting. Remedy: - try to save again. - replace the memory card or Control Unit.
  • Page 400 Too many time slices occupied by OA (e.g. DCC). 999: Too many time slices occupied by the basic system. Too many different sampling times may have been set. Additional values: Only for internal Siemens troubleshooting. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 401 Drive object: All objects Cause: Insufficient processing time is available for the existing topology. Fault value (r0949, interpret hexadecimal): Only for internal Siemens troubleshooting. Remedy: - reduce the number of drives. - increase the sampling times. F01221 CU: Bas clk cyc too low...
  • Page 402 All objects Cause: Error when reading the read-only data of the EEPROM in the Control Unit. Fault value (r0949, interpret decimal): Only for internal Siemens troubleshooting. Remedy: - carry out a POWER ON. - replace the Control Unit. SINAMICS DCP...
  • Page 403 Cause: Error when reading the read-write data of the EEPROM in the Control Unit. Alarm value (r2124, interpret decimal): Only for internal Siemens troubleshooting. Remedy: For alarm value r2124 < 256, the following applies: - carry out a POWER ON.
  • Page 404 Drive object: CU_DCP, TM150, TM15DI_DO, TM31 Cause: For the active drive object involved, at least one activated component is missing. Note: All other active and operational drive objects can be in the "RUN" state. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 405 - p0978 must include all of the drive object numbers (p0101). - it is not permissible for a drive object number to be repeated. - by entering a 0, the drive objects with PZD are separated from those without PZD. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 406 - by entering a 0, the drive objects with PZD are separated from those without PZD. - only 2 partial lists are permitted. After the second 0, all values must be 0. - dummy drive object numbers (255) are only permitted in the first partial list. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 407 - bb = 01 hex = 1 dec: The Order No. [MLFB] of the power unit that was replaced includes a space retainer. The space retainer (*) must be replaced by a correct character. - cccc = preliminary component number of the component with illegal EEPROM data. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 408 Sign-of-life errors can be expected. The conditions of operation with a current controller sampling time of 31.25 µs have not been maintained. 5yy: Internal buffer overflow for net data of a DRIVE-CLiQ connection. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 409 The device target topology (p0099) does not correspond to the device actual topology (r0098). The fault only occurs if the topology was commissioned using the automatic internal device mechanism and not using the commissioning software. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 410 4 Faults and alarms 4.2 List of faults and alarms Fault value (r0949, interpret decimal): Only for internal Siemens troubleshooting. See also: r0098 (Actual device topology), p0099 (Device target topology) Remedy: One of the following counter-measures can be selected if no faults have occurred in the topology detection itself: If commissioning is still not completed: - carry out a self-commissioning routine (starting from p0009 = 1).
  • Page 411 Cause: The DRIVE-CLiQ performance is not sufficient at one line in order to identify an inserted component. Fault value (r0949, interpret hexadecimal): Only for internal Siemens troubleshooting. Remedy: - carry out a POWER ON (power off/on). - Distribute components across several DRIVE-CLiQ lines.
  • Page 412 X501 of the TM54F module via DRIVE-CLiQ socket X500. 11: On the DRIVE-CLiQ Hub Module, only Sensor Modules Cabinet (SMC) and Sensor Modules External (SME) may be connected to X501 through X505. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 413 When detecting the actual topology, a component with a defective EEPROM was detected. Fault value (r0949, interpret hexadecimal): bbbbaaaa hex: bbbb = reserved aaaa = preliminary component number of the defective components Remedy: Output the fault value and remove the defected component. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 414 Alarm value (r2124, interpret hexadecimal): ddccbbaa hex: dd = connection number (%4) cc = component number (%3) bb = component class (% 2) aa = component number of the incorrectly inserted component (% 1) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 415 - adapt the project/parameterization in the commissioning software (correct the target topology). - automatically remove the topology error (p9904). Note: Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics capability (e.g. setpoint/actual value comparison). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 416 The topology comparison has found a component in the actual topology which is not specified in the target topology. Alarm value (r2124, interpret hexadecimal): ddccbbaa hex: dd = component class (% 2) cc = connection number (%4) bb = component class of the additional component (%1) aa = component number (%3) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 417 The serial number is different. Alarm value (r2124, interpret hexadecimal): ddccbbaa hex: dd = reserved cc = number of differences (%3) bb = component class (% 2) aa = component number (%1) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 418 A01481 (N) Topology: power unit not inserted Drive object: CU_DCP, TM150, TM15DI_DO, TM31 Cause: The topology comparison has detected a power unit that is missing in the actual topology with respect to the target topology. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 419 = connection number (%4) cc = component number (%3) bb = component class (% 2) aa = component number of the component that has not been inserted (% 1) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 420 Component class and connection number are described in F01375. Remedy: Adapting topologies: - insert the components involved at the right connection (correct the actual topology). - adapt the project/parameterization in the commissioning software (correct the target topology). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 421 - check DRIVE-CLiQ cables for interruption and contact problems. - check that the component is working properly. Note: Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics capability (e.g. setpoint/actual value comparison). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 422 Number of BICO interconnections found to inactive drive objects. Remedy: - set all open BICO interconnections centrally to the factory setting with p9495 = 2. - make the non-operational drive object active/operational again (re-insert or activate components). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 423 This means that the factor p2002/p2001 is calculated between the BICO output and the BICO input. p2002: contains the reference value for current p2001: contains the reference value for voltage Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 424 - check the DRIVE-CLiQ cables at the Control Unit. - remove any short-circuit for motors with DRIVE-CLiQ. - carry out a POWER ON. For fault value = 11: - check the electrical cabinet design and cable routing for EMC compliance SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 425 PROFIsafe parameter error (e.g. F_dest). 502: PROFIsafe telegram does not match. 503: PROFIsafe connection is rejected as long as there is no isochronous connection (p8969). Additional values: Only for internal Siemens troubleshooting. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 426 The reception of setpoints from the fieldbus interface (onboard, PROFIBUS/PROFINET/USS) has been interrupted. - bus connection interrupted. - controller switched off. - controller set into the STOP state. See also: p2040 (Fieldbus interface monitoring time), p2047 (PROFIBUS additional monitoring time) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 427 Alarm value (r2124, interpret decimal): Number of the drive object with different current controller sampling time. Remedy: Set current controller sampling time to identical values (p0115[0]). Note: PB: PROFIBUS PN: PROFINET See also: p0115 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 428 Remedy: - check the master application and bus configuration. - check the consistency between the clock cycle input when configuring the slave and clock cycle setting at the master. Note: PB: PROFIBUS PN: PROFINET SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 429 All objects Cause: Synchronization of the internal clock cycle to the global control telegram has failed. The internal clock cycle exhibits an unexpected shift. Remedy: Only for internal Siemens troubleshooting. Note: PB: PROFIBUS PN: PROFINET F01951 CU SYNC: Synchronization application clock cycle missing...
  • Page 430 After the drive system is powered up, the synchronization between the basic clock cycle, DRIVE-CLiQ clock cycle and application clock cycle was started but was not completed within the selected time tolerance. Alarm value (r2124, interpret decimal): Only for internal Siemens troubleshooting. Remedy: Carry out a POWER ON (power off/on) for all components.
  • Page 431 For all of the drives specified for connection, set the speed setpoints to zero. Note: The alarm is reset as follows: - remove the cause of this alarm. - restart the function generator. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 432 Remedy: Check and adapt the value for the period. Note: The alarm is reset as follows: - remove the cause of this alarm. - restart the function generator. See also: p4821 (Function generator period) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 433 See also: p4823 (Function generator bandwidth), p4830 (Function generator time slice cycle) Remedy: Check the value for the bandwidth and adapt accordingly. Note: The alarm is reset as follows: - remove the cause of this alarm. - restart the function generator. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 434 Enter the clock cycle of an existing time slice with a cycle time >= 2 ms for up to 4 recording channels or >= 4 ms from 5 recording channels per trace. The existing time slices can be read out via p7901. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 435 Cause: The selected pretrigger time must be shorter than the trace time. See also: p4721 (Trace recording time), p4722 (Trace trigger delay) Remedy: Check the pretrigger time setting and change if necessary. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 436 It is not possible to save the measurement results of a multiple trace on the memory card (trace recorder 1). A multiple trace is not started or is canceled. Alarm value (r2124, interpret decimal): 1: Memory card cannot be accessed. - card is not inserted or is blocked by a mounted USB drive. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 437 Alarm value (r2124, interpret hexadecimal): The interface version in the DCB user library is not compatible to the DCC standard library that has been loaded. Only for internal Siemens troubleshooting. Remedy: - carry out a POWER ON (power off/on) for all components.
  • Page 438 When initializing the Terminal Modules, the terminals of the Control Unit or the Terminal Board 30, an internal software error has occurred. Fault value (r0949, interpret decimal): yxxx dex y = Only for internal Siemens troubleshooting xxx = component number (p0151) Remedy: - power down/power up the power supply for the Control Unit.
  • Page 439 - power down/power up the power supply for the Control Unit. - check the DRIVE-CLiQ wiring. Note: If it reoccurs, then replace the module. In principle, operation could continue. The analog channel involved possibly does not achieve the specified accuracy. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 440 32: A device was not able to be found for the determined drive object number. 34: A trigger parameter was recursively called. 35: It is not permissible to write to the parameter via macro. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 441 The command is either influenced via binector input p0840 (current CDS) or control word bit 0 via the master control. Remedy: Switch the signal via binector input p0840 (current CDS) or control word bit 0 via the master control to 0. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 442 The fault value includes the drive data set number of p0187, p0188 and p0189. The fault value is increased by 100 * encoder number (e.g. for p0189: Fault value 3xx with xx = data set number). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 443 The condition for "External alarm 1" is satisfied. Note: The "External alarm 1" is initiated by a 1/0 edge via binector input p2112. See also: p2112 (External alarm 1) Remedy: Eliminate the causes of this alarm. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 444 Terminal Board 30 detects an incorrect internal power supply voltage. Fault value (r0949, interpret decimal): 0: Error when testing the monitoring circuit. 1: Fault in normal operation. Remedy: - replace Terminal Board 30. - replace Control Unit. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 445 All objects Cause: The cyclic actual and/or setpoint values were not transferred within the specified times. Alarm value (r2124, interpret decimal): Only for internal Siemens troubleshooting. Remedy: Check the parameterizing telegram (Ti, To, Tdp, etc.). F08510 (A) PN/COMM BOARD: Send configuration data invalid...
  • Page 446 500: Illegal PROFIsafe configuration for the interface set in p8815[1]. 501: PROFIsafe parameter error (e.g. F_dest). 503: PROFIsafe connection is rejected as long as there is no isochronous connection (p8969). Additional values: Only for internal Siemens troubleshooting. Remedy: Check the receive configuration data. Re alarm value = 1, 2: - Check the list of the drive objects with process data exchange (p0978).
  • Page 447 An adequate license was not able to be determined as there is no licensing data available on the memory card. An adequate license was not able to be determined as there is a checksum error in the license key. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 448 Re fault value = 2, 3, 12, 13: - contact the responsible OEM. - Deactivate copy protection (p7765) and acknowledge the fault (p3981). - Deactivate know-how protection (p7766 ... p7768) and acknowledge the fault (p3981). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 449 Cause: A short-circuit at the motor holding brake terminals has been detected. Fault value (r0949, interpret decimal): Only for internal Siemens troubleshooting. Remedy: - check the motor holding brake for a short-circuit. - check the connection and cable for the motor holding brake.
  • Page 450 - infeed: Correct connection of the line reactor. - check the power cable connections. - check the power cables for short-circuit or ground fault. - check the length of the power cables. - replace power unit. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 451 Telegram is shorter than specified in the length byte or in the receive list. 3 (= 03 hex): Telegram is longer than specified in the length byte or in the receive list. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 452 A DRIVE-CLiQ communications error has occurred from the Voltage Sensing Module involved (VSM) to the Control Unit. The nodes do not send and receive in synchronism. Fault cause: 26 (= 1A hex): Sign-of-life bit in the receive telegram not set and the receive telegram is too early. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 453 - check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...). - check the electrical cabinet design and cable routing for EMC compliance - if required, use another DRIVE-CLiQ socket (p9904). - replace the component involved. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 454 This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal Module. Fault value (r0949, interpret decimal): Temperature actual value at the time of initiation [0.1 °C]. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 455 For the temperature evaluation via the Terminal Module (TM), at least one of the following conditions to initiate this fault is fulfilled: - alarm threshold has been exceeded longer than that set in the timer (p4102[6], p4103[3]). - fault threshold exceeded (p4102[7]). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 456 Temperature actual value at the time of initiation [0.1 °C]. Remedy: - allow the temperature sensor to cool down to below p4102[4] - hysteresis (5 K); for TM150, can be set using p4118[2]. See also: p4102 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 457 - enter the encoder pulse number in the permissible range (p0408). - if necessary, replace TM41 SAC with TM41 DAC. Note: TM41 SAC: order no. = 6SL3055-0AA00-3PA0 TM41 DAC: order no. = 6SL3055-0AA00-3PA1 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 458 Temperature actual value at the time of initiation [0.1 °C]. Remedy: - allow the temperature sensor to cool down to below p4102[9] - hysteresis (p4118[4]). - if required, set the fault response to NONE (p2100, p2101). See also: p4102 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 459 - if r4101[7] > 1650 ohms, the temperature r4105[7] = 250 °C - if r4101[7] <= 1650 ohms, the temperature r4105[7] = -50 °C The temperature actual value is displayed via connector output r4105[7] and can be interconnected. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 460 Temperature actual value at the time of initiation [0.1 °C]. Remedy: - allow the temperature sensor to cool down to below p4102[19] - hysteresis (p4118[9]). - if required, set the fault response to NONE (p2100, p2101). See also: p4102 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 461 Alarm value (r2124, interpret decimal): Temperature actual value at the time of initiation [0.1 °C]. Remedy: Allow the temperature sensor to cool down to below p4102[8] - hysteresis (p4118[4]). See also: p4102 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 462 - if r4101[8] <= 1650 ohms, the temperature r4105[8] = -50 °C Alarm value (r2124, interpret decimal): Temperature actual value at the time of initiation [0.1 °C]. Remedy: Allow the temperature sensor to cool down to below p4102[16] - hysteresis (p4118[8]). See also: p4102 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 463 The individual information is coded as follows in the message value (r0949/r2124): 0000yyxx hex: yy = component number, xx = error cause Remedy: - check the DRIVE-CLiQ connection. - replace the component involved. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 464 A SYNC telegram is expected - but the received telegram is not a SYNC telegram. 8 (= 08 hex): No SYNC telegram is expected - but the received telegram is one. 9 (= 09 hex): The error bit in the receive telegram is set. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 465 Send error: The telegram buffer memory contains an error. Note regarding the message value: The individual information is coded as follows in the message value (r0949/r2124): 0000yyxx hex: yy = component number, xx = error cause Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 466 6 (= 06 hex): The address of the power unit in the telegram and in the receive list do not match. 9 (= 09 hex): The error bit in the receive telegram is set. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 467 The cyclic telegram has not been received. 34 (= 22 hex): Timeout in the telegram receive list. 64 (= 40 hex): Timeout in the telegram send list. 98 (= 62 hex): Error at the transition to cyclic operation. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 468 Synchronization error during alternating cyclic data transfer. Note regarding the message value: The individual information is coded as follows in the message value (r0949/r2124): 0000yyxx hex: yy = component number, xx = error cause Remedy: Carry out a POWER ON. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 469 10: TM15 24 V power supply for DI/DO 16 ... 23 (X522) missing. 20: TM41 24 V power supply for DI/DO 0 ... 3 missing. Remedy: Check the terminals for the power supply voltage (L1+, L2+, L3+, M or +24 V_1 for TM41). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 470 PTC thermistor: R < 20 Ohm, KTY84: R < 50 Ohm (TM150: R < 180 Ohm), PT100: R < 60 Ohm, PT1000: R < 603 Remedy: - make sure that the sensor is connected correctly. - replace the sensor. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 471 KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm 2: Measured resistance too low. PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 472 KTY84: R > 2170 Ohm, PT100: R > 194 Ohm, PT1000: R > 1944 Ohm 2: Measured resistance too low. PTC thermistor: R < 20 Ohm, KTY84: R < 180 Ohm, PT100: R < 60 Ohm, PT1000: R < 603 Ohm SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 473 The telegram is longer than that specified in the length byte or in the receive list and the receive telegram is too early. 20 (= 14 hex): The length of the receive telegram does not match the receive list and the receive telegram is too early. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 474 The individual information is coded as follows in the message value (r0949/r2124): 0000yyxx hex: yy = component number, xx = error cause Remedy: - check the supply voltage of the component involved. - carry out a POWER ON. - replace the component involved. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 475 One cause can be, e.g. that a DRIVE-CLiQ cable or DRIVE-CLiQ component has been replaced. Fault value (r0949, interpret decimal): Component number. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 476 An alarm has occurred at the drive object at the DRIVE-CLiQ socket X100. Alarm value (r2124, interpret decimal): First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 477 The individual information is coded as follows in the message value (r0949/r2124): 0000yyxx hex: yy = component number, xx = error cause Remedy: - carry out a POWER ON (power off/on). - replace the component involved. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 478 A DRIVE-CLiQ communications error has occurred from the Control Unit to the controller extension involved. The nodes do not send and receive in synchronism. Fault cause: 33 (= 21 hex): The cyclic telegram has not been received. 34 (= 22 hex): Timeout in the telegram receive list. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 479 Note regarding the message value: The individual information is coded as follows in the message value (r0949/r2124): 0000yyxx hex: yy = component number, xx = error cause Remedy: Carry out a POWER ON (power off/on). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 480 0000yyxx hex: yy = component number, xx = error cause Remedy: - carry out a POWER ON (power off/on). - check the electrical cabinet design and cable routing for EMC compliance - check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 481 CX32 DRIVE-CLiQ (CU): Component fault Drive object: TM150, TM15DI_DO, TM31 Cause: Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded. Fault cause: 32 (= 20 hex): Error in the telegram header. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 482 Alarm value (r2124, interpret decimal): Telegram word used twice See also: p8871 (SINAMICS Link send telegram word PZD) Remedy: CBE20 SINAMICS Link: Correct the parameter assignment. See also: p8871 (SINAMICS Link send telegram word PZD) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 483 Drive object: All objects Cause: CBE20: PROFINET Name of Station is invalid. Remedy: CBE20: Correct the name of the station (p8940) and activate (p8945 = 2). See also: p8940 (CBE2x Name of Station) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 484 - check the threshold for triggering the fault (p50492). - check the temperature at the location where the external temperature sensor is installed - and if necessary, reduce. See also: p50492 (Temperature monitoring external fault threshold) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 485 See also: p50710 (CUD analog input 1 type) Remedy: - check the wiring of the input terminals (X177.27/28) (cable break, contacts, etc). - check the parameter assignment for analog input 1 (p50710). Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 486 21: Analog input 3 (X177.1/2), voltage input, incorrect offset value 22: Analog input 3 (X177.1/2), voltage input, +10 V incorrect value 23: Analog input 3 (X177.1/2), voltage input, -10 V incorrect value 24: Analog input 3 (X177.1/2), voltage input, reference value incorrect SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 487 2: The TMS320 cannot be released (memory is password-protected). 3: Incompatible version of the bootloader software. 4: Incompatible version of the application software. 5: Error when deleting the TMS320 flash memory. 6: Error when programming the TMS320 flash memory. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 488 2nd character of the serial number r50047[30]: 30th character of the serial number Note for fault value = 2, 5, 7: r50047[1]: 1st character of the MLFB r50047[2]: 2nd character of the MLFB r50047[30]: 30th character of the MLFB SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 489 Temperature power unit 1 (in °C) r50047[2]: Temperature power unit 2 (in °C) r50047[3]: Temperature power supply module (in °C) r50047[4]: Temperature mainboard module (in °C) r50047[5]: Temperature CUD module (in °C) Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 490 Air intake temperature (in °C) r50047[7]: Reference voltage +10 V (in Volt) r50047[8]: Reference voltage -10 V (in Volt) r50047[9]: Temperature power unit 3 (in °C) Remedy: Check the current load of the power supply P5 (X179.1). SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 491 Power supply unit fault Drive object: DCP_CTRL Cause: The power supply unit in the SINAMICS DCP has a fault condition. Note: r50047[1]: Temperature power unit 1 (in °C) r50047[2]: Temperature power unit 2 (in °C) r50047[3]: Temperature power supply module (in °C) r50047[4]: Temperature mainboard module (in °C)
  • Page 492 Fault value (r0949, interpret decimal): 1: The TMS320 does not respond. 2: The TMS320 cannot be released (memory is password-protected). 3: Incompatible version of the bootloader software. 4: Incompatible version of the application software. SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 493 Air intake temperature (in °C) r50047[7]: Reference voltage +10 V (in Volt) r50047[8]: Reference voltage -10 V (in Volt) r50047[9]: Temperature power unit 3 (in °C) Remedy: Check the ambient temperature and reduce if necessary. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 494 Overtemperature monitoring has responded in the power unit. Fault value (r0949, interpret hexadecimal): Value in r55550. Remedy: - check the ambient temperature and reduce if necessary. - check the function of the device fan. See also: r55550 (Power unit monitoring status) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 495 Fault module temperature exceeded Drive object: DCP_CTRL Cause: The temperature has exceeded 95 °C. Fault value (r0949, interpret decimal): 3: Power supply module temperature too high. 4: Mainboard module temperature too high. Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 496 Cause: An I2C bus communication error has occurred on the mainboard. Fault value (r0949, interpret decimal): I2C error code (only for internal Siemens error diagnostics). Remedy: - carry out a POWER ON (power off/on). - if necessary, send the device to an authorized repair shop.
  • Page 497 Appendix Content ASCII table (characters that can be displayed) List of abbreviations Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 498 Slash, slant Digit 0 Digit 1 Digit 2 Digit 3 Digit 4 Digit 5 Digit 6 Digit 7 Digit 8 Digit 9 Colon Semicolon < Less than Equals > Greater than Question mark Commercial At SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 499 Capital letter X Capital letter Y Capital letter Z Opening bracket Backslash Closing bracket Circumflex Underline ‘ Opening single quotation mark Small letter a Small letter b Small letter c Small letter d Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 500 Small letter r Small letter s Small letter t Small letter u Small letter v Small letter w Small letter x Small letter y Small letter z Opening brace Vertical line Closing brace Tilde SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 501 Communication Board CAN Communication Board CAN Communication Board Ethernet Communication Board PROFINET (Ethernet) Compact Disk Compact disk Command Data Set Command data set CF card CompactFlash card CompactFlash card Connector Input Connector input Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 502 Drive Component Link with IQ Dynamic Servo Control Dynamic Servo Control Digital Time Clock Timer EASC External Armature Short-Circuit External armature short-circuit Encoder data set Encoder data set EEPROM Electrically Erasable Programmable Electrically Erasable Programmable Read-Only Memory Read-Only-Memory SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 503 0 V (also referred to as Generic Station Description Generic Station Description: Describes the features of a PROFIBUS slave Gate Supply Voltage Gate supply voltage GUID Globally Unique Identifier Globally unique identifier Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 504 Kinetische Pufferung Kinetic buffering Proportional gain Special temperature sensor Symbol for inductance Light Emitting Diode Light-emitting diode Linear motor Linear motor Lageregler Position controller Least Significant Bit Least significant bit Line-Side Converter Line-side converter SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 505 Version of the SINAMICS firmware from which the OA-application can be used OASP Open Architecture Support Package Expands the STARTER commissioning tool by the corresponding OA-application Operating Condition Operating condition Original Equipment Manufacturer Original equipment manufacturer Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 506 Ramp-Function Generator Ramp-function generator RJ45 Registered Jack 45 Term for an 8-pin socket system for data transmission with shielded or non-shielded multi- wire copper cables Rückkühlanlage Cooling unit Renewable Line Module Renewable Line Module SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 507 SINAMICS Sensor Module Integrated Single Motor Module Single Motor Module Sicherer Software-Nocken Safe software cam Safe Operating Stop Safe operating stop Service Pack Service pack Safe Position Safe position Setpoint Channel Setpoint channel Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 508 Voltage Protection Module Volt peak to peak Volt peak-to-peak Voltage Sensing Module Voltage Sensing Module Wiedereinschaltautomatik Automatic restart Werkzeugmaschine Machine tool Extensible Markup Language Extensible Markup Language (standard language for Web publishing and document management) SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 509 A Appendix A.2 List of abbreviations Abbreviation Source of abbreviation Meaning Zwischenkreis DC link Zero Mark Zero mark Zustandswort Status word Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 510 A Appendix A.2 List of abbreviations SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 511 IF1 status words, free interconnection, 332 6855 2546 Power unit monitoring, 361 Control word, faults/alarms, 334 6860 2548 Power unit, properties, 362 Status word, faults/alarms 1, 335 8030 2580 Temperature sensor, 364 Control word, sequence control, 336 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 512 Alarms, 382 Axxxx, 384 Faults, 382 Display parameters, 15 Basic Operator Panel (BOP), 378 DO, Drive Object, 16 Battery charging characteristic, 345 Drive object, 16 BI, Binector Input, 16 Dynamic overload, 350 BICO technology, 317 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 513 Setpoint processing, 348 MPP Tracker, 344 Voltage controller, 354 Function generator, 342 Voltage limitation, 352 Function module, 16 Voltage limitation, dynamic, 353 Fxxxx, 384 Function diagrams, communication between devices Paralleling interface, 377 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 514 Objective of this manual, 5 Explanation, Part 1, 314 Explanation, Part 2, 315 Explanation, Part 3, 316 T - Ready state, 17 Target group for this manual, 5 Temperature sensor, 364 Trace, power unit:, 366 SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 515 Index Version List of all parameters, 22 U - Operation state, 17 List of faults and alarms, 386 Voltage controller, 354 Values (parameter), 19 Voltage limitation, 352 Voltage limitation, dynamic, 353 Siemens Parts SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 516 Index SINAMICS DCP List Manual (LH21), 05/2016...
  • Page 517 Siemens Parts...
  • Page 518 Siemens AG Subject to change Industry Sector © Siemens AG 2014 - 2016 Drive Technologies Large Drives P.O. Box 4743 90025 NUREMBERG GERMANY www.siemens.com/automation...