8.
Set the module parameter of the master station "To Use or Not to Use the Safety Communication Setting" to "Use".
[Module Parameter] [Application Settings] [Safety Communication Setting] [To Use of Not to Use the Safety
Communication Setting]
9.
Select "Detailed Setting" of the module parameter of the master station "Safety Communication Setting" and the "Safety
Communication Setting" window is displayed.
[Module Parameter] [Application Settings] [Safety Communication Setting] [Safety Communication Setting]
10.
Select "Local Network" in "Communication Destination" and the "Select the target module for the Safety Communication
Setting" window is displayed. Select the target safety remote I/O module and click the [Add] button.
8 PARAMETER SETTINGS
8.2 Module Parameter Setting
8
69