Mitsubishi Electric MELSEC iQ-R Series Reference Manual page 37

Inter-module synchronization function
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Displayed items
Item
Use Inter-module Synchronization Function in System
Select Inter-module
Detailed Setting
Synchronization Target
Module
Fixed Scan Interval
0.05ms Unit Setting
Setting of Inter-module
Synchronization
Fixed Scan Interval Setting
(Not set in 0.05ms unit)
Fixed Scan Interval Setting
(Set in 0.05ms unit)
Inter-module
Synchronous Master Setting
Synchronization Master
of CC IE Field
*3
Setting
Mounting Slot No.
*2 The inter-module synchronization cycle setting range differs according to the module. (Manual for each module)
*3 When a project is created with the remote head module, the setting is not available.
*4 This item is not displayed for the R00CPU, R01CPU, and R02CPU.
*5 This item cannot be specified for the Safety CPU.
Description
Sets whether to use the inter-module
synchronization function.
Sets the module to be synchronized.
Sets whether to set the inter-module synchronization
cycle in 0.05ms units.
When not setting in 0.05ms units, select the inter-
module synchronization cycle from the options.
When setting in 0.05ms units, set the inter-module
*2
synchronization cycle.
When "Set" is selected, the CC-Link IE Field
Network module on the local station becomes the
inter-module synchronous master. When "Not Set" is
selected, the CPU module (CPU module on the
extreme left for the multiple CPU system
configuration) or remote head module becomes the
inter-module synchronous master. (Page 9
Inter-module synchronous master)
Set the mounting slot No. for the CC-Link IE Field
Network module on the local station that becomes
the inter-module synchronous master.
Setting range
• Not Use
• Use
• Do Not Synchronize
• Synchronize
• Not Set
• Set
*4*5
• 0.222ms
*2
*4*5
• 0.444ms
*5
• 0.888ms
• 1.777ms
• 3.555ms
• 7.111ms
• R00CPU, R01CPU,
R02CPU: 0.50 to
10.00ms
• Safety CPU: 1.00 to
10.00ms
• CPU modules other
than the above: 0.10
to 10.00ms
• Not Set
• Set
0 to 11
6 PARAMETER SETTINGS
6.1 Inter-Module Synchronization Setting
Default
Not Use
Do Not
Synchronize
Set
• Safety CPU:
7.111ms
• CPU
modules
other than
the above:
0.888ms
• Safety CPU:
5.00ms
• CPU
modules
6
other than
the above:
0.50ms
Not Set
0
35

Advertisement

Table of Contents
loading