Siemens 6DR55 Series Manual page 125

Electropneumatic positioner for linear and part--turn actuators
Table of Contents

Advertisement

YEND2
RANGE
x
ok
RUN 1/
x
ERROR
d___U
x
SEt
x
MIDDL
x
UP >
x
90_95
x
x
U--d>
U nn.n
x
D-->U
x
SIPART PS2 PA Manual
A5E00127926--05
Meaning/Cause
only during manual initialization
second end position can be moved
to
only during manual initialization
End position or measurement span
are outwith the permitted
measurement range
only during manual initialization
permitted measurement range for
end positions reached
Fault in RUN 1
no movement e.g. no compressed air
Bar display of the zero point
Zero point is outwith the tolerance
range
Friction clutch misaligned; "P 50.0"
no displayed when arm horizontal
"UP" -- tolerance range exceeded or
inactive zone of potentiometer ent-
ered
Only applies to part--turn drives:
Actuator travel is not within range 90
to 95%
Measurement span "Up--Down" is
insufficient
Display the positioning time "Up"
Actions
Move to second end position using
S
the "+" or "--" key
Press "operating mode" key to
S
acknowledge
Using "+" and "--" keys move to the
S
other end position and press "opera--
ting mode" key to acknowledge,
or
Adjust friction clutch until "ok" is
S
displayed and press "operating
mode" key to acknowledge
or
Interrupt initialization by pressing the
S
"operating mode" key, switch to P
manual mode and correct the
actuator travel and position sensing
Press "operating mode" key to
S
acknowledge, the remaining steps
("RUN1" to "FINSH") will run through
automatically
Ensure compressed air is sufficient
S
Open any choke(s)
S
Re--start initialization
S
With friction clutch set to "P 4.0" to
S
"P 9.9" ( >0< )
Continue using the "+" or "--" key
S
For thrust drives, use the "+" and "--"
S
keys to bring the arm to the correct
angle on the spindle
Press "operating mode" key briefly to
S
acknowledge (initialization will
resume)
Increase effective arm length with lin-
S
ear actuators or set transmission ra-
tio selector to 90 degrees
Press "operating mode" key briefly to
S
acknowledge
Re--start initialization
S
Use the "+" and "--" keys to move into
S
the range of 90 to 95%
Press "operating mode" key briefly to
S
acknowledge
Reduce effective arm length for thrust
S
drives or set transmission ratio selec-
tor to 33 degrees
Press "operating mode" key briefly to
S
acknowledge
Re--start initialization
S
Wait, or
S
To change the positioning time
S
interrupt initialization with the "--" key,
or
Activate the leakage test with the "+"
S
key
Operation