Cerberus Division Introduction Introduction The GW-23 interfaces both the peripheral control units and a virtual digital I/O sub- system to a structured network such as: • X.25 via X.28 asynchronous RS-232 PAD • X.25 via ISDN channel D and asynchronous RS-232 terminal adapter •...
This manual is intended as a guide for planning, installation and service personnel of Cerberus danger management systems which use GW-23 device. All necessary information to install a GW-23 gateway are listed in this manual. Related publications The following documents could be useful in dealing with GW-23 gateway and under-...
Cerberus Division Product description The connection board The connection board (CD96812) has two connectors to insert the CPU and I/O board in. On the board there are two DB9 D connectors for the two serial ports (Com 3 and 4). COM 1 and 2 are accesible through screw connectors - only the TX, RX and GND signals are available.
Cerberus Division Product description Power supervision The power supervision board is reporting the following information on a set of LEDs: Red ⊗ ⊗ Tamper: normally OFF, it indicates tamper condition Yellow ⊗ Low Battery: normally OFF, it is ON if voltage drops below 10.8V± 0,5V Yellow ⊗...
I/O signals Cables (RS 232 signals) shielded cable, with twisted pairs min. section 0.50 mm2 max. distance between the GW-23 and the devices up to 15 mt, longer distance may be possible depending on specific conditions Configuration...