5 ACTUAL VALUES
The 489 Event Recorder stores generator and system information each time an event occurs. The description of the event
is stored and a time and date stamp is also added to the record. This allows reconstruction of the sequence of events for
troubleshooting. Events include: all trips, any alarm optionally (except Service Alarm, and 489 Not Inserted Alarm, which
always records as events), loss of control power, application of control power, thermal resets, simulation, serial communica-
tion starts/stops and general input control functions optionally.
The highest event number is the most recent event, and lowest event number is the oldest event. Each new event bumps
the other event records down until the 40th event is reached. The 40th event record is lost when the next event occurs. This
information can be cleared using
signifies that no event has occurred since the last clearing of the event record. The event record will not update if a digital
input programmed as Test Input is shorted.
GE Power Management
ANALOG INPUT 2
ESCAPE
E65535: 0.0 Units
MESSAGE
ANALOG INPUT 3
ESCAPE
E65535: 0.0 Units
MESSAGE
ANALOG INPUT 4
ESCAPE
E65535: 0.0 Units
MESSAGE
S1 489 SETUP \ CLEAR DATA \ CLEAR EVENT RECORD
489 Generator Management Relay
5.6 A5 EVENT RECORDER
Range: –50000 to 50000
Seen only if the Analog Input is in use.
Range: –50000 to 50000
Seen only if the Analog Input is in use.
Range: –50000 to 50000
Seen only if the Analog Input is in use.
setpoint. An event number of 65535
5
5-23