The Overview Of The Vf-As3 Command Parameters - Toshiba TOSVERT VF-AS3 Instruction Manual

Embedded ethernet function
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

2.5. The overview of the VF-AS3 command parameters

[FA36: Communication command1 from embedded ethernet]
bit
Function
0
Preset speed switching 1
1
Preset speed switching 2
2
Preset speed switching 3
3
Preset speed switching 4
4
V/f switching 1 (*2)
5
PID control OFF
6
Acc/Dec switching 1 (*3)
7
DC braking
8
Jog run
9
Forward/Reverse
10 Run/Stop
11 Coast stop (*4)
12 Emergency off
13 Fault reset
14 Frequency priority
15 Command priority
(*1): When set "12 [Sr0]" to FMOd, preset speed operation frequency 0 is selected.
(*2): The V/f switching ORs with Bit 10 of [FA38].
(*3): The Acc/Dec switching ORs with Bit 8 of [FA38]
(*4): When set "2 [Embedded Ethernet]" to CMOd, the Bit 11 (Coast stop) of [FA36] is ON at startup.
If you want to start the operation by [FA36], please turn OFF the Bit 11.
0
0000: Preset speed operation OFF
(*1)
0001-1111: Setting of preset speed
operation frequencies (1-15)
V/f 1
V/f 2
PID control
PID control
permitted
prohibited
AD mode 1
AD mode 2
Forced DC
OFF
braking
OFF
Jog run
Forward run
Reverse run
Stop
Run
Standby
Cost stop
OFF
Emergency off
OFF
Reset
OFF
Enabled
OFF
Enabled
19
1
Preset speed operation is disabled
or preset speed operation
frequencies (1-15) are set by
specifying bits for preset speed
operation frequencies 1-4.
V/f 1: Pt = setting value, vL, vLv, vb, tHrA
V/f 2: Pt = "0", F170, F171, F172, F182
-
AD mode 1: ACC, DEC
AD mode 2: F500, F501
-
-
-
-
-
Always enable, [E] trip
Trip reset
Enabled regardless of the setting of
FMOD
Enabled regardless of the setting of
CMOD
E6582125
Note