Function Code 06: Store Single Setpoint - GE MOTOR MANAGEMENT RELAY 469 Instruction Manual

Table of Contents

Advertisement

6.2 SUPPORTED MODBUS FUNCTIONS
Modbus Implementation:
469 Implementation:
This command allows the master to store a single setpoint into the memory of an 469. The slave response to
this function code is to echo the entire master transmission.
MESSAGE FORMAT AND EXAMPLE
Request slave 11 to store the value 01F4 in Setpoint address 1180. After the transmission in this example is
complete, setpoints address 1180 will contain the value 01F4.
MASTER TRANSMISSION:
SLAVE ADDRESS
FUNCTION CODE
DATA STARTING ADDRESS
DATA
CRC
SLAVE RESPONSE:
SLAVE ADDRESS
FUNCTION CODE
DATA STARTING ADDRESS
DATA
CRC
6
6-10

6.2.5 FUNCTION CODE 06: STORE SINGLE SETPOINT

Preset Single Register
Store Single Setpoint
BYTES
EXAMPLE / DESCRIPTION
1
0B
1
06
2
11 80
2
01 F4
2
8D A3
BYTES
EXAMPLE / DESCRIPTION
1
0B
1
06
2
11 80
2
01 F4
2
8D A3
469 Motor Management Relay
6 COMMUNICATIONS
message for slave 11
store single setpoint
setpoint address 1180
data for address 1180
CRC calculated by the master
response message from slave 11
store single setpoint
setpoint address 1180
data for address 1180
CRC calculated by the slave