Mitsubishi Electric QJ71MT91 User Manual page 168

Modbus/tcp interface module
Table of Contents

Advertisement

9
PROGRAMMING
9
9 - 2
(3) Timing charts for basic parameter setting
(a) When setting is completed normally
Parameter creation
ON
OFF
Module READY
X0
Basic parameter
OFF
Y1
setting request
Basic parameter
OFF
X1
setting, normally
completed
Basic parameter
OFF
X2
setting, error
completed
Basic parameter
OFF
X3
setting existence
Basic parameter
0C10
H
error code storage
area
(b) When setting is completed with an error
Parameter creation
ON
OFF
Module READY
X0
Basic parameter
OFF
Y1
setting request
Basic parameter
OFF
setting, normally
X1
completed
Basic parameter
OFF
X2
setting, error
completed
Basic parameter
OFF
X3
setting existence
Basic parameter
0C10
H
error code storage
area
Basic parameter
setting, normally
completed
Basic parameter
creation
ON
Error code
clear
Basic parameter
setting, error
completed
Basic parameter
creation (error)
ON
ON
Error code
storage
MELSEC-Q
ON
ON
Executed by QJ71MT91
Executed by sequence program
Basic parameter
setting, normally
completed
Basic parameter
correction
ON
ON
ON
Error code
clear
Executed by QJ71MT91
Executed by sequence program
9 - 2