For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
Series pefy ceiling concealed air conditioner (31 pages)
Summary of Contents for Mitsubishi Electric CITY MULTI PEFY-P06NMAU-E3
Page 1
Air-Conditioners INDOOR UNIT PEFY-P06,08,12,15,18,24,27,30,36,48,54NMAU-E3 INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. MANUEL D’INSTALLATION Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
Page 2
[Fig. 3.2.1] [Fig. 3.2.2] (Unit: mm [in]) (Viewed from the direction of the arrow A) 700 [27- 9/16 [17- 475 [18- 100~200 ]~[7- 15/16 50~150 [2]~[5- 450 [17- 15/16 [Fig. 3.2.3] [Fig. 3.2.4] (Viewed from the direction of the arrow B) 50 [2] 700 [27- 9/16...
Page 3
[Fig. 4.1.1] A Center of gravity [Fig. 5.1.1] [Fig. 5.1.2] [Fig. 5.2.1] C Nuts (field supply) D Washers (square) (accessory) A Unit body A Indoor unit’s bottom surface E M10 hanging bolt (field supply) B Lifting machine [Fig. 6.2.1] (Unit: mm [in]) A Refrigerant pipe (liquid pipe) B Refrigerant pipe (gas pipe) C Drain pipe (O.D.
Page 4
[Fig. 7.1.1] [Fig. 7.1.3] A Cut here B Remove brazed cap A Thermal insulation [Fig. 7.1.2] B Pull out insulation C Wrap with damp cloth D Return to original position A Cool by a wet cloth E Ensure that there is no gap here F Wrap with insulating tape [Fig.
Page 5
[Fig. 7.3.1] [Fig. 7.3.2] A Insert pump's end 2 to 4 cm [13/16 to 1-5/8 in]. B Remove the water supply port. C About 2500 cc D Water E Filling port <Indoor controller board> F Screw [Fig. 8.0.2] [Fig. 8.0.1] <A>...
Page 6
[Fig. 9.2.4] [Fig. 9.2.3] A Non-polarized DC10~13V B TB15 DC24~30V C Remote Controller D TB5 (A, B) [Fig. 9.3.1] [Fig. 9.3.2] A Screw holding cover (1pc) C Terminal box B Cover D Knockout hole E Remove [Fig. 9.3.3] [Fig. 9.3.4] F Use PG bushing to keep the weight of the cable and external force from being N Terminal block for power source applied to the power supply terminal connector.
- If the pressure switch, thermal switch, or other protection device is shorted - Inadequate connection and fastening may generate heat and cause a fire. and operated forcibly, or parts other than those specified by Mitsubishi Electric • Prepare for typhoons and other strong winds and earthquakes and install are used, fire or explosion may result.
1.4. Before getting installed (moved) - elec- • Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized copper as specified in the JIS H3300 “Copper and copper alloy seamless trical work pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, Caution: shaving particles, oils, moisture, or any other contaminant.
• If the unit is run for long hours when the air above the ceiling is at high tem- (2) When a space of less than 300 mm [11-13/16 in] is available below the unit perature/high humidity (due point above 26°C [79°F]), due condensation may between the unit and the ceiling (At least 20 mm [13/16 in] of space should be be produced in the indoor unit.
- It may also be in violation of applicable laws. 1. Insert the drain hose (accessory) into the drain port (insertion margin: 32 mm - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for [1-1/4 in]). malfunctions or accidents resulting from the use of the wrong type of refrigerant.
5. Attach the insulating material, and fix it with the band (accessory) to insulate 7.3. Confirming drain discharge the drain port. Make sure that the drain-up mechanism operates normally for discharge [Fig. 7.2.2] (P.4) and that there is no water leakage from the connections. A Indoor unit •...
9. Electrical wiring Precautions on electrical wiring 5. Never connect the power cable to leads for the transmission cables. Otherwise the cables would be broken. Warning: 6. Be sure to connect control cables to the indoor unit, remote controller, and the Electrical work should be done by qualified electrical engineers in accord- outdoor unit.
*3 Current sensitivity is calculated using the following formula. G1 = (V2 × Quantity of Type1) + (V2 × Quantity of Type2) + (V2 × Quantity of Type3) + (V2 × Quantity of Others) + (V3 × Wire length [km]) Current sensitivity Wire thickness 30 or less...
9.5. Selecting the external static pressure As the factory setting is for use under an external static pressure of 0.20 in. WG (50 9.7. Sensing room temperature with the Pa), no switch operation is needed when using under the standard condition. built-in sensor in a remote controller External static pressure Switch operation...
Page 15
This product is designed and intended for use in the residential, commercial and light-industrial environment. Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN KD79K438H02...
Page 16
Air-Conditioners INDOOR UNIT PEFY-P06,08,12,15,18,24,27,30,36,48,54NMAU-E3 OPERATION MANUAL For safe and correct use, please read this operation manual thoroughly before operating the air-conditioner unit. MANUEL D’UTILISATION Pour une utilisation correcte sans risques, veuillez lire le manuel d’utilisation en entier avant de vous servir du climatiseur.
Page 17
Remote controller-Button Touche Commande à distance TEMP. ON/OFF MENU ON/OFF FILTER BACK MONITOR/SET CHECK TEST CLOCK OPERATION CLEAR 5 6 8 1 [Set Temperature] Button 1 Touche [Réglage de la température] 2 [Timer menu] Button 3 [mode] Button 2 Touche [Timer menu] 3 Touche [Mode] [moniTor/SeT] Button [Back] Button...
Page 18
Remote controller-Display Affichage Commande à distance TIME MON TUE WED THU FRI TIMER AFTER AFTER ERROR CODE FUNCTION ˚F ˚C FILTER ˚F ˚C WEEKLY SIMPLE ONLY 1Hr. AUTO OFF TEMP. ON/OFF A current time/Timer time A Heure réelle/heure de la minuterie B Centralized control indicator B Témoin de commande à...
Page 19
[Fig.A] 1: In case of rear inlet 2: In case of bottom inlet : Air Flow A: Filter En cas d’entrée arrière En cas d’entrée sur le dessous Flux d’air Filtre...
• Use only accessories authorized by Mitsubishi Electric and ask your dealer or an authorized company to install them. If accessories are installed 6) Grounding improperly, water leakage, electric shock or fire may result.
• If the remote controller displays an error indication, the air conditioner Warning: does not run, or there is any abnormality, stop operation and contact your • Do not splash water over the unit and do not touch the unit with wet dealer.
3.3. Room temperature adjustment For fan Press the 3 [Mode (BACK)] Button and bring up the “ Fan” display. To change room temperature • The fan operation functions to circulate the air in the room. Press the 1 [Set Temperature] Button and set the room temperature of your •...
5. Caring for the machine How to clean Always have filter maintenance performed by a service person. Before care-taking, turn the power supply OFF. • Clear dust away lightly or clean it up with a vacuum cleaner. In the case of Caution: severe staining, wash the filter in lukewarm water mixed with dissolved neutral detergent or water, and then rinse off the detergent completely.
7. Installation, transferring works, and checking • Never connect the grounding wire to a gas pipe, water pipe, arrester, or Regarding place for installation telephone grounding wire. For details, consult with your dealer. Consult with your dealer for details on installation and transferring the installation. •...
Page 26
This product is designed and intended for use in the residential, commercial and light-industrial environment. Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN KD79K437H01...