Basic Installation and Operation Guide
 
 

Auxiliary Output Relay Settings

Functions F060 through F062 provide the ability to program the functions of each of the 3 Output
Auxiliary Relays. Factory default programming is provided which covers a wide variety of applications,
but any of these relays can be changed as per the following chart.
Notes:
Check relay wiring before changing programming to avoid unintended consequences.
Relays programmed to some protection features will not operate if function is disabled
elsewhere.
 
Setting
Relay Operation Description
1
Run / Stop (Changes on Start, resets on Stop)
2
At-Speed / Stop
3
At-Speed / End of Decel
4
Start / End of Decel
5
Short SCR Trip
6
Phase Loss Trip
7
Shunt Trip
8
OL (Motor Thermal Overload) Trip
9
OT (Starter Thermal Over Temperature) Trip
10
Short Circuit Trip
11
Current Imbalance Trip
12
Over Current (Shear-Pin) Trip
13
Under Current Trip
Table 7: Aux. Relay Settings
29 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
Setting
Relay Operation Description
14
Ground Fault Trip
15
Phase Rotation Trip
16
Any Trip (#5 - #15)
17
Any Trip, (#5-#15) flashing output*
18
Coast Down Time Lockout
19
Starts Per Hour Lockout
20
Time Between Starts Lockout
21
Any Lockout (#18-#20)
22
Run Timer (F030) Engaged
23
Run / Stop with On-delay from F063
24
At-Speed / Stop with On-delay from F063
25
At-Speed / End of Decel w/ On-delay from F063
26
Start / End of Decel with On-delay from F063
27
Power Loss (nCP No Control Power) Trip
*Note: Flash rate for Setting #17 is ½ second On and Off
 