7.2.2 Points of Replacement

The points for replacing the conventional models FP0A04V or FP0A04I with the new model
FP0RDA4 as an alternative are described below.
 Hardware
• Turn off the mode switch No.1 and select "12-bit FP0A04 compatibility mode". The voltage
output range is "-10 to 10 V DC", and the current output range is "4 to 20 mA DC".
• The new model FP0RDA4 has two terminal blocks for the voltage output and current output.
They are connected according to the application.
• In the case of FP0RDA4, select whether to output signals to the voltage output or current
output for each channel with the mode switch. The factory default setting is the voltage
output for all channels. Change the mode switch setting as necessary.
Item
Appearance
Terminal block
Mode switch
 Software
User programs created for the conventional models FP0A04V and FP0A04I can be used as
they are.
REFERENCE
For details of the setting method of the mode switch, refer to "2.2.2 Setting
of Mode Switch".
FP0A04V compatibility
The terminal block on the voltage output
side is used.
The 12-bit FP0A04 compatibility mode is
selected.
The voltage output is selected for all
channels.
7.2 Analog Output Unit
FP0A04I compatibility
The terminal block on the current output
side is used.
The 12-bit FP0A04 compatibility mode is
selected.
The current output is selected for all
channels.
7-5