Analog I/O Unit; Compatibility With Conventional Models - Panasonic FP0R Series User Manual

Analog i/o unit
Hide thumbs Also See for FP0R Series:
Table of Contents

Advertisement

Compatibility with Conventional Models

7.3 Analog I/O Unit

7.3.1 Compatibility with Conventional Models
 Specification Comparison Chart
Item
Appearance
Resolution and Operation mode
Number of channels
-10 to 10 V DC
-5 to 5 V DC
Analog input
voltage range
0 to 10 V DC
0 to 5 V DC
Analog input
0 to 20 mA
current range
-10 to 10 V DC
-5 to 5 V DC
Analog output
voltage range
0 to 10 V DC
0 to 5 V DC
0 to 20 mA
Analog output
current range
4 to 20 mA
Conversion speed
Voltage
Overall
precision
Current
Analog input averaging function
External power
supply
Power supply
Control unit
(24V DC)
consumption current
increment
(Note 1): The resolution and operation mode is switched by the mode switch.
7-6
FP0-A21
12-bit (1/4000)
Input 2 ch/Output 1 ch
Available
Not available
Not available
Available
Available
Available
Not available
Not available
Not available
Available
Not available
1 ms/channel
±0.6%F.S. or less (at 25°C)
±1%F.S. or less (at 0 to 55°C)
Not available
100 mA or less
20 mA or less
FP0R-A21 / FP0R-A42
12-bit (1/4000)
14-bit (1/16000) (Note 1)
A21:Input 2 ch/Output 1 ch
A42:Input 4 ch/Output 2 ch
Available
Available (Note 2)
Available (Note 2)
Available
Available
Available
Available (Note 3)
Available (Note 3)
Available (Note 3)
Available
Available (Note 3)
Input 2 ms / All channels
Output 500 μs / All channels
±0.2%F.S. or less (at 25°C)
±0.4%F.S. or less (at 0 to 55°C)
±0.3%F.S. or less (at 25°C)
±0.6%F.S. or less (at 0 to 55°C)
Available (Moving average 10
times/ No. of averaging times: 64
times or 128 times) (Note 4)
A21:80 mA or less
A42:120 mA or less
10 mA or less

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp0rad4Afp0rad8Afp0ra21Afp0ra42Afp0rda4