Instruction Bulletin / Boletín de instrucciones / Directives d'utilisation / 34EOHU364-5-6JRS / A, 1SCC340038M1401
EOHU364/5/6JK/RK/S/SS
NEMA 12, 3R, 4X / 200 A, 400 A, 600 A

Advertisement

Table of Contents
loading

Summary of Contents for ABB EOHU Series

  • Page 1 Instruction Bulletin / Boletín de instrucciones / Directives d‘utilisation / 34EOHU364-5-6JRS / A, 1SCC340038M1401 EOHU364/5/6JK/RK/S/SS NEMA 12, 3R, 4X / 200 A, 400 A, 600 A...
  • Page 2 Retain for future use. / Conservar para uso futuro. / À conserver pour usage ultérieur.
  • Page 3 EOHU364/5/6JK/RK/S/SS NEMA 12, 3R, 4X / 200 A, 400 A, 600 A EOHU Series Heavy Duty Non-fusible Safety Switches EOHU Serie Interruptores de seguridad de servicio pesado EOHU Série Interrupteurs de sécurité pour service intensif French version is available at later date.
  • Page 5: Table Of Contents

    1/19 Cable outlets / knockouts for NEMA 12 and 3R types 1/20 Accessories (optional) 1/21 Ordering information 1/21 Maintenance 1/22 Replacement parts, ordering information 1/22 Installation and maintenance log 1/23 Instruction Bulletin EOHU364/5/6JK/RK/S/SS, 1SCC340038M1401 / A | EOHU Series 1/1...
  • Page 6: General Safety Instructions

    General safety instructions Read these safety instructions carefully before using this product! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH – Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E or CSA Z462. – This equipment must only be installed and serviced by qualified electrical personnel.
  • Page 7: Receiving, Handling And Storage

    ABB sales office. and protection from dirt and moisture. Storing the unit outdoors could cause harmful condensation inside the switch enclosure.
  • Page 8: Applications

    Applications The EOHU series non-fusible safety switches are side-operated, 3 pole, 600V, available in UL environmental ratings TYPE 12 and TYPE 3R housed in steel sheet enclosures and TYPE 4X housed in stainless steel sheet enclosures. Heavy duty non-fusible safety switches offer the ability to Catalog numbers: manually open and close a circuit.
  • Page 9: Product Overview

    Product overview EOHU364JK/_RK/_S/_SS, EOHU365JK/_RK/_S/_SS, EOHU366JK/_RK/_S/_SS Door latches, provision for padlocking Line side terminal lugs Handle Load side terminal lugs Knockouts in catalog numbers EOHU364JK/_RK, EOHU365JK/_RK and Ground bus (2 lugs) EOHU366JK/_RK (TYPE12 and 3R), blank in catalog numbers 10. Operating mechanism, inside place for auxiliary contacts (optional) EOHU364S/_SS, EOHU365S/_SS and EOHU366S/_SS (TYPE 4X) 11.
  • Page 10: Ratings

    Ratings Heavy duty non-fusible safety switches Non-fusible safety switch catalog number EOHU364_ EOHU365_ EOHU366_ AMPS General purpose current rating Max. horse power rating Three phase 240 V 480 V 600 V Max. motor FLA current Three phase 240 V 480 V 600 V Short circuit rating Class R, J or T fuses...
  • Page 11: Cabling

    Cabling Heavy duty non-fusible safety switches Cabling / Non-fusible safety switches Cable entry/exit locations: Top entry-bottom exit. WARNING Cable entry/exit through top/bottom endwalls maximize the cable bending area. All cable entry/exit must be in accordance with the National Electrical Code and all other local codes. Use To avoid hazard of electric shock, turn off and lock out all power sources before installing or performing maintenance on this equipment.
  • Page 12: Neutral Bus And Auxiliary Contacts

    Cabling Neutral bus and auxiliary contacts Cabling / Neutral bus (optional) Use 5/32 hex key/wrench. See chapter Installation / Neutral assembly (optional). Non-fusible safety switch catalog number EOHU364_ EOHU365_ EOHU366_ AMPS Suitable neutral bus, catalog number EOHXSN4 EOHXSN56 EOHXSN56 Neutral bus / terminal lugs Terminal lug OZXA-400 OZXA-800...
  • Page 13: Installation

    Installation Opening the enclosure Opening of the enclosure Operate switch to the OFF-position and open the door latches CAUTION according to the picture. Open the enclosure. HAZARD OF INJURY OR EQUIPMENT DAMAGE Do not in any circumstances bend or twist the locking hook fixed on the door.
  • Page 14: Knockouts

    It is not allowed to do any other extra holes except In catalog numbers EOHU364S/_SS, EOHU365S/_SS and cable entry/exit to the enclosure. No responsibility is assumed by ABB EOHU366S/_SS (TYPE 4X) the top and bottom of the enclosure for any consequences arising out of the installing of cable entry/exit or if are blank for own holes.
  • Page 15: Mounting

    Installation Mounting 200 A: 6× 400 A, 600 A: 10× Mounting the safety switch on the wall or other supporting structure CAUTION Mount the safety switch using 3/16” screws (for 200 A: 3 pcs, for 400 A /600 A: 5 pcs) and 5/16” screws (for 200 A: 3 pcs, for 400 A /600 A: 5 pcs).
  • Page 16: Wiring

    Installation Wiring Wiring Safety Connect the power wires to the switch terminals and connect switch Line and load side size [A] terminal lugs Ground bus the ground wire to the ground terminal block inside the Wire range [kcmil / mm enclosure.
  • Page 17: Neutral Assembly (Optional)

    Installation Neutral assembly (optional) Neutral assembly (optional) Install the neutral link to the bottom plate of the safety switch DANGER to the existing threaded holes according to the picture. See chapter Cabling. HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH See general safety instructions on page 1/2 before proceeding.
  • Page 18: Auxiliary Contact (Optional)

    Installation Auxiliary contact (optional) Auxiliary contacts OA1G10 and OA3G01 (optional) Install the auxiliary contacts to the safety switch mechanism DANGER according to the pictures. In the picture 3 the mounting example is for 200A and 400 A safety switches. In 600 A safety switches, please, leave the mechanism cover off, when the maximum amount HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH See general safety instructions on page 1/2 before proceeding.
  • Page 19: Operation

    Operation Operating Closing the enclosure and operation to the ON-position Close the enclosure door and the latches according to the CAUTION picture. Operate switch to the ON-position. NOTE: The door must be closed and fastened securely with HAZARD OF INJURY OR EQUIPMENT DAMAGE Do not in any circumstances bend or twist the locking hook fixed on the door latches before the switch is operated.
  • Page 20: Operating Mechanism

    Operation Operating mechanism Door interlock mechanism A door interlock prevents opening the enclosure door if the DANGER switch is in ON-position. It also works in conjunction with the mechanism interlock, which prevents the operation to ON-position if the enclosure door is open. HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH See general safety instructions on page 1/2 before proceeding.
  • Page 21 Operation Operating mechanism Defeating the door interlock mechanism Note: Only qualifi ed personnel should perform this procedure. The door of the safety switch cannot be opened when the switch is in the ON-position. This can be defeated to allow authorized personnel access for inspection. DANGER CAUTION DANGER...
  • Page 22: Padlocking Handle And Door Latches

    Operation Padlocking handle and door latches Ø 0.20 - 0.39 in / 5 - 10 mm Ø 0.20 - 0.24 in / 5 - 6 mm Padlocking handle Padlocking door latches Operating handle can be padlocked in the OFF-position with up Door latches can be padlocked by one padlock each to prevent to three padlocks.
  • Page 23: Dimension Drawings

    Dimension drawings EOHU364JK/_RK/_S/_SS, EOHU365JK/_RK/_S/_SS, EOHU366JK/_RK/_S/_SS / NEMA 12, 3R, 4X / 200 A, 400 A, 600 A EOHU364/5/6JK/RK EOHU364/5/6S/SS Size Catalog number [in] [mm] [in] [mm] [in] [mm] [in] [mm] [in] [mm] EOHU364JK, _RK, _S, _SS 26.77 17.01 19.09 7.36 10.16 EOHU365JK, _RK, _S, _SS 42.72...
  • Page 24: Cable Outlets / Knockouts For Nema 12 And 3R Types

    Dimension drawings Cable outlets / knockouts for NEMA 12 and 3R types For catalog numbers EOHU364JK, _RK For catalog numbers EOHU365JK, _RK For catalog numbers EOHU366JK, _RK 1/20 Dimension drawings | Instruction Bulletin EOHU364/5/6JK/RK/S/SS, 1SCC340038M1401 / A...
  • Page 25: Accessories (Optional)

    Accessories (optional) Ordering information Neutral assembly Mounting screws included as standard. Units/catalog number = 1 piece. Weight/ unit Suitable for safety switch Includes terminal lug Catalog number [kg] Solid, mountable separately to the mounting plate EOHU364_ OZXA-400 EOHXSN4 EOHU365_, 6_ OZXA-800 EOHXSN56 EOHXSN4...
  • Page 26: Maintenance

    Mounting screws included as standard. Units/catalog number = 3 pieces. EOHU364_ OZXA-400/3 EOHU365_, 6_ OZXA-800/3 Door assembly Includes a door, ABB logo stripe, labels and hinges with screws as standard. Units/catalog number = 1 piece. EOHU364JK EOHNDJ4 EOHU365JK EOHNDJ5 EOHU366JK...
  • Page 27: Installation And Maintenance Log

    Maintenance Installation and maintenance log Maintenance The switch is properly lubricated at the factory. No lubrication DANGER is required. However, careful cleaning is required after wire connections and mounting of additional accessories HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH and replacement parts.
  • Page 29 Serie EOHU Interruptores de seguridad de servicio pesado Instrucciones de seguridad Réception, manutention et entreposage Aplicaciones Visión general del producto EOHU364JK/_RK/_S/_SS, EOHU365JK/_RK/_S/_SS, EOHU366JK/_RK/_S/_SS Datos nominales Interruptores de seguridad de servicio pesado Cableado Interruptores de seguridad de servicio pesado Barra del neutro Instalación Apertura del gabinete Aberturas tipo knockout...
  • Page 30: Instrucciones De Seguridad

    Instrucciones de seguridad Lea con detenimiento estas instrucciones antes de utilizar este producto PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO – Utilice equipo de protección personal (EPP) apropiado y siga las prácticas de seguridad eléctrica establecidas por su compañía.
  • Page 31 ABB. protection contre la saleté et de l’humidité. L’entreposage de l’appareil en plein air pourrait provoquer de la condensation Ne retirez pas l’emballage d’expédition jusqu’à...
  • Page 32 Aplicaciones La serie EOHU de interruptores de seguridad de servicio pesado son tripolares y tienen una tensión nominal de 600 V. Los gabinetes están disponibles en tipos 12 y 3R (acero) y tipo 4X (acero inoxidable), de acuerdo a la norma UL. La serie EOH de interruptores de seguridad de servicio pesado Número de catálogo: tiene la capacidad de conectar y desconectar circuitos.
  • Page 33 Visión general del producto EOHU364JK/_RK/_S/_SS, EOHU365JK/_RK/_S/_SS, EOHU366JK/_RK/_S/_SS Cerradura de la puerta Barraje de conexión a tierra (2 zapatas) Palanca 10. Mecanismo de operación, espacio interior para montaje de contactos Abertura para cable tipo knockout en números de catálogo auxiliaries (opcional) EOHU364JK/_RK, EOHU365JK/_RK y EOHU366JK/_RK (tipos 12 y 3R), 11.
  • Page 34 Datos nominales Interruptores de seguridad de servicio pesado Tipo de interruptores de seguridad EOHU364_ EOHU365_ EOHU366_ AMPS Corriente nominal Potencia maxima (HP) Trifásica 240 V 480 V 600 V Máxima corriente FLA del motor Trifásica 240 V 480 V 600 V Especifi...
  • Page 35 Cableado Interruptores de seguridad de servicio pesado Cableado / Interruptores de seguridad de servicio pesado Ubicación de cables de entrada/salida: Entrada en la parte ADVERTENCIA superior y salida en la parte inferior, lo cual maximiza el área de cableado. Las entradas y salidas de cables deben de seguir la norma NEC (National Electrical Code) y todas las normas Para evitar daños por descarga eléctrica, desenergice y desconecte el interruptor antes de llevar a cabo la instalación o mantenimiento.
  • Page 36 Cableado Barra del neutro Cableado/Barra del neutro Para interruptores de 200 A, utilice una llave hexagonal 3/8. Para interruptores de 400 y 600 A, utilice una llave hexagonal 1/2. Vea la figura en el capítulo Instalación - Ensamble de la terminal de neutro (opcional).
  • Page 37 Instalación Apertura del gabinete Apertura del gabinete Desenergice el interruptor (posición OFF) y abra la cerradura de PRECAUCIÓN la puerta de acuerdo a la imagen. Abra el gabinete. PELIGRO DE LESIONES O DAÑO AL EQUIPO No doble o tuerza el gancho para bloquear el mecanismo, bajo ninguna circunstancia.
  • Page 38 No está permitido hacer otros RK, EOHU365JK/_RK y EOHU366JK/_RK (Tipos 12 y 3R). Los agujeros que no sean la entrada o salida de cable del gabinete. ABB no gabinetes EOHU364S _SS, EOHU365S/_SS y EOHU366S/_SS se responsabiliza por consecuencias de la instalación de los cables y...
  • Page 39 Instalación Montaje 200 A: 6× 400 A, 600 A: 10× Montaje del interruptor de seguridad en la pared u otras estructuras de soporte PRECAUCIÓN Monte el interruptor de seguridad con 3 (200 A)/ 5 (400 A y 600 A) tornillos 3/16” y 3 (200 A)/ 5 (400 A y 600 A) tornillos 5/16”. Atención: utilice el agujero bocallave para colgar el gabinete PELIGRO DE LESIONES O DAÑO AL EQUIPO No doble o tuerza el gancho para bloquear el mecanismo, bajo ninguna...
  • Page 40 Instalación Conexión de cableado Conexión de cableado el soporte adecuado. Doble el cable cuidadosamente para evitar Conecte los cables a las terminales del interruptor. Conecte deformación en las terminales. Deformación en las terminales el cable a tierra al bloque de conexión localizado dentro del tiene un impacto negativo en el funcionamiento del interruptor.
  • Page 41 Instalación Ensamble de la terminal de neutro (opcional) Ensamble de la terminal de neutro EOHXSN13 (opcional) Instale la terminal de neutro de acuerdo a los agujeros roscados PELIGRO existentes en la placa de montaje. Vea el capítulo Cableado. Rango de calibres: PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO EOHXSN4: #2 - 600 kcmil / 35 - 300 mm...
  • Page 42 Instalación Contactos auxiliaries (opcional) Contactos auxiliaries OA1G10 y OA3G01 (opcional) Instale los contactos auxiliaries dentro del mecanismo del PELIGRO interruptor de acuerdo a la imagen. Vea el capítulo Cableado. La imagen 3 muestra un ejemplo de como montar contactos auxiliares en interruptores de 200 A y 400 A. En el caso de los PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO interruptores de 600 A y la cantidad máxima de contactos sea...
  • Page 43 Operación Operación del interruptor Cerradura del gabinete y operación hacia la posición ON Cierre la puerta del gabinete y las cerraduras de acuerdo a la PRECAUCIÓN imagen. Opere el interruptor hacia la posición ON. ATENCIÓN: La puerta debe de cerrarse firmemente con la PELIGRO DE LESIONES O DAÑO AL EQUIPO No doble o tuerza el gancho para bloquear el mecanismo, bajo ninguna cerradura antes de operar el interruptor...
  • Page 44 Operación Mecanismo de operación Mecanismo de bloqueo de puerta El bloqueo de seguridad de la puerta previene la abertura de PELIGRO la puerta del gabinete cuando el interruptor está en la posición ON. En conjunto con el bloqueo del mecanismo, evita que el interruptor sea operado hacia la posición ON cuando la puerta PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO...
  • Page 45 Operación Mecanismo de operación Vencimiento del mecanismo de bloqueo Atención: Solamente el personal especializado puede llevar a La puerta del gabinete no puede ser abierta cuando el cabo esta acción. interruptor esté en la posición ON. Éste puede ser vencido por el personal autorizado para inspección PELIGRO PRECAUCIÓN...
  • Page 46 Operación Enclavamiento de la palanca y cerradura Ø 0.20 - 0.39 in / 5 - 10 mm Ø 0.20 - 0.24 in / 5 - 6 mm Enclavamiento de la palanca Enclavamiento de la cerradura La palanca es candadeable en la posición OFF. Se pueden La cerradura se puede enclavar usando un candado para utilizar hasta tres candados.
  • Page 47 Dimensiones generales EOHU364JK/_RK/_S/_SS, EOHU365JK/_RK/_S/_SS, EOHU366JK/_RK/_S/_SS / NEMA 12, 3R, 4X / 200 A, 400 A, 600 A EOHU364/5/6JK/RK EOHU364/5/6S/SS Tamaño Número de catálogo [in] [mm] [in] [mm] [in] [mm] [in] [mm] [in] [mm] EOHU364JK, _RK, _S, _SS 26.77 17.01 19.09 7.36 10.16 EOHU365JK, _RK, _S, _SS...
  • Page 48 Dimensiones generales Salidas de cable / abertura tipo knockout NEMA 12 y 3R Para números de catálogo EOHU364JK, _RK Para números de catálogo EOHU365JK, _RK Para números de catálogo EOHU366JK, _RK 2/20 Dimensiones generales | Boletín de instrucciones EOHU364/5/6JK/RK/S/SS, 1SCC340038M1401 / A...
  • Page 49 Accesorios (opcional) Información de pedido Terminal de neutro Tornillos incluidos de manera estándar. Unidades/No. de catálogo = 1 pieza. Adecuado Peso/ para unidad interruptores Incluye Zapata tipo No. de catálogo [kg] Sólido, para fi jar en placa de montaje EOHU364_ OZXA-400 EOHXSN4 EOHU365_, 6_...
  • Page 50 OT400/600U30EOHR Tornillos incluidos como estándar. Unidades/No. de catálogo = 3 piezas EOHU364_ OZXA-400/3 EOHU365_, 6_ OZXA-800/3 Ensamble de puerta Incluye calcomania con logotipo ABB, etiquetas, bisagras y tornillos como estándar. Unidades/No. de catálogo=1 pieza. EOHU364JK EOHNDJ4 EOHU365JK EOHNDJ5 EOHU366JK EOHNDJ6...
  • Page 51 Mantenimiento Registro de Instalación y Mantenimiento Mantenimiento El interruptor es lubricado apropiadamente en la fábrica, por PELIGRO lo cual no se necesita lubricación adicional. Sin embargo, es necesario limpiarlo cuidadosamente después de la instalación de los cables, accesorios, fusibles y piezas de repuesto. Se PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO recomienda limpiar e inspeccionar el cableado una vez al año.
  • Page 52 Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed Low Voltage Control Products by ABB for any consequences arising out of the use of this material. 16250 W Glendale Drive New Berlin, WI 53151 Todo el equipo eléctrico debe de ser instalado, operado y...