7. Initial settings

Initial settings need to be made for each AE-200 on the AE-200's LCD, Initial Setting Tool, or the Web browser.
The table below explains how to make initial settings on the AE-200's LCD. Details about the initial settings are
covered in the AE-200 Instruction Book (Initial Settings).
Note
To monitor and operate the air conditioning units on the web browser (Integrated Centralized Control Web), settings need to
be configured on the Initial Setting Tool.
Note
The software versions of all AE-200/AE-50/EW-50 in the same system need to be the same. It is recommended to have
all of them at the latest version.
Note
When using an Advanced Touch Controller AT-50A/AT-50B as a sub controller, set the "Clock setting signal" setting to
"OFF" on the AT-50A/AT-50B. (Only one controller will be used as the primary clock source.)
The startup and initial setting procedures vary with the system configuration.
System configuration 1: System without connection to AE-50 controller
System configuration 2: System with connection to one or more AE-50 controllers
Procedure
Start-up
Date and time
settings
Unit information
settings
Network settings
WT07935X04
(controlling 50 or fewer units of equipment)
(controlling more than 50 units of equipment)
System
configuration
1
2
Turn on the power to the AE-50 controllers.
Make initial settings for the AE-50 controllers on the [Unit Info.] and [Network]
screens.
* The AE-50 will restart.
Turn on the power to the AE-200.
The language selection window will appear. Select the desired language.
The [Initial Settings] screen will appear.
(Once the initial settings have been made, the [Monitor/Operation] screen will
appear when the unit is turned on. Touch the
Settings] screen if necessary.)
Set the current date and time.
Make other settings as necessary, and touch [Save Settings].
Touch the [Unit info.] tab in the [Initial Settings] menu.
Set the [System Exp] setting to [Do not expand].
Set the [System Exp] setting to [Expand].
When using an AE-200 apportioned electricity billing function or not using an
AE-200 M-NET, set the [AE-200 M-NET] setting to [Do not use].
When using an AE-200 apportioned electricity billing function, set the [AE-200
Apportion] setting to [Use].
Make other settings as necessary, and touch [Save Settings].
Touch the [Network] tab in the [Initial Settings] menu.
Set the AE-200's IP address and other necessary settings, and touch [Save
Settings].
* The AE-200 will restart.
Make sure that [AE200] is selected as [Controller], set the AE-200's IP address
and other necessary settings, and touch [Save Settings].
* The AE-200 will restart.
Touch the [AE200] button to change it to [Exp(1–3)]
IP addresses and other necessary settings, and touch [Save Settings].
Details
22