17 - Operating features

Electrical characteristics

25 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C
Operating currents and voltages
The correct operation of Ekip Touch trip unit is guaranteed with primary currents with clearly defined
characteristics.
In addition, Ekip Touch trip unit can be powered directly by the internal current sensors or, in the presence of
the Ekip Measuring Pro module, by the installation voltage.
The following are the specifications:
Parameter
Minimum three-phase turn-on current
Rated frequency
Peak factor
Minimum three-phase turn-on voltage
Auxiliary power supply
All the trip units of the Ekip Touch range can be connected to an external auxiliary power supply source,
useful to activate certain functions such as communication on a Local Bus, recording of manual operations,
measurements and the datalogger.
The auxiliary power can be supplied by the modules of the Ekip Supply rangeor with direct connection to a
terminal box.
The direct connection must be made guaranteeing the following operating conditions:
Parameter
Voltage
Tolerance
Maximum ripple
Maximum inrush current @ 24 V
Maximum rated power @ 24 V
Connection cable
IMPORTANT: in case of direct connection, the power supply must be galvanically
insulated and provide the insulation characteristics established by the Standard IEC
60950 (UL 1950) or equivalent.
Operating limits
> 80 A (E1.2-E2.2-E4.2)
> 160 A (E6.2)
50 / 60 Hz ± 10 %
Complying with standard IEC 60947-2
> 80 V
Operating limits
24 V DC galvanically isolated
± 10 %
± 5 %
10 A per 5 ms
4 W
Insulated with grounding cable (same characteristics
as Belden 3105A/B or higher)
Ekip Touch protection trip unit | 17 - Operating features
ABB | SACE Emax 2