Configuration; Set Boot Mode - Bosch ACS 561 Repair Instructions

A/c service unit
Table of Contents

Advertisement

ACS 561 Service Manual
3. Enter the manufacturing date using the
keypad and press Save (F1).

Configuration

Setting the Configuration is usually done at the
factory but may be performed or checked when
maintenance is performed on the unit.
1. From any menu scroll to Configuration.
2. Press Select (F1). The following displays:
As the items are selected one at a time, the
current value of that item is displayed in a new
screen. The windows where Select and Exit
normally appear with change to Yes or No,
except for the refrigerant which will change to
1234yf and 134a, which is shown below.
Robert Bosch GmbH
Diagnostics and Testing
The items, selectable options, and default
settings are listed in the table.
ITEM
OPTIONS
Refrigerant
R1234yf / R134a
Inject Enabled
Yes /No
Inject Load Cell
Yes /No
Drain Load Cell
Yes /No
HS Transducer
Yes /No
LS Transducer
Yes /No
ISV Transducer
Yes /No
Acc Transducer
Yes /No
ISV Temp
Yes /No
Charge Leak Test
Yes /No
Air Flow Sensor
Yes /No
3. After the options have been entered press
Exit (F2) to return to the Service Menu.

Set Boot Mode

Setting the Boot Mode makes it possible to boot
into a mode other than Normal (default). The
choices to boot to are Normal, Filter Change
in Progress, Leak Test Required, or End-User
Install.
1. From any menu scroll to Select Boot Mode.
2. Press Select (F1).
3. Enter password to 2-8-7-6-8, If the pass-
word is valid, the following displays:
4. Scroll to the boot mode desired and press
Save (F1). The unit will boot to the selected
mode at the next power up cycle.
29
DEFAULT
R1234yf
Yes
No
No
No
Yes
No
Yes
No
Yes
Yes
SP00D00517
2018-07-11