Sdi2 Device Failure; Primary Destination Device - Bosch B9512G Installation Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panels
Figure 1.22: SDI2 Device Failure
PANEL WIDE PARAMETERS > Communicator > Primary
Destination Device
For the Route Group 4 column, set Primary Destination Device
to Destination 4 for the type of device in use (for example,
Onboard IP, Destination 4 if the control panel sends reports
using the on-board Ethernet.
Figure 1.23: Primary Destination Device
PANEL WIDE PARAMETERS > Enhanced Communication >
Destination 4
In the Destination 4 column, set Network Address to: 0.1.1.1
(this address is intentionally not a real address on the network).
Set the Poll Rate to 0. Set the ACK Wait Time (sec.) to 5.
Bosch Security Systems B.V.
ULC Installation Guide | en
2019.06 | 02 | F.01U.321.698
31