Panasonic 1735 Technical Description page 14

Alert annunciation units
Hide thumbs Also See for 1735:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
Push button
Alarms queued
P1
(Flera larm)
Acknowledge
P2
6
(Kvittering)
P3
Reset
(Återställning)
Component
7
Buzzer
Display
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
Table of push buttons:
Colour
Operation / function
Used, when LED "L2" (Alarms queued) is turned on,
Black
to scroll through the queued alarms. (The first alarm
will automatically be shown again after 20 seconds,
if no button is used during that time.)
Used to acknowledge an AA alarm. The unit's
Yellow
buzzer will also be silenced. (Investigation time
starts.) Acknowledged AA alarm is indicated by
LED "L4" (Acknowledge).
Green
Used to reset all AA alarm(s). (Fire alarms, i.e. not
6
AA alarms, have to be reset in the c.i.e.). So called
"encapsulation" is not possible to do.
NOTE! Regarding "P1" and "P2", see chapter "SW mode & Address
setting, page 16 and regarding "P3", chapter "SW version", page 27.
Table of others:
Indicating
1 beep/5 s
Cont. + All LEDs
turned off as well.
All or selected Fire alarms
c.i.e. that the AA unit is connected to and an alarm text (if
programmed).
(NOTE! A fault message may be shown, indicating a
communication fault (i.e. no connection between the unit and
the c.i.e.).
NOTE! Regarding the Buzzer and the Display, see also chapter "SW
mode & Address setting, page 16.
6
Press simultaneously "P2" (Acknowledge) & "P3" (Reset) for a test of the
LEDs, the buzzer and the display (back-light and dots).
NOTE! This must be done only in quiescent condition.
7
The buzzer may be programmed as "disabled" (via Win512 / Win128 /
Win512 G3), i.e. it will never sound.
8
Also Heavy smoke / heat alarms.
AA alarm.
There is a CPU / memory fault in the unit.
8
/ AA alarms presented like in the
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

1736

Table of Contents