Siemens Cerberus DO1101A-Ex Technical Description

Siemens Cerberus DO1101A-Ex Technical Description

Wide spectrum smoke detector

Advertisement

Cerberus® DO1101A Ex,
DT1101A Ex, DT1102A Ex
Wide spectrum smoke detector,
collective
Heat detectors, collective,
intrinsically safe
Technical description
Fire & Security Products
Siemens Building Technologies Group

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Cerberus DO1101A-Ex

  • Page 1 Cerberus® DO1101A Ex, DT1101A Ex, DT1102A Ex Wide spectrum smoke detector, collective Heat detectors, collective, intrinsically safe Technical description Fire & Security Products Siemens Building Technologies Group...
  • Page 3: Table Of Contents

    Brief overview ........... . Characteristics .
  • Page 5: Brief Overview

    Brief overview OptoRex DO1101-Ex ThermoRex DT1101-Ex / DT1102-Ex Dimensions Dimensions Ø 115 Ø 115 47...70 47...70 With base DB1101 With base DB1101 Characteristics For applications in explosion-hazard areas of zones For applications in explosion-hazard areas of zones 1 and 2 1 and 2 Balanced response behavior and wide range of ap- Heat detectors to meet the highest requirements...
  • Page 6: Design

    Design OptoRex DO1101-Ex ThermoRex DT1101-Ex / DT1102-Ex The OptoRex DO1101-Ex is eminently suited to early The DT1101-Ex/DT1102-Ex ThermoRex is suitable for the detection of smoldering fires, but it also quickly detects monitoring of rooms in which upon an outbreak of fire, a flaming fires that produce smoke.
  • Page 7: Technical Data

    Technical data Normal ambient conditions, if nothing else is specified: Temperature T DO1101-Ex 20°C (293K) DT1101-Ex/DT1102-Ex 25°C (298K) Air pressure p 1’000hPa (750 Torr) Parameters Symbol Unit DO1101-Ex DT1101-Ex DT1102-Ex Conditions Operating voltage ..
  • Page 8: Principle Of Operation

    Principle of operation OptoRex DO1101-Ex ThermoRex DT1101-Ex / DT1102-Ex The OptoRex DO1101-Ex is based on the principle that The ThermoRex DT1101/DT1102 measures the ambient smoke scatters light. An infrared LED (IRED) transmits temperature with the NTC thermistor R in the tip of the brief, intensive light pulses into the scattering chamber.
  • Page 9: Environmental Influences

    Environmental influences Influence of the ambient temperature OptoRex DO1101-Ex [%/m] DO1101A-Ex ϑ ° –10 Ambient temperature Fig. 3 Smoke sensitivity of the OptoRex DO1101-Ex as a function of the ambient temperature Other influencing variables Ambient light, air drafts and fluctuations within the speci- fied operating voltage range have no influence on the de- tector.
  • Page 10: Application

    Application Compatibility Control units: Compatible with all Cerberus control units with collective signal evaluation to- gether with input/output module DC1192 and shunt Zener barrier Bases: DB1101 Alignment functions None. Application OptoRex DO1101-Ex ThermoRex DT1101-Ex / DT1102-Ex The OptoRex DO1101-Ex is suitable for applications in ex- The ThermoRex DT1101-Ex/DT1102-Ex is suitable for ap- plosion-hazard areas of zones 1 and 2.
  • Page 11: Commissioning

    Commissioning To prevent unnecessary soiling during the construction phase, the detectors should be inserted into the bases just before the system is put into service. For detailed information, see «Fire Detection in Explosion-hazard Areas», document e1204. . Maintenance Functional check A functional check of the detectors must be performed periodically (usually once per year) by forcing each detector to respond by means of a suitable testing device (RE6 or DZ1192 for DO1101-Ex...
  • Page 12: Terms

    Terms ASIC Application Specific Integrated Circuit CC11 Fire detection control unit AlgoControl to fire detection system S11 CZ.. Fire detection control unit to fire detection system MS9 DB1101 Base for collective DS11 fire detectors DBZ1191 Base attachment DC1192 Input/output module DO1101-Ex OptoRex smoke detector, for explosion-hazard areas DT1101-Ex...

This manual is also suitable for:

Cerberus dt1101a-exCerberus dt1102a-ex

Table of Contents