Installing the SVI FF for Double- Acting Operation

This section explains how to mount the SVI FF for the 84/85/86 kit for double-acting valve
positioner configurations.
To mount the kit:
1. Set valve to the closed position.
2. Install the mounting assembly to the yoke (Figure 27) using helical spring washer 5/16, flat
washer 5/16 and hex screw 5/16-18x44.5 [1.75] LG.
NOTE
3. Set rod-ends and brackets to stroke and size of actuator. The default setting is a 4.00"
stroke. Other stroke settings are as in Figure 28.
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Kit Mount
Bracket
Figure 27 85/86 Valve
Mount all components snug enough to stay in place but loose
enough to tap with rubber hammer into final position.
Hole A: .50" to .80"
Hole B: 1.00" to 1.50"
Hole C: 2.00" to 2.50"
Hole D: 3.00" to 4.50"
Hole E: 5.00" to 6.00"
Figure 28 Stroke Settings
Lever
Rod-end
Masoneilan SVI FF Instruction Manual
| 59
=