INSTALLATION

WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON THE COMMON OUTPUT AND HOT
OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. JOIN INVERTER
CONNECTOR INSIDE THE CASE AFTER INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
NOTE: Make sure the inverter connector is closed before screwing the front cover to the case.
STEP #1
INSTALLING THE EMERGENCY LIGHTING INVERTER
>
Remove front cover and any packing material inside the unit housing that may have been used for shipping
purposes.
>
Secure housing to the mounting surface through the keyhole knockouts using mounting hardware (not supplied).
This hardware must be appropriate to hold the unit weight of 25 lbs with the batteries installed.
>
Remove the knockouts to install input and output wiring conduit fittings.
>
Extend AC supply, output load wiring, and optional control wiring into the equipment enclosure using appropriate
wiring hardware and methods.
>
Illustration 1 details the locations of the various wiring terminals and switch locations needed for the remainder of
the installation. Reference Illustration 1 for steps through 2 through 5
STEP #2
WIRING THE EMERGENCY LIGHTING INVERTER'S PRIMARY POWER CONNECTIONS
NOTE: Make sure all connections are in accordance with the National Electrical Code, Canadian Electrical Code and
any local regulations.
Reference Illustration 2 when making the following wiring connections.
>
Connect the Load Common lead to screw terminal "J3 –Out Com"
>
Connect the Load Hot lead to screw terminal "J3 –Out Hot"
>
Connect the Emergency Lighting Inverter to ground using screw terminal "J3 -GND"
>
Connect the AC Power Source Common to screw terminal "J3 –COM"
>
Connect the Unswitched Hot to screw terminal "J3 -UnSwHot"
Screw terminal "J3 -SwHot" is the means of powering the load luminaires in Normal Mode. If a wall switch is the local
control means, this switched hot must be connected in order to power the load when AC power is present. If no wall
switch is used, and the load luminaires are controlled by the same circuit breaker that is powering the unswitched
hot,"J3SwHot" can be jumpered to "J3 –UnSwHot".
ILLUSTRATION 1
INSTALLATION QUICK REFERENCE GUIDE
2