GE AF-650 GP Operating Instructions Manual page 39

General purpose drive high power 460/575/690v 125hp and above
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Installation
AF-650 GP 3-phase
[HP]
IP21 / Nema 1 and IP55 / Nema 12 and IP66 / Nema 4
15
20
25
3
3
30
40
50
60
75
100
125
150
200
250
300
350
400
500
550
650
750
900
1000
1150
1250
1350
Table 3.8 525-690V. IP21 / Nema 1 and IP55 / Nema 12 and IP66 / Nema 4
3.4.13 NEC and UL Compliance
Fuses or Circuit Breakers are mandatory to comply with NEC 2009. We recommend using a selection of the following
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 600V
depending on the drive voltage rating. With the proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
AF-650 GP
Power
HP
1/3-1/2
1
2
3
5
7.5
10
15
20-25
30
40
50
Table 3.9 200-240V, Unit Sizes 1X, 2X and 3X
38
AF-650 GP High Power Operating Instructions
Recommended fuse size
gG-25
gG-32
gG-40
gG-63
gG-80
gG-100
gG-125
aR-250
aR-315
aR-350
aR-400
aR-500
aR-550
aR-700
aR-900
aR-1600
aR-2000
Bussmann
Bussmann
1)
Type J
Type RK1
KTN-R-05
JKS-05
KTN-R-10
JKS-10
KTN-R-15
JKS-15
KTN-R-20
JKS-20
KTN-R-30
JKS-30
KTN-R-50
KS-50
KTN-R-60
JKS-60
KTN-R-80
JKS-80
KTN-R-125
JKS-125
KTN-R-150
JKS-150
KTN-R-200
JKS-200
KTN-R-250
JKS-250
Recommended max fuse
gG-63
gG-80
gG-100
gG-125
gG-160
aR-250
aR-315
aR-350
aR-400
aR-500
aR-550
aR-700
aR-900
aR-1600
aR-2000
Recommended max. fuse
Bussmann
Bussmann
Type T
Type CC
JJN-05
FNQ-R-5
JJN-10
FNQ-R-10
JJN-15
FNQ-R-15
JJN-20
FNQ-R-20
JJN-30
FNQ-R-30
JJN-50
-
JJN-60
-
JJN-80
-
JJN-125
-
JJN-150
-
JJN-200
-
JJN-250
-
Recommended circuit breaker
-
Bussmann
Type CC
KTK-R-5
KTK-R-10
KTK-R-15
KTK-R-20
KTK-R-30
-
-
-
-
-
-
-
Max trip level
[A]
-
Bussmann
Type CC
LP-CC-5
LP-CC-10
LP-CC-15
LP-CC-20
LP-CC-30
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents