26
PositionMaster EDP300 DIGITAL POSITIONER | CI/EDP300-EN REV. D
... 6 Installation
... Electrical connections
Module for the emergency shutdown function*
When the 24 V DC signal is interrupted, the I/P module executes
the respective safety function, depending on the mechanical
construction.
The positioner output 1 is depressurized, and the valve is moved
to the safe position. In case of a double-acting actuator, output
2 is additionally pressurized.
The emergency shutdown module works independently of the
mother board, i.e., all information from the final control element
is available in the control system at any time.
Terminals
Supply voltage
Safe position
*
There are two slots for the option modules. Any combination of different
option modules is possible. However, identical option modules cannot be
combined.
Change from two to one column
+85 / −86
24 V DC (20 to 30 V DC)
(electrically isolated from the input signal)
Active at < 5 V DC
Limit switch
The limit switch can either be equipped with proximity switches
or with potential-free microswitches.
Limit switch Limit 1 / Limit 2 with proximity switches
Two proximity switches for independent position signaling.
Terminals
Supply voltage
Output 'logical 0'
Output 'logical 1'
Switching point
Direction of action
Metal tag in proximity
Type SJ2-SN (NC; log. 1)
Limit switch Limit 1 / Limit 2 with 24 V - microswitches
Terminals
Supply voltage
Load rating
+41 / −42, +51 / −52
5 to 11 V DC
(Control circuit in accordance with DIN
19234/NAMUR)
< 1.2 mA
> 2.1 mA
Adjustable between 0 and 100 %
Metal tag outside
switch
proximity switch
< 1.2 mA
> 2.1 mA
41 / 42 / 43, 51 / 52 / 53
maximum 24 V AC/DC
Maximum 2 A