Download Print this page
Siemens Binary Input N 260 Technical Product Information
Siemens Binary Input N 260 Technical Product Information

Siemens Binary Input N 260 Technical Product Information

4 x 230 v ac

Advertisement

Quick Links

Binary Input N 260
4 x 230 V AC
Product and Applications Description
The binary input N 260 is a N-system DIN-rail mounted
device with four inputs for AC 230 V switching or keying
signals from separate external outside lines (L1, L2, L3)
with a shared reference potential (N).
Each of the inputs can be assigned various tasks
depending on the application program used, i.e. the
binary input N 260 consists of the device (hardware) and
its application programs (software).
Appropriate application programs are available for
the different tasks the binary input N 260 can handle;
e.g. sending of on/off telegrams at different edges of the
input signal either event-controlled or cyclic with
parametrisable repetition intervals.
With the ETS (EIB Tool Software) the application
program is selected, its parameters and addresses are
assigned appropriately, and downloaded to the binary
input N 260.
Applikationsprogramme
12 S4 BinCycl 240505
• 4 binary inputs
• each input allows switching on/off or toggling at
leading or trailing edge
• allows cyclic sending
• allows sending at bus voltage recurrence
• sending condition can be set
12 S2 On-off-toggle/Dim/Shu 220703
• 4 binary inputs
• allows configuration for dimmer/shutter or
on/off/sending value
• switching at leading edge or at leading and trailing
edge
• switching short/long key depression
Siemens AG
Automation and Drives Group
Electrical Installation Technology
P.O.Box 10 09 53, D-93009 Regensburg
• sending value at leading edge or at leading and
trailing edge
• duration of long key depression can be set
• used type of contacts can be set
11 S4 BinVal 240A01
• 4 binary inputs
• each input allows to send values at leading edge
and/or at leading and trailing edge
• allows cyclic sending
• allows delay
• allows interlocking
Example of Operation
Installation Instructions
• The device may be used for permanent interior
installations in dry locations within distribution boards.
V
• The device may be built into distribution boards
(230/400 V) if VDE-certified devices are used
exclusively and must be mounted and commissioned
by an authorised electrician.
• A safety disconnection of the device must be possible.
Especially if the device is connected to different
phases.
• Free DIN rail areas must be covered with covers,
order no. 5WG1 192-8AA01.
• The prevailing safety rules must be heeded.
• The device must not be opened. A device suspected
faulty should be returned to the local Siemens office.
N 260, 4 pages
 Siemens AG 2001
Subject to change without prior notice
Technical Product Information
AC 230/400V
binary input N 260
2
channel A
4
channel B
3
N
6
1
channel C
5
channel D
WARNING
Update: http://www.siemens.de/installationstechnik
instabus EIB
September 2001
5WG1 260-1AB01
load circuit
L1 L2 L3 N
switching /
keying signals
Technical Manual
2.7.1.3/1

Advertisement

loading

Summary of Contents for Siemens Binary Input N 260

  • Page 1 AC 230/400V L1 L2 L3 N The binary input N 260 is a N-system DIN-rail mounted binary input N 260 device with four inputs for AC 230 V switching or keying signals from separate external outside lines (L1, L2, L3) channel A with a shared reference potential (N).
  • Page 2 EIB Technical Product Information September 2001 Binary Input N 260 5WG1 260-1AB01 4 x 230 V AC Technical Specifications WARNING Power supply When looping through the shared N-conductor via bus cable (connection blocks 3 and 6), take care that the maximum...
  • Page 3 EIB Technical Product Information September 2001 Binary Input N 260 5WG1 260-1AB01 4 x 230 V AC Location and Function of the Display and Mounting DIN-rail devices (Figure 2) Slide the device (B1) onto the DIN-rail (B2) and Operator Elements swivel back the device until the slide clicks into place audibly.
  • Page 4 EIB Technical Product Information September 2001 Binary Input N 260 5WG1 260-1AB01 4 x 230 V AC Dimensions Diagram Notes Dimensions in mm b = 2 SU 1 Spacer unit (SU) = 18mm Technical Manual N 260, 4 pages...