Commissioning
Confirming or rejecting the change
Rejecting the change
▶ Press the selector to activate the marked entry or to
confirm the change.
▶ Turn the selector to highlight Continue and press the
selector.
&
The Display switches to the higher menu level. The
user interface operates with the modified setting.
Rejecting the change
▶ Press the Back key to undo the change.
Table 18
6.7.2
Central heating settings - Outdoor temperature or Room
temperature compensated control
The pump operation when used with a HIU unit does not need to be
optimised and the Pump economy mode should be disabled.
▶ Enter the Service menu and navigate through the menus and select
the Heating settings menu.
▶ Navigate through the Heating settings and select Heating circuit 1
▶ Set Pump economy mode to No.
Heating circuit 1:
Parameter
Description
Pump economy mode ▶ Optimised pump operation for the heat
source.
– Yes = Enabled
– No = Disabled
Default value is Yes.
Table 19
Outdoor temperature or Room temperature compensated control
Compensated control modulates the central heating flow temperature
via the central heating pump and control valve position to control the
required flow of heated water into the system.
The default central heating room temperature control is Weather-
compensated but can be set to Room temperature-dependent.
▶ Enter the Service menu and navigate through the menus and select
the Heating settings menu.
▶ Navigate through the Heating settings and select Heating circuit 1.
▶ Navigate through the Heating circuit 1 and select Control type.
▶ Set Control type to Room temperature-dependent.
Heating circuit 1:
Parameter
Description
Control type
▶ Central heating control method.
– Weather-compensated
– Outside temp. with base point
– Room-temperature-dependent
– Room temperature output
– Single room-dependent
Default value is Weather-compensated.
Table 20
36
6.7.3

Heat Interface Unit settings

▶ Enter the Service menu and navigate through the menus and select
the Heat Interface Unit settings menu.
▶ Navigate through the Heat Interface Unit settings and select the
parameter required.
▶ Adjust the parameter as required.
Heat Interface Unit
settings: Parameter Description
Set return
District return temperature set point.
temperature
▶ Range from 0 - 90 ( °C)
Default value is 50 °C
Min. contr. valve off
Minimum CH delay time, (to avoid control
time
valve oscillations).
▶ Range from 0 - 60 minutes
Default value is 3 minutes.
Calibrate control valve Calibration DHW/CH control valve via
controller.
▶ Select either DHW or CH
– Off = Normal operation
– On = Calibrate valve
Once On has been selected the calibration
starts and the value returns to Off.
Table 21
6.7.4

Electronic by-pass function setup

DHW circulation for electronic by-pass function
Check that the DHW circulation pump is enabled.
▶ Enter the Service menu and navigate through the menus and select
the DHW settings menu.
▶ Navigate through the DHW settings and select DHW system I menu.
▶ Navigate through the DHW system I and select DHW circulation
pump.
▶ Ensure that the DHW circulation pump is set to On.
DHW settings:
Parameter
Description
DHW circulation pump ▶ Control of DHW circulation pump by heat
source.
– Off = Disabled
– On = Enabled
Default value is On.
Table 22
Following checking DHW circulation pump is enabled you will need to
set the DHW circ.pmp op.mode.
▶ Navigate through the DHW system I and select DHW circ.pmp
op.mode.
▶ Set DHW circ.pmp op.mode to On.
DHW settings:
Parameter
Description
DHW circ.pmp
▶ Operating mode for the DHW circulation
op.mode
pump.
– Off = Disabled
– On = Enabled
– As DHW system I = As per timings for
DHW demand
– Own time program = Separate time
control
Default value is Off.
6 720 808 928 (2017/06)