EN – Quick start-up guide on page 49. To read a manual, go to www.abb.com/drives/documents and search for the document number. Obey the safety instructions WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur: •...
12 EN – Quick installation and start-up guide Select the power cables Size the power cables according to local regulations to carry the nominal current given on the type designation label of your drive. Ensure the cooling See table on page (UL: table on page 7) for the heat dissipation.
EN – R0…R3 Quick installation guide 13 Switch off the power and open the cover See figure on page 19. 2. Switch off the power from the drive. 3. Remove the front cover: Loosen the retaining screw with a screwdriver (3a) and lift the cover from the bottom outwards (3b) and then up (3c).
Page 16
14 EN – Quick installation and start-up guide Check from the table below if you have to disconnect the EMC filter (EMC) or ground- to-phase varistor (VAR). For instructions on how to do this, see page 16. Frame Ground- Symmetrically Corner grounded IT systems sizes...
EN – R0…R3 Quick installation guide 15 Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see figure on page 19.
16 EN – Quick installation and start-up guide Connect the power cables See figures (page 19) D, E, F1, and G. 1. Remove the rubber grommets from the lead-through plate. Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE conductor for drive or motor, make sure that is has sufficient conductivity for the PE.
EN – R0…R3 Quick installation guide 17 Connect the control cables See figure on page 20. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the default configuration in use. The default connections of the HVAC default configuration are shown in section Default I/O connections on page 19.
18 EN – Quick installation and start-up guide Default I/O connections Default I/O connections of the HVAC default configuration are shown below. Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND Analog input circuit common +10V...
EN – R0…R3 Quick installation guide 19 Install optional modules, if any See chapter Electrical installation in ACH580-01 hardware manual (3AUA0000076331 [English]). Reinstall cover See figure on page 20. 1. Put the tabs on the inside of the cover top in their counterparts on the housing (1a) and then press the cover at the bottom (1b).
Page 22
20 EN – Quick installation and start-up guide...
EN – Quick start-up guide on page 49. To read a manual, go to www.abb.com/drives/documents and search for the document number. Obey the safety instructions WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur: •...
32 EN – R6…R9 Quick installation guide Select the power cables Size the power cables according to local regulations to carry the nominal current given on the type designation label of your drive. Ensure the cooling See table on page (UL: table on page 27) for the heat dissipation.
EN – R6…R9 Quick installation guide 33 Check the insulation of the power cables and the motor Check the insulation of the input cable according to local regulations before connecting it to the drive. See figure on page 1. Check the insulation of the motor cable and motor before connecting it to the drive.
Page 36
34 EN – R6…R9 Quick installation guide WARNING! Do not install the drive with the ground-to-phase varistor connected on an IT system (an ungrounded power system or a high- resistance-grounded [over 30 ohms] power system), otherwise the varistor circuit can be damaged.
EN – R6…R9 Quick installation guide 35 Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see steps 5, IP21 and 5, IP55 in figure R6…R9 Figures A on page...
36 EN – R6…R9 Quick installation guide Connect the power cables See figure on page 41. Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE conductor for drive or motor, make sure that is has sufficient conductivity for the PE.
42. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the default configuration in use. The default connections of the ABB standard macro are shown in section Default I/O connections on page 38.
38 EN – R6…R9 Quick installation guide Default I/O connections Default I/O connections of the HVAC default configuration are shown below. Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND Analog input circuit common +10V Reference voltage 10 V DC...
EN – R6…R9 Quick installation guide 39 Install optional modules, if any See chapter Electrical installation in ACH580-01 hardware manual (3AUA0000076331 [English]). Install side plates and covers See figure R6…R9 Figures E on page 44. IP21 1. Reinstall the side plates of the cable entry box. Tighten the retaining screws with a screwdriver.
EN – Quick start-up guide 49 EN – Quick start-up guide This guide describes how to start-up the drive using the First start assistant on the HVAC control panel. For complete information on start-up, see ACH580 firmware manual (3AXD50000027537 [English]). Before you start Ensure that the drive has been installed as described in chapter EN –...
Page 52
Refer to the motor nameplate for the following nominal value settings of the motor. Enter the values exactly as shown on the motor nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl.
Page 53
EN – Quick start-up guide 51 To change a value in an edit view: • Use to move the cursor left and right. • Use to change the value. Press (Save) to accept the new setting, or press (Cancel) to go back to the previous view without making changes.
Page 54
52 EN – Quick installation and start-up guide Change the units shown on the panel if needed. • Go to the edit view of a selected row by pressing • Scroll the view with Go to the next view by pressing (Next).
Page 55
EN – Quick start-up guide 53 The Home view monitoring the values of the selected signals is shown on the panel.
Page 56
54 EN – Quick installation and start-up guide 2 – Hand/Off/Auto operation The drive can be in remote control or local control, and in local control there are additionally two different modes. Remote control: Drive is controlled from the I/O or the fieldbus.
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.