About this document ................5 Safety regulations ................7 Signal words and symbols ..............7 2.1.1 Classification and meaning of signal words ..........7 2.1.2 Symbols and their meaning ..............7 2.1.3 Classification and meaning of additional symbols ........8 Safety-relevant working instructions ............8 Commissioning overview ..............10 Commissioning the system ..............
About this document About this document Goal and purpose This document describes commissioning of the hardware components of control panel CS1140/45. Safe applications will result from consistently following these in- structions. Scope of validity This document contains information valid for software variant EP7F. Target audience This product documentation and the operating instructions are intended for the fol- lowing people, who carry out a particular job and have been trained for it.
Page 6
Products are designed for proper use, and before they are delivered they are test- ed to ensure they function correctly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warn- ings of danger contained in the documentation.
Safety regulations Safety regulations This chapter describes the danger levels and the relevant safety regulations appli- cable for the use of our products. Please read the work instructions as well as the chapter 1 'About this document' before beginning any work. Signal words and symbols 2.1.1 Classification and meaning of signal words...
Safety regulations 2.1.3 Classification and meaning of additional symbols Tips and information. Refers to extremely important or critical decisions to be taken into account before continuing the work. Safety-relevant working instructions Country-specific standards The products are developed and produced in compliance with the relevant Euro- pean safety standards.
Page 9
Safety regulations Testing the product operability Evacuate and cordon off the extinguishing sector. κ Inform people about the possibility of fogging and noise. κ Inform people before testing alarm devices; take the possibility of panic reac- κ tions into account. Inform the alarm and fault receiving stations connected to the system before car- κ...
Commissioning overview Commissioning overview Commissioning the system CI1145 CI1145 CT1142 CC1142 Precondition for complete work 1. Control panel fitted and detector lines ready for connection (1), or detector lines connected to separate connection panel (2). 2. Peripheral devices such as operating terminal (3), plain text operating terminal, parallel display, etc.
Commissioning overview 3.1.1 Preparations Compact control panel CI1145 –> see document 008727 κ Fit and connect the hardware – Control panel CC/CI κ according to system documentation: Fit power supply unit – Connect mains cable and supply line – Fit board holder and attach connection cable –...
Fitting the hardware Fitting the hardware Fitting and connecting hardware CI1145 For a complete description of the installation process for the various variants of the CI1145 control panel –> see document 008727. Fitting board holder in CS1140 For details of installation instructions –> see reference documents in chapter 1 Item Component Preparation...
CPUs CPUs E3X101 control panel module Take measures to protect against overvoltage when inserting RAM and NOTE EPROMs. Press modules all the way into the base. Item Component Preparation Default ex factory RAM kit (2x 512Kx8 bits) Z3S070 Insert in pos. 'D11' / 'D12' Not used 0 ς...
CPUs E3X102/103 control panel module Item Component Preparation Default ex factory SRAM – E3X102 (2x512Kx8 bits) E3X103 (4x512Kx8 bits) Flash ROM – Program file E3X102 CCX00xxx E3X103 CCY00xxx 'S2' programming switch: Battery type Set to battery make used, see description in docu- 'ALARMCOM (FIAMM)' type selection ment 001260...
CPUs B3Q460/480/485 operating terminal can be used as 'CT' or 'CI' Take measures to protect against overvoltage when inserting RAM and NOTE EPROMs. Press modules all the way into the base. Item Component Preparation Default ex factory Shielding hood Remove (refit in last step) Fitted RAM kit (2x 512Kx8 bits) Z3S070 Insert in pos.
CPUs B3Q66x/670/68x/56x operating terminal used as 'CT' or 'CI' Item Component Preparation Default ex factory SRAM – B3Q6xx (2x512Kx8 bits) B3Q565 (4x512Kx8 bits) Flash ROM If using as 'CI', load other program file: Program file as 'CT' B3Q6xx CIX00xxx B3Q6xx CTX00xxx B3Q565 CIYTxxxx B3Q565 CTYTxxxx Shielding hood...
Line plug-in modules Line plug-in modules E3M060 line plug-in module 'MS9i' Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress E3M071 'interactive' line plug-in module Allows up to 128 D bus devices to be connected, but only if all the devices used feature the 'A' designation (e.g.
Line plug-in modules E3M171 'interactive Ex' line plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress E3M080 'collective' line plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0...
Line plug-in modules E3M120 line plug-in module 'CBA8000/TS9000' Item Component Preparation Default ex factory 'S1' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'X1' bridge: Watchdog – attached 'in' -> watchdog active E3M140 'FD20' line plug-in module Item Component Preparation...
Line plug-in modules E3M141 'FD20' line plug-in module Item Component Preparation Default ex factory 'I BUS ADR' programming switch: Set in accordance with system documentation Address 0 I bus address 'SYNC-MASTER' programming switch: if the line plug-in module is the master, set switch 1 to To 'OFF' Synchronization of alarm devices in 'ON'...
LON plug-in module LON plug-in module E3I040 I bus/LON plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 100 ς 'R60' resistor: 'LON bus' terminator If the LON bus is wired as free topology, 'R60' must be changed to 50 ς, see description in document resistor 001260...
Control plug-in modules Control plug-in modules E3L020 'I/O' control plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'S2' service switch: Activate test LEDs Set to 'ON' for commissioning To 'OFF' 'H1'..'H16' E3L030 'VdS' control plug-in module...
Control plug-in modules E3G050 'contacts' control plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'S2' service switch: Activate test LEDs Set to 'ON' for commissioning To 'OFF' 'H1'..'H8' E3G060 'monitored' control plug-in module...
Control plug-in modules E3G070 'universal' control plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'S2' service switch: Activate test LEDs Set to 'ON' for commissioning To 'OFF' 'H1'..'H11' 0 ς...
Operation and floor repeater display Operation and floor repeater display 11.1 B3Q... AlgoPilot operating terminal For operation of AlgoPilot B3Q..–> see pages 15 –16 11.2 B3Q321 fire brigade operating unit Item Component Preparation Default ex factory Shielding hood Remove (refit) Fitted 'S3' programming switch: I bus ad-...
Operation and floor repeater display 11.4 K3R072 mimic display board Item Component Preparation Default ex factory Mounting plate Remove, fit according to system documentation, see Fitted also description in document 001260 'N3' resistor array Remove from all but 1 device, also see description in Equipped document 001260 'S1' programming switch: Device...
Operation and floor repeater display 11.6 K3I050 LON/mimic display converter Item Component Preparation Default ex factory Mounting plate Remove, fit according to system documentation, see Fitted also description in document 001260 'S3' programming switch: LON bus Set in accordance with system documentation Address 0 address 'S4-1' programming switch: Define...
Operation and floor repeater display 11.8 K3I110 LON I/O board Item Component Preparation Default ex factory 'S3' programming switch: LON bus Set in accordance with system documentation Address 0 address 'X30' bridge: Ground fault monitoring Set according to system documentation, see also To 'right' (not monitored) 'Inputs' description in document 001260...
Operation and floor repeater display 11.10 B3Q590/595 plain text operating terminal Item Component Preparation Default ex factory 'S3' programming switch: LON bus Set in accordance with system documentation Address 0 address 'S4-1' programming switch: Buzzer off For 'S4-1' commissioning, set to 'ON' To 'OFF' 'R1' resistor: 'LON bus' terminator When using stub line: If B3Q5xx is not the last de-...
Printer Printer 12.1 K3L080 printer control (included and fitted in B2Q191 protocol printer) Item Component Preparation Default ex factory 'S1' programming switch: For Baud Set according to description in document 001260, To 'closed' rate, set of characters 'Protocol printer B2Q191' chapter 'X11/12' bridges: Define active inter- All plugged to '2-3' faces...
Gateway Gateway 13.1 E3H020 C bus gateway Take measures to protect against overvoltage when inserting RAM and NOTE EPROMs. Press modules all the way into the base. Item Component Preparation Default ex factory RAM modules 'D11/12', 'D15/16' or – 4x512Kx8 bits RAM kit Z3S070 (2x 512Kx8 bits) Change RAM if necessary, see description in docu- ment 001260...
Gateway 13.2 E3H021 C bus gateway Item Component Preparation Default ex factory SRAM – 8x512Kx8 bits Flash ROM – Program file for E3H021 CK1142 CKX00xxx CK1143 CKY00xxx 'S3' programming switch: Set in accordance with system documentation All switches to 'OFF' Set station address 'S5' programming switch: Set according to system documentation, see also...
Power supply Power supply 14.1 B1F120/B2F020/B2F040/B2F060 converter Item Component Preparation Default ex factory Metal cover Remove – Bridge Important: Check voltage set, possibly, reconnect at 230 V AC mains voltage 115 V AC mains voltage Metal cover Refit – Converter (power supply unit) Fit in housing or on component carrier –...
Power supply 14.2 E3C011 battery charging plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'S2' programming switch: Battery type Set to battery make used, see description in docu- 'ALARMCOM' (FIAMM) type selection ment 001260...
Ground fault monitoring Ground fault monitoring 15.1 Components with ground fault monitoring For detailed information about components with ground fault monitoring, use, func- tion and programming, see document 001260, 'Ground fault monitoring' chapter. The ground fault monitoring is inactive for all components, i.e. 'C bus potential' is not routed to 'system ground' –>...
Inserting plug-in modules Inserting plug-in modules NOTE Do not under any circumstances connect I buses from different stations! Procedure 1. Insert plug-in modules (1) according to system documentation and lock. 2. Fit I bus flat cable (2) (ensure good contact). Never plug in or remove when en- ergized.
Switching on for the first time Switching on for the first time 1. Check whether the batteries are connected. 2. Establish mains voltage. Note 2 'Safety regulations' chapter. The 'CC'/'CI'/'CT' stations load basic configuration stored in the EPROM into – the RAM.
Activating interactive and AnalogPLUS devices 18.4 Input/output modules Item Input/output module Procedure DC11xx Addressing by order of installation – Addressing by inserting switching unit DC11xx-AA – Addressing by alarming, press button (3), the addressing is – indicated by the LED (4) flashing Building Technologies 008726_e_en_-- Fire Safety...
Activating Sinteso devices 19.2 Manual call point Item Manual call point Procedure FDM.. 'KAC' version Insert test key – Wait until the response indicator flashes – – Remove test key again FDM11... 'DIN' version Use key to open doors – Press button firmly –...
Activating Sinteso devices 19.4 Alarm devices FDUD292 FDUD293 Activating of alarm devices via FDUD29x is not possible. This can be done by activating the corre- sponding zone. Building Technologies 008726_e_en_-- Fire Safety 06.2017...
Tool for localization Tool for localization 20.1 Commissioning list for identifying devices Handheld list κ 01: demo system Area: 01: 2nd floor west Section: Detector Location ID number type laboratory 201 window left DO1151 95683489 DO1151 25897954 laboratory 201 window right Enter detector ID number, laboratory 201 door left DO1151...