Dispatch.txt" Gateway File - Siemens S7 Series Communication Instruction Manual

Communication via knx gateway
Table of Contents

Advertisement

4 Configuration and Project Engineering

"dispatch.txt" gateway file

4.4.7
The assignment between KNX data points and PROFINET data points is made in
the "dispatch.txt" configuration file.
Table 4-9: Structure of the "dispatch.txt" gateway file
No.
1.
Syntax of a dispatch entry:
[<route source> <type source>
<address>]
target = <route target> <type
target> <address>
<route source>: Source driver routing
address
<type source>
<route target>
address
<type target>
<address>: Data point address
Note
For a data point to be used in the dispatch.txt
file, the data point must have previously been
declared in the driver-specific *.txt files.
For a driver's routing address and name, go to
2.
"General > Overview".
Note
In the dispatch file, you can use formulas for calculating data points. For more
information about this and the dispatch mechanism, please refer to Links &
Literature, \5\.
Communication with S7 CPU via KNX Gateway
Entry ID: 109739689,
V1.0,
Description
: Source driver name
: Target driver routing
: Target driver name
06/2017
Comment
# S7 --> KNX
[1190 pnetd outbyte 0]
target = 70 eib 1/1/2
[1190 pnetd outbit 2.0]
target = 70 eib 1/1/4
# KNX --> S7
[70 eib 1/1/1]
target = 1190 pnetd inbyte 0
[70 eib 1/1/3]
target = 1190 pnetd inbit 2.0
[70 eib 1/1/5]
target = 1190 pnetd inbyte 3