ARC GUARD SYSTEM™ – T VOC-2 INSTALL ATION AND MAINTENANCE GUIDE
4.2.3
Mounting TVOC-2-COM
Follow this steps to connect TVOC-2-COM module to the
Arc Monitor:
WARNING
Make sure that supply voltage is switched off!
1.
1
Remove the TVOC-2 HMI module from the Arc
Monitor by pressing on both sides on HMI and at
the same time.
2
Pull straight out from the Arc
Monitor.
INFORMATION
The removed TVOC-2 HMI module can be
mounted on the door.
See Mounting the HMI on door on page 21.
2.
3
Place the TVOC-2-COM into the Arc Monitor.
4
3.
Cut the cable casing 10 millimeters.
5
Insert the cable into the contact on the top of
the TVOC-2-COM
Figure 20
Remove the HMI
Figure 21
Place TVOC-2-COM
Figure 22
Fasten cable into the TVOC-2-COM
27
1SFC170011M0201
1SFC170011M0201
10 mm
0,2...1,5 mm
2
2
0,2...1,5 mm
+(B)
-(A) DGND
1SFC170011M0201