Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...
Page 2
POWER SUPPLY T H Y R O - S T H Y R I S T O R - S C H A LT E R T H Y R O - S 1 S . . . H 1 T H Y R I S T O R S W I T C H T H Y R O - S 1 S .
S A F E T Y I N S T R U C T I O N S The following safety and operating instructions must be carefully read before assembly, installation and commissioning. Obligation to give instructions The following safety and operating instructions must be carefully read before initial assembly, installation and commissioning of Thyro-A by those persons working with or on Thyro-A.
Page 4
The Thyristor switch may only be operated in the sense of its intended use, other- wise hazards to persons (e.g. electric shocks, burns) and systems (e.g. overload) may arise. Residual hazards of the product • Even in case of proper use, should a fault occur, it is possible that control of currents, voltages and power is no longer performed in the load circuit by the Thyristor switch.
Page 5
Different components in the power section are screwed into place using exact torques. For safety reasons, power component repairs must be performed by AEG SVS Power Supply Systems GmbH. S A F E T Y I N S T R U C T I O N S...
C o n t e n t s ➜ Safety instructions ➜ Safety regulations ➜ Remarks on the present operating instructions and Thyro-S ➜ Introduction General Specific characteristics Type designation ➜ Functions Operating modes overview 2.1.1 Digital set point value inputs Indications 2.2.1 Equipment temperature monitoring...
➜ Safety regulations Important instructions and explanations The skilled personnel assembling and disassembling the devices, commissioning them and maintaining them must know and observe these safety regulations. CAUTION This instruction indicates work and operating procedures to be obser- ved exactly to exclude hazards to persons. ATTENTION This instruction refers to work and operating procedures to be obser- ved exactly to avoid damage or destruction of Thyro-S or parts...
Page 9
(e.g. overload) may occur. Any unauthorized reconstruction and modification of Thyro-S, use of spare and ex- change parts not approved by AEG SVS as well as any other use of Thyro-S is not permitted. The person responsible for the system must ensure that...
Page 10
Guidelines The CE mark on the device confirms adherence to the general EC guidelines for 72/23 EEC – low voltage and for 89/339 EEC electromagnetic compatibility if the instructions on installation and commissioning described in the operating instructions are observed. Artisan Technology Group - Quality Instrumentation ...
Modification of information contained in these operating instruc- tions, especially technical data, operation, dimensions and weights, remain reserved at any time. AEG SVS reserves the right to content modifications and technical chan- ges within the present operating instructions without obligation to notification.
➜ Introduction Thyro-S meets the demands for simple assembly, speedy commissioning and safer operation. For transport, assembly, installation, commissioning, operation and decommissio- ning, it is essential that the safety instructions included in these operating instructions are observed and made available to all persons handling this product. In case of uncertainties or missing information, please contact your supplier.
1.3 Type designation The type designation of the Thyristor switch is derived from the construction of its power section: Thyro-S 1S Thyristor switch with single phase power section suited for single phase loads Beispiel ...400- with 400 Volt type voltage ...280 280 with 280 Amp type current with integrated semi-conductor fuse...
2.1.1 Digital set point inputs The Thyristor switch Thyro-S is equipped with two set point inputs which are electri- cally isolated from the mains for triggering signals: • Set point input 1 logic input 0-24V DC (R > 3.3 k ) IN: U >...
➜ 3. Operation 3.1 Configuration switch S1 A 2-pole DIP switch is situated at the front behind the hood. The individual switches are marked from 1-2 starting from the bottom and must be set before operation. They are only read in once when switched on (mains recovery). For safety reasons further operation is carried out with the hood closed.
➜ 4. External connections 4.1 Power supply for Thyro-S Connecting the power supply is carried out as shown in the figures and TECHNICAL DATA. 4.2 Power supply for the control device The control device is supplied directly from the power section (terminals U1, X1:1.2).
4.4 Block connection diagram Fig. 1: Block connection diagram and connecting plan The block connection diagram shows the functions of the H 1 design. Central control element is a -controller. Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
4.5 Connections and terminal strips This chapter describes all terminal strips and socket connectors. System interface Control ground (5 / 3.3 V) RM 3.5 RxD / connection to bus module TxD / connection to bus module Bus module recognition Ground Pos.
➜ 6. Mains load optimization Thyro-S is not suitable for mains load optimization in multiple controller applications. If mains load optimization is necessary, Thyristor controllers of type Thyro-A or Thyro-P must be used. 7. Connecting diagrams ➜ Thyro-S can be employed in single phase switch and in three phase switches which can be transposed to single phase switches, e.g.
➜ 8. Special remarks 8.1 Installation Thyro-S requires a vertical fitting position. With cabinet mounting sufficient ventila- tion of the cabinet must be ensured. The distance between the Power Controller and the cabinet ceiling or other mountings should be at least 150mm. The distance be- low the Power Controller should be at least 100mm.
8.4 Checklist • LED ON greenn lights up -> mains voltage available • LED ON green does not light up Check fuse control 500V 1.6 A, if defective, check external wiring, also applies to faults of external fusing, check Power Controller fusing. If fuse is defect then check load and wiring to load.
➜ 10. Technical data Type voltage 230 Volt -57% +10% 400 Volt -57% +10% 500 Volt -57% +10% Mains frequency all models 47Hz bis 63Hz; f=6Hz; max. frequency change 5% per half wave Load description ohmic load Operating modes Name Load signal, with digital set point = ON all full wave (default setting) every 2.
Page 25
Power connections Type current Connector U1, U2, Earthing Conductor screw cross sect. Screw plug-in terminal Bracket / M4 4 mm , max. 16 A Bracket / M4 Bracket / M4 6 mm , max. 30 A Bracket / M4 Bracket / M4 6 mm , max.
➜ 12. Accessories and options Order No. 8000 006 757 Support for 35 mm snap-on assembly for devices with type current 8A, 16A and 30A Order No. 2000 000 841 Bus module Profibus DP Order No. 2000 000 842 Bus module Profibus RTU ➜...
Page 30
Load class DIN EN 60 146-1-1 T.2 Humidity class DIN EN 50 178 Tab. 7 Overvoltage category ÜIII DIN EN 50 178 Tab. 3 Degree of pollution DIN EN 50 178 Tab. 2 Air pressure 900 mbar * 1000m above NN Safe isolation up to 500 V mains voltage: DIN EN 50 178 Chap.
Page 31
Weltweit ist AEG SVS auf allen wichtigen Märkten durch Vertriebspartner vertreten. AEG SVS is represented by sales partners in all important markets world wide. Die aktuellen regionalen Adressen finden Sie im Internet: http://www.aegsvs.de You can find the current adresses on the Internet: http://www.aegsvs.de...
Page 32
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...