8. Special remarks

8.1 Installation

Thyro-S requires a vertical fitting position. With cabinet mounting sufficient ventila-
tion of the cabinet must be ensured. The distance between the Power Controller and
the cabinet ceiling or other mountings should be at least 150mm. The distance be-
low the Power Controller should be at least 100mm. Heating up of the device by
heat sources must be avoided. The dissipation of the Power Controller is stated in
the Type overview table.
ATTENTION
Grounding must be carried out according to local electricity board
regulations! (grounding screw for protective conductor connection on
fastening adapter is provided).
The grounding also serves EMV devices (Y capacitor 4.7 nF).
For Thyro-S with type currents 8A, 16A or 30A an adapter can be delivered for the
35mm top-hat rail assembly.

8.2 Commissioning

The device must be connected to the mains and the associated load according to the
corresponding connecting plans.
On delivery the device is parameterized and adjusted to the respective power sec-
tion. If a different operating mode is desired, then it must be set with DIP fix 1 and
2 by the user (commissioning phase).
ATTENTION
Heat sinks and neighbouring plastic parts can become hot during
operation (Œ 70°C)! Provided sign should be fixed nearby Thyro-S.

8.3 Service

The devices delivered have been produced under quality standard ISO 9001.
Should nevertheless faults or problems occur, our
24-hour service hotline: Tel: 02902 / 763-100.
is at your service.