Electrical installation
Figure 4-5
Connection
When connecting the dV/dt filter compact plus Voltage Peak Limiter, you must take into
account the following conditions to ensure that it functions correctly:
● Control cables must be routed separately from power cables. Power cables are the motor
● You must use shielded motor cables. The shield for the motor cable must be attached to
● The ground wire for the motor must be fed directly back to the Power Module.
24
Interface overview dV/dt filter compact plus Voltage Peak Limiter - Voltage Peak Limiter,
Type 4
cable or the connecting cables from the DC link of the Power Module (terminals
DCPS/DCNS) to the dV/dt filter compact plus Voltage Peak Limiter. In particular, you
must ensure that control cables and power cables are not routed in parallel in a joint
cable raceway, even if all the cables are shielded.
the shield plate and motor housing.
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 03/2011, A5E02590131A