Remote Pressure Transmitter

Product Description

The Remote Pressure Transmitter (RPT) (Figure 1)
measures the difference in air pressure between a
room and an adjacent space. It sends that
measurement to the Differential Pressure Monitor.
This kit contains:
Remote Pressure Transmitter and inside
cover assembly
Outside cover assembly
One 12-inch airflow tube
Eight 1-1/4 inch tamper-resistant screws
Four wall anchors
Two removable wire connectors
Figure 1. Remote Pressure Transmitter (RPT).
Product Numbers
547-003
Revision: EA
AIRFLOW TUBE
OUTSIDE
COVER PLATE
INSIDE
COVER PLATE

Installation Instructions

Warning/Caution Notations
CAUTION:

Required Tools

Small flat-blade screwdriver
5/64-inch Allen key wrench
Wire strippers
Electric drill
2-inch hole saw
1/4-inch drill bit
Plastic tube cutter, pipe cutter, or hacksaw
Level
Tape measure
Volt-ohm meter
Expected Installation Time
15 minutes
Prerequisites
Electrical box and plaster ring in place
24 Vac Power cable in place
Pressure signal cable in place
CAUTION:
Do not apply 24 Vac power until the
installation is fully completed. If power is
applied and one of the heat sinks makes
contact with the electrical box, damage will
occur to the RPT.
Ratings
Power input: 24 Vac, 2.5 VA
Pressure signal: standard RS485
Document No. 540-369
November 15, 2006
Equipment damage or loss of
data may occur if the user does
not follow procedure as
specified.
Page 1 of 3

Advertisement

loading

Summary of Contents for Siemens RPT

  • Page 1: Installation Instructions

    Warning/Caution Notations Product Description CAUTION: Equipment damage or loss of The Remote Pressure Transmitter (RPT) (Figure 1) data may occur if the user does measures the difference in air pressure between a not follow procedure as room and an adjacent space. It sends that specified.
  • Page 2 SIEMENS LOGO IS AT THE BOTTOM 1. Verify that the electrical box, onto which the front (UPSIDE DOWN) part of the RPT will be mounted, is grounded. 6-18" NOTE: In Steps 2 through 5, you will determine (15.25 - 45.7cm) where, on the outside wall, to drill a 2- inch hole.
  • Page 3 Figure 3. Wiring Connections. Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. © 2000 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc.