Bosch Rexroth IndraDrive Project Planning Manual page 79

Additional components
Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents

Advertisement

Rexroth IndraDrive
Connection Cross Section
Loadability
Assignment
Circuit states
Shield connection
DOK-INDRV*-ADDCOMP****-PR02-EN-P
X31, Connection for Messages
Design
Type
Spring power
Fig. 8-12:
Design
Cross section
single-wire
[mm²]
0,08-1,5
Fig. 8-13:
Connection Cross Section
Max. switching voltage
Max. switched current
Max. continuous current
minimum load of
contacts
6
5
4
3
2
1
Ready for operation contact:
Contact is closed, if all of following conditions are met:
• control voltage present
• heat sink temperature OK
• load resistor temperature OK
• continuous power is smaller than specified (see Electrical Data)
• maximum regenerated power is smaller than specified (see Electrical
Data)
Prewarning contact:
Contact is open, if one of the following conditions is met:
• heat sink temperature is too high
• continuous power > 90%
• regenerated power > 90%
Connect the shields of the control lines to shield connection XS1 of the
neighboring drive controller.
DC Bus Resistor Unit HLB01.1C and HLB01.1D
Number of poles
6
Cross section
multi-wire
[mm²]
0,08-1,5
ready for operation contact
ready for operation contact
prewarning contact
prewarning contact
8-11
Type of design
female (connector)
Cross section
in AWG
Gauge-Nr.:
28 - 14
DC 30V
DC 1A
DC 1A
10 mA
n.c.
n.c.