[8-13 Parts Replacement Instructions ]
(22) Before removing the front heat exchanger, protect the surrounding electrical components and the pipe cover with a
recommended felt soaked in water, and then remove the braze from four areas. (See Figure 16)
To remove the rear heat exchanger, remove the braze from four areas. (See Figure 17)
Removal of the front heat exchanger
(Figure 16)
Notes for replacing refrigerant circuit components (heat exchanger)
Be sure to perform non-oxidized brazing.
After brazing is done, check that the brazing is done properly and check for leaks before vacuum-drying the pipes.
Direct the brazing torch flame away from the wiring and sheet metals inside the unit not to damage them.
Place the wet felt sheets listed below (or their equivalents) around the areas to be brazed to protect the heat
exchanger, pipes, and pipe covers from being damaged from the brazing torch flame.
Recommended felt sheets: Spatter felt 50CF-11 (5t x 1 m x 1 m) by TRUSCO Nakayama
Felt sheets that meet the JIS standard (JIS A 1323 type A "Flame retardant testing method for spark droplets of
welding and gas cutting on fabric sheets in construction works")
92
- chapter 8
Brazed area
Brazed area
Removal of the rear heat exchanger
(Figure 17)
HWE18220_GB