Mitsubishi Electric HP120TNU-A Service Handbook page 62

R410a
Table of Contents

Advertisement

[2-10 Restrictions on Refrigerant Pipes ]
Piping length and height between IU and BC controller
100
90
80
70
60
50
40
30
20
10
0
5
Height difference between the main BC controller
and indoor unit (m)
250
200
150
100
50
0
0
5
10
15
20
Height difference between Main BC controller
and farthest indoor unit (ft)
Fig. 2
Main
BC
SUB
Fig. 3
BC
Fig. 2
Fig. 2
IU
IU
Piping "A"size selection rule
Outdoor Model
HP72T/YNU
HP96T/YNU
HP120T/YNU
Piping "B", "C", "D", "E" size seleciton rule
Total down-stream Indoor capacity
P54 or less
P55-P72
P73-P96
Piping "a", "b", "c", "d", "e", "f", "g", "i", "j", "k", "m", "n" size selection rule
Indoor Unit size
P05-P18
P24-P54
P72
P96
Piping "F", "G", "J", "K" size selection rule
Total down-stream Indoor capacity
P72 or less
P73 to P108
P109 to P126
P127 to P144
P145 to P180
P181 to P234
P235 to P288
P289 to P360
P361 or above
HP: High pressure, LP: Low pressure
HWE18220_GB
10
15
25
30
35
40
45
Fig. 3
Fig. 3
*9. When the piping length or the vertical separation exceeds the limit specified in Fig. 2, connect
a sub BC to the system.
The restriction for a system with a sub BC connection is shown in Fig. 3.
SUB
When a given system configuration falls within the shaded area in Fig. 3, increase the size of
BC
the high-pressure pipe and the liquid pipe between the main BC and sub BC by one size.
The maximum liquid branch pipe diameter is ø19.05. If a given system already has a ø19.05-pipe
between the main BC and sub BC, there is no need to increase the pipe size.
When using P12, P15, P18, P36, or P48 model of indoor units, increase the size of the liquid
Fig. 2
branch pipe between the sub BC and indoor unit by one size.
When using indoor models P54 or larger, the restrictions shown in Fig. 2 cannot be exceeded.
IU
Pipe(High pressure)
Pipe(Low pressure)
ø15.88 [5/8"]
ø19.05 [3/4"]
ø19.05 [3/4"]
Pipe(Liquid)
ø9.52 [3/8"]
ø9.52 [3/8"]
ø9.52 [3/8"]
Pipe(Liquid)
ø6.35 [1/4"]
ø9.52 [3/8"]
ø9.52 [3/8"]
ø9.52 [3/8"]
Pipe(Liquid)
Pipe(HP Gas)
ø9.52 [3/8"]
ø15.88 [5/8"]
ø9.52 [3/8"]
ø19.05 [3/4"]
ø12.70 [1/2"]
ø19.05 [3/4"]
ø12.70 [1/2"]
ø22.20 [7/8"]
ø15.88 [5/8"]
ø22.20 [7/8"]
ø15.88 [5/8"]
ø28.58 [1-1/8"] ø28.58 [1-1/8"]
ø19.05 [3/4"]
ø28.58 [1-1/8"] ø34.93 [1-3/8"]
ø19.05 [3/4"]
ø28.58 [1-1/8"] ø41.28 [1-5/8"]
ø19.05 [3/4"]
ø34.93 [1-3/8"] ø41.28 [1-5/8"]
100
90
80
*9
70
60
50
40
30
20
10
0
5
Height difference between the main BC controller
and indoor unit (m)
300
250
*9
200
150
100
50
0
0
5
10
15
20
25
Height difference between Main BC controller
and farthest indoor unit (ft)
Selection criteria for joints_A
(mm [in.])
Total down-stream Indoor capacity
ø19.05 [3/4"]
-P72
ø22.20 [7/8"]
P73-P96
ø28.58 [1-1/8"]
Selection criteria for joints_B
Total down-stream Indoor capacity
(mm [in.])
-P120
Pipe(Gas)
P121-P216
ø15.88 [5/8"]
ø19.05 [3/4"]
ø22.20 [7/8"]
(mm [in.])
Pipe(Gas)
ø12.70 [1/2"]
ø15.88 [5/8"]
ø19.05 [3/4"]
ø22.20 [7/8"]
(mm [in.])
Pipe(LP Gas)
ø19.05 [3/4"]
ø22.20 [7/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
10
15
30
35
40
45
Joint
CMY-Y102SS-G2
CMY-Y102LS-G2
Joint
CMY-R201S-G
CMY-R202S-G
chapter 2 -
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents