Siemens 6ES7547-1JF00-0AB0 Manual
Siemens 6ES7547-1JF00-0AB0 Manual

Siemens 6ES7547-1JF00-0AB0 Manual

Simatic s7-1500/et 200mp communication module io-link master cm 8xio-link
Hide thumbs Also See for 6ES7547-1JF00-0AB0:

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Siemens 6ES7547-1JF00-0AB0

  • Page 2 Preface ___________________ Documentation guide ___________________ SIMATIC Product overview ___________________ ___________________ Connecting S7-1500/ET 200MP Communication module IO-Link Master CM 8xIO-Link ___________________ Parameters/address space (6ES7547-1JF00-0AB0) ___________________ Diagnostic alarms Manual ___________________ Technical specifications ___________________ Dimensional drawing ___________________ Parameter data record 03/2019 A5E45488510-AA...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    For environmentally friendly recycling and disposal of your old equipment, contact a certified electronic waste disposal company and dispose of the equipment according to the applicable regulations in your country. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 5 Siemens accepts no liability for the use of the open source software over and above the intended program sequence, or for any faults caused by modifications to the software.
  • Page 6: Table Of Contents

    Diagnostic alarms ........................29 Technical specifications ........................31 Dimensional drawing ..........................34 Dimensional drawing....................... 34 Parameter data record .......................... 36 Parameter assignment and structure of parameter data set ..........36 Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 7: Documentation Guide

    You can download the documentation free of charge from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109742691). Changes and supplements to the manuals are documented in a Product Information. You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/68052815). Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 8 You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/en). "mySupport" - Documentation In the Documentation area in "mySupport" you can combine entire manuals or only parts of these to your own manual.
  • Page 9 ● Performing a CPU memory reset ● Resetting devices to factory settings ● Downloading a firmware update to a device You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 10 You can find SIEMENS PRONETA on the Internet (https://support.industry.siemens.com/cs/ww/en/view/67460624). SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
  • Page 11: Product Overview

    ● Data transmission rate COM1 (4.8 kbaud), COM2 (38.4 kbaud), COM3 (230.4 kbaud) ● Standard DI mode ● Suitable for connecting up to eight IO-Link devices (3-wire connection) or eight standard encoders. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 12 ● U connector ● Universal front cover Additional information You can find more information on accessories in the ET 200MP Distributed I/O System (https://support.industry.siemens.com/cs/ww/en/view/59191792) system manual in the Accessories/Spare parts section. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 13: Functions

    IO-Link Standard as of V1.1. You can find additional information on the master backup functions in the section 'Integration into the automation system' in the IO-Link System (https://support.industry.siemens.com/cs/ww/en/view/65949252) function manual. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 14: Reset Communication Module To Factory Settings

    You should reset a removed IO-Link Master CM 8xIO-Link communication module to the factory settings before you place it in storage. Procedure To perform a "Reset to factory settings", proceed as described in the S7-PCT online help. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 15: Connecting

    Ensure that all devices are connected to the SELV/PELV power supply (or equivalent). NOTICE Internal transducer supply Use only the supply voltage (US /M) made available by the IO-Link Master CM 8xIO-Link communication module to supply the IO-Link device (L+/L-). Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 16 Port status/channel error LED (green/red) Supply voltage 24 V DC LED channel status in standard DI mode (green) Figure 3-1 Block diagram and terminal assignment for 3-wire and 5-wire connection of IO-Link devices Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 17 Port status/channel error LED (green/red) Supply voltage 24 V DC LED channel status in standard DI mode (green) Figure 3-2 Terminal assignment for 2-wire and 3-wire connection in DI operating mode Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 18: Parameters/Address Space

    Port Qualifier Information (PQI) Module Disable • Enable • Port configuration without S7-PCT Module Disable • Enable • The following table shows the port parameters for the IO-Link Master CM 8xIO-Link communication module. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 19 For the remaining ports, you can assign a total of 60 bytes of input data. Reference You can find additional information on the Vendor ID and Device ID on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109748852). Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 20: Declaration Of Parameters

    The setting of the port is granular and you can combine the operating modes as you like. IO-Link Autostart The connected IO-Link device starts automatically (Plug&Play functionality). The IO-Link device is immediately ready for operation. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 21 ● Type-compatible (V1.1) with Restore You can find instructions for determining the Vendor ID and Device ID on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109748852). The port operates as standard digital input. Deactivated The port is deactivated. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 22: Address Space

    Exceptions are 2 interface modules: IM 155-5 PN BA, which only supports 64 bytes, and IM 155-5 DP ST with a limit of 244 bytes per station. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 23 ● Configuration of the I/O data lengths for each port ● Activating the Port Qualifier Information (PQI) ● Port mode: – Operation in "IO-Link Autostart" mode (default) – Operation in "IO-Link Manual" mode – Operated as DI – Deactivated Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 24 1 byte together with the input data of the IO-Link device. PQI is not available for 8 bytes input / 8 bytes output. The figure below shows the structure of the PQI byte. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 25 In the example above, 16 bytes are set for port 1, the IO-Link device transfers the data in bytes 0 to 7 and the PQI byte is set to byte 15. Note Restriction The graphic only applies to the input range. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 26 Figure 4-3 Address space of the inputs of the IO-Link Master CM 8xIO-Link in standard DI mode Reference You can find additional information in the IO-Link System (https://support.automation.siemens.com/WW/view/en/65949252) function manual. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 27: Diagnostic Alarms

    Meaning of the LED displays The following tables show the meaning of the status and error displays. Remedial measures for diagnostic alarms can be found in the Diagnostic alarms (Page 29) chapter. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 28 Table 5- 2 POWER status display LED P Meaning Solution Supply voltage L+ too low or missing. Check the supply voltage L+. Supply voltage L+ is present and OK. On (green) Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 29 Status displays of LEDs Q1 to Q8 Q1 to Q8 Meaning Process signal = 0 in standard DI mode, deactivated or in IO-Link mode Process signal = 1 in standard DI mode On (green) Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 30: Diagnostic Alarms

    Could not configure IO-Link Master (1882 , 1883 • Storage error (1886 • Process data length exceeded (1887 • PQI not supported (1889 • Device was not configured correctly (6320 , 6321 , 6350 • Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 31 , 180D • More than 6 errors are pending simultaneously on the IO-Link • device (1808 Consistency error in electronic coding element (1885 • Process data length exceeded (1887 • Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 32: Technical Specifications

    1 A; 4 A total current per module Rated value • 24 V encoder supply Yes; per channel, electronic Short-circuit protection • IO-Link Number of ports of which simultaneously controllable • IO-Link protocol 1.0 Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 33 Yes; Green LED Channel status display • Yes; Red LED for channel diagnostics • Yes; Red LED for module diagnostics • Potential separation Potential separation channels between the channels • Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 34 The following derating curves show the load capacity of the transducer supply outputs in relation to the mounting position and the ambient temperature. ① Horizontal mounting of the system ② Vertical mounting of the system Figure 6-1 Derating curve, IO-Link master Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 35: Dimensional Drawing

    Always observe the specified dimensions for installation in cabinets, control rooms, etc. Figure 7-1 Dimensional drawing of the IO-Link Master CM 8xIO-Link module Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 36 Dimensional drawing 7.1 Dimensional drawing Figure 7-2 Dimensional drawing of the IO-Link Master CM 8xIO-Link module, side view with open front cover Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 37: Parameter Data Record

    The following table shows the module-specific error codes and their meaning for the parameter data record 128: Table A- 1 Error message Error code Meaning 80B1 Error in data length 80E0 Error in header information 80E1 Parameter error Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 38 A.1 Parameter assignment and structure of parameter data set Structure of data record 128 Figure A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Figure A-2 Header information Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 39 A.1 Parameter assignment and structure of parameter data set IO-Link start parameters The following figure shows the structure of the IO-Link start parameter. Activate a parameter by setting the corresponding bit to "1". Figure A-3 IO-Link start parameters Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 40 If you have selected IO-Link Manual operating mode, you must enter the Vendor ID (byte x+5 and x+6) and Device ID (byte x+7 to x+10) yourself. You can find the Vendor ID and Device ID in the IODD of the IO-Link device being used. Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...
  • Page 41 Parameter data record A.1 Parameter assignment and structure of parameter data set Figure A-4 Port parameter Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) Manual, 03/2019, A5E45488510-AA...

Table of Contents