30 Start-up and acceptance test

you must sign and store the acceptance test report for further reference.

Acceptance test reports

You must store the signed acceptance test reports in the logbook of the machine. The report
must include, as required by the referred standards:
a description of the safety application (including a figure)
a description and revisions of safety components that are used in the safety application
a list of all safety functions that are used in the safety application
a list of all safety-related parameters and their values
documentation of start-up activities, references to failure reports and resolution of failures
the test results for each safety function, checksums, date of the tests, and confirmation
by the test personnel.
You must store any new acceptance test reports performed due to changes or maintenance
in the logbook of the machine.
Start-up and acceptance test
You need the Drive composer PC tool to perform the start-up and acceptance test.
Action
Initial status
Safety encoder interface:
When you use a safety pulse encoder in the safety application, validate the safety encoder interface as
described in FSO-21 safety functions module user's manual (3AXD50000015614 [English]), chapter
Verification and validation.
Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up procedure.
See the hardware manual.
WARNING!
Obey the safety instructions. If you ignore them, injury or death, or damage to the equipment
can occur.
Checks and settings with no voltage connected
Stop the drive and do the steps in section
work.
After you have done the wiring to the POUS switch and to the indication lamp, check the connections
against the appropriate circuit diagrams. Make sure that the POUS request is not on (the POUS switch
is closed).
Inverter units with parallel R8i inverter modules:
Check that the XSTO.OUT output on the inverter control unit [A41] is chained to the STO inputs of all
inverter modules.
Settings with voltage connected
Close the cabinet doors and power up the drive. See the hardware manual.
Check the parameters that are relevant to the safety function. If necessary, set the parameters according
to your application needs as defined in section Parameter settings.
Create a backup file of the drive (button Backup/restore in the Drive composer pro PC tool).
Electrical safety precautions (page 8)
before you start the