CERBERUS® AlgoRex
Installation guidelines for fire detection
systems collective, interactive,
AnalogPLUS
Planning and realization
Specific national regulations are not integrated in this document
Fire & Security Products
Siemens Building Technologies Group

Advertisement

loading

Summary of Contents for Siemens CERBERUS AlgoRex Series

  • Page 1 CERBERUS® AlgoRex Installation guidelines for fire detection systems collective, interactive, AnalogPLUS Planning and realization Specific national regulations are not integrated in this document Fire & Security Products Siemens Building Technologies Group...
  • Page 2 Data and design subject to change without notice. / Supply subject to availability E Copyright by Siemens Building Technologies AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche...
  • Page 3: Table Of Contents

    ..........Acceptance test and handing over the system to the customer ..12.2001 Fire & Security Products Siemens Building Technologies Group...
  • Page 4 12.2001 Fire & Security Products Siemens Building Technologies Group...
  • Page 5 This document is intended for planning engineers in all national sales organiza- tions. Local standard practices, regulations, languages etc that vary from this doc- ument must be taken into account and and documented by the national sales orga- nizations. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 6: Planning

    Fire detection system control unit Response indicator (Model ...) Signalling, e.g. mimic panel, Special devices terminal etc. (Model ...) (Model ...) Fig. 2 Planning symbols (ISO/DIS 6790.2) Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 7 Input / output module Electromagnetic compatibility Electromagnetic influence Fire detection system Fire detection system control unit Explosion hazard area Extra low voltage Voltage <50V Low voltage Voltage <1000V Shunt-Zener-Diode barrier Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 8: Basic Wiring Layout Of A Fire Detection System

    Fuse Door magnet line CT.. Door magnet line Line to remote transmission system for alarms and faults Extra-low voltage 16...30V Low voltage 110...240V Fig. 3 Basic fire detection system layout Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 9: Fire Detection System Line Network

    All equipment is largely protected against EMI. Nevertheless, the following precautions are necessary: Maintain the greatest possible distances from thyristor control cables, high voltage lines, lightning protection systems, transmitter cables etc. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 10 Not recommended for new systems Upper level Ground floor È È È È È DC1192 È È È È È 1,5mm 240V~/10A CT.. CC/CI.. Basement level Fig. 4 Block diagram «collective» detection system Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 11 È È È (HD) È È È (HD) (HD) (HD) (HD) Detection line (HD) false ceiling Fire detection system control unit Response indicator line (HB) raised floor Fig. 5 Collective wiring Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 12 DC1135 Ground floor DC1134 DC1135 DC1192 È È È È È È È È 1,5mm 240V~/10A CT.. CC/CI.. Basement level DC1134 DC1135  Fig. 6 Block diagram detection system AnalogPLUS Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 13 È È È (HD) È È È (HD) (HD) (HD) (HD) (HD) Loop line (HD) false ceiling Fire detection system control unit Stub line (HB) raised floor  Fig. 7 AnalogPLUS wiring Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 14 Not recommended for new systems Upper level DC1154 Ground floor DC1192 È È È È È È È È DC1154 1,5mm 240V~/10A CT.. CC1140 Basement level DC1154 Fig. 8 Block diagram «interactive» detection system Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 15 È È È (HD) È È È (HD) (HD) (HD) (HD) (HD) Loop line (HD) false ceiling Fire detection system control unit Stub line (HB) raised floor Fig. 9 Interactive wiring Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 16 Remote transmission equipment or danger management systems mounted separately from the control unit must be wired according to the corresponding manufacturer’s instructions. 1.3.14 Standards In general, the standard IEC 950 also applies (International Electrical Commission) Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 17: Installation

    If required, two different designation plates are available for the marking of detectors. They are attached under the detector base after installation. As component parts of a fire detection system, terminal boxes, distributor boxes, loop- ing-in boxes must be marked accordingly. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 18: Installing The Equipment

    The response indicator in the base must be easily visible from the alarm investigation route. Response indicator Fig. 11 Response indicator clearly visible See product packing sheets, for further details. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 19 Í Í Í Í Í Í Í Í Í Í Í Fig. 13 Making the rubber membrane air-tight Important: Push the cable through the rubber membrane, or make holes with an awl. Do not cut holes or slits! Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 20 Equipment for explosion-hazard areas must be installed and earthed according to docu- ment e1204, «Fire detection in explosion-hazard areas». Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 21: Wiring Check

    The installer is obliged to hand over to the commissioning engineer a correctly installed and tested supply network. Any deficiencies are normally eliminated and the work charged to the installer. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 22: Commissioning

    The acceptance procedure varies from country to country. It can be done by an accep- tance inspector or by the customer himself. The system is handed over to the customer who is given thorough training based on com- prehensive operating instructions. Fire & Security Products e1453b Siemens Building Technologies Group 12.2001...
  • Page 23 Fire & Security Products Back Siemens Building Technologies Group 12.2001...
  • Page 24 Siemens Building Technologies AG Alte Landstrasse 411 CH 8708 Männedorf Tel. +41 1 − 922 61 11 +41 1 − 922 64 50 www.cerberus.ch Fire & Security Products Back Document no. e1453b Manual DS11 Siemens Building Technologies Group 12.2001 Edition 12.2001...